. JUl 2 i, 1979.
,/*
MEMORANDUM FOR:
A. Schwencer, Chief, Operating Reactors Branch #1~
Division *of Operating*.Reactors FROM:':
G. La-inas, Chief, Plant Systems Branch,. Division of Operating Reactors
SUBJECT:
.SALEM UNIT 1, REQUEST FOR ADDITIONAL INFORMATION 8BR DEGRADED GRID.VOLTAGE (TAC 10050)
Plant Name:
Salem Unit l Dock~t *No.;. 50-272.
Responsible Branch:.
O~B #1 Project Manager:
D. Ross.*
Reviewing Branch:
Plant Systems Branch Status:
Awaiting Information
- Iri response*to* technical assistance' request TAC 10050, the Plant
- *Systems Branch has reviewed the 1 i'censee~s sub.initta 1 of August l, l 97T and. found that. additional informatfon is required in order to complete' our review.
The attached request for additional infonnation should be for~farded.*
to the licensee as soon-as possible with a request for response. within 45 days.
- / ~
G. Lainas, Chief
-Pl ant Systems Branch Div_ision of Operating Reactors
Contact:
- s. Rhow, g28077
- C. Cleveland, EG&G
Enclosure:
As stated
,-) *.
OP'P'IClli!l> ~~-.. -~~~~~~~pft}..*. -Uf!:~~,..
GURNAMl!l~.. 7/J~"/79'""""""".. -*77"j*~*i:i9'"""" -",/:W"/79"""""".................................. _
....................................................... *****************.********* ***************************************\\************* **********************
DATl!l~
mtC POP.M 318 (9*76) NRCM 0240
- u.s. GOVERNMENT PRINTING OFFICE: to1a' - 28!1 - 709
UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 JUL 201979 MEMORANDUM FOR:
A. Schwencer, Chief, Operating Reactors Branch #1, Division of Operating Reactors FROM:
G. Lainas, Chief, Plant Systems Branch, Division of Operating Reactors
SUBJECT:
SALEM UNIT 1, REQUEST FOR ADDITIONAL INFORMATION FOR DEGRADED GRID VOLTAGE (TAC 10050)
Plant Name:
Salem Unit 1 Docket No.:
50-272 Responsible Branch:
ORB #1 Project Manager:
D. Ross Reviewing Branch:
Plant Systems Branch Status: Awaiting Information In response to technical assistance request TAC 10050, the Plant Systems Branch has reviewed the licensee's submittal of August 1, 1977 and found that additional information is required in order to complete our review.
The attached request for additional information should be forwarded to the licensee as soon as possible with a request for response within 45 days.
Contact:
S. Rhow, X28077 C. Cleveland, EG&G
Enclosure:
As stated
~7 j.-/ -*
//
/:'
I
,..* _/
~.,.,,-*1.....,.
- r1-
/ \\ r-... -
/'.
G. Lainas, Chfef Plant Systems Branch Division of Operating Reactors
cc w/enclosure:
D. Eisenhut W. Gammill B. Grimes D. Ross G. Lainas D. Tondi M. Chiramal P. Shemanski S. Rhow C. Cleveland, EG&G REQUEST FOR ADDITIONAL INFORMATION SALEM UNIT l DEGRADED GRID VOLTAGE (TAC 10050)
Based on our review of submittal dated August 1, 1977 we have concluded that your claims that the grid voltage at your station does not degrade below 90% of normal voltage as the basis for not proposing any modrLfication to your undervoltage protection scheme, is not acceptable.
Hence, we require that you provide your proposed design modification and changes to the Technical Specifications based on the guidance contained in the staff positions submitted to you by our letter dated June 2, 1977.