~--oJ'
- .derick W. Schneider ce President Public Service Electric and Gas Company 80 Park Place Newark, N.J. 07101 201/430-7373 Production Mr. Boyce H. Grier, Director Office of Inspection and Enforcement Region 1 U. S. Nuclear Regulatory Commission 631 Park Avenue King of Prussia, Pennsylvania 19406
Dear Mr. Grier:
SUPPLEMENTAL REPORT NRC INSPECTiON REPORT NO. 50-272/77-13 INSPECTION DATE APRIL 12, 1977 NO. 1 UNIT SALEM GENERATING STATION April 8, 1980 In this Supplemental Report, we are informing you of a change to our previous response dated May 20, 1977 to the NRC, with respect to starting a reactor coolant pump while the reactor is critical.
The previous response indicated Operating Instruction (OI)
II-1.3-1 was revised to include step 3.il, Do not start a Reactor Coolant Pump wh;ile the reactor is critical."
A plastic tag was placed on the control console as a warning to Control Operators that three loop operation above P-7 is not allowed.
On December 27, 1979,
- an on-the-spot change was implemented to the Operating Instructions which deleted. the above commitment.
The change was implemented following a detailed review by PSE&G and Westinghouse which now permits the starting of a reactor coolant. pump with the reactor below P-7 (10%).
g 00416*0 z..tft
J
'-4---.
Mr. Boyce 4/8/80 Procedural guidance includes that following a loss of a reactor coolant pump with the reactor critical and no associated reactor trip, reactor power shall be reduced as quickly as possible, in a controlled manner, to less than P-7 (10%) within one hour.
If you require additional information, we will be pleased to discuss it with you.
Sincerely, CC:
Director, Office of Inspection and Enforcement U. S. -Nuclear Regulatory Commission Washington, D. C. 20555
~ '..