ML18086B121

From kanterella
Jump to navigation Jump to search
Responds to NRC Re Violation Noted in IE Insp Repts 50-272/81-25 & 50-311/81-25.Corrective Actions:Area Immediately Posted as Airborne Radioactivity Area & Caution Note Inserted Into Radiation Instruction 1.010
ML18086B121
Person / Time
Site: Salem  
Issue date: 12/04/1981
From: Schneider F
Public Service Enterprise Group
To: Haynes R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
NUDOCS 8112090166
Download: ML18086B121 (3)


Text

Public Service Electric and Gas Company Frederick W. Schneider 80 Park Plaza, Newark, NJ 07101 201-430-7373 Mailing Address: P.O. Box 570, Newark, NJ 07101 Vice President -

Production and Assistant to Senior Vice President -

Energy Supply*and Engineering Mr. R. C. Haynes, Regional Administrator December 4, 1981 U.S. Nuclear Regulatory Commission Region 1 631 Park Avenue King of Prussia, Pa.

19406 Attention:

Mr. R. R. Keimig, Chief Projects Branch #2, Division of Resident and Project Inspection NRC INSPECTION 50-272/81-25 AND 50-311/81-25 UNIT NOS. 1 AND 2 SALEM GENERATING STATION Gentlemen:

We have reviewed the report of your inspection conducted by Mr.

L. Norrholm during the period September 15 to October 19, 1981.

Our response to the violation described in Appendix A is as follows:

Item of Violation 10 CFR 20.203(d) states in part:

"Airborne radioactivity area" means (i) any room, enclosure, or operating area in which air-borne radioactive materials composed wholly or partly of licensed material, exist in concentrations in excess of the amounts specified in Appedix B, Table 1, Column l... Each airborne radio-activity area shall be conspicuously posted with a sign or signs bearing the radiation caution symbol and the words:

Caution (or "Danger")

AIRBORNE RADIOACTIVITY AREA 10 CFR 20, Appendix B, Table 1 lists in part, XE 133... 1 E-5 uCi/ml.

Contrary to the above, approximately 11:00 a.m. on October 2, 1981, the Xe 133 concentration in Unit 1 containment exceeded the limit in 10 CFR 20, Appendix B, Table 1.

The containment air sample, No. 14756-81, obtained with a 100 cc Johnson Bomb at approximately 1:26 a.m. on October 2, 1981, indicated Xe 133 (5.29 day half-life)

( 8112090166811'">0~

~DR ADOCK 05000272

r NRC Inspection 50-272/81-25 12/4/81 and 50-311/81-25 Units Nos.

1 and 2 Salem Generating Station concentration was 1.42 E-3 uCi/cc.

No sign indicating airborne radioactivity was posted in the vicinity of the containment.

Reply to the Item of Violation The area was immediately posted as an AIRBORNE RADIOACTIVITY AREA.

A caution note has been inserted into Radiation Protection Instrution 1.010, pertaining to noble gas concentrations, which states:

"Posting requirements for noble gases are the same as those for particulate airborne radioactivity".

All Radiation Protection Department personnel will be provided additional instructions on the requirements of the cited regulation and the procedure to be followed by January 1, 1982.

We feel that these corrective actions which have been or will be completed in the near future will effectively preclude the recurrence of this violation, therefore,* no further action on this item is necessary.

Sincerely,

-!21~

CC Director, Office of Inspection and Enforcement Nuclear Regulatory Commission Washington, D.C.

20555

.. --.~-V STATE OF NEW JERSEY SS:

COUNTY OF ESSEX COUNTY OF ESSEX FREDERICK W. SCHNEIDER, being duly sworn according to law deposes and says:

I am a Vice President of Public Service Electric and Gas Company, and as such, I find the matters set forth in our response dated December 4, 1981, to the NRC's combined inspection report 50-272/81-25 and 50-311/81-25 are true to the best of my knowledge, information and belief.

Subscribed and sworn to before me this __

-/~' _day of,.~ncf0c_._.,_ 1981

(

\\,..

~;11vr~

Notary Public of New Jersey My Commission expires onr? *;;:,/:?JO