ML18079A325

From kanterella
Jump to navigation Jump to search
Responds to IE Bulletin 79-03.No safety-related Pipe Assemblies from Youngstown Welding & Engineering Co Are Used
ML18079A325
Person / Time
Site: Salem  
Issue date: 04/04/1979
From: Schneider F
Public Service Enterprise Group
To: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
NUDOCS 7905290065
Download: ML18079A325 (2)


Text

--

Frederick W. Schneider Vice President Public Service Electric and Gas Company 80 Park Place Newark, N.J. 07101 201 /430-7373 Production April 4, 1979 Mr. Boyce H. Grier, Director U.S. Nuclear Regulatory Commission Off ice of Inspection and Enforcement Region 1 631 Park Avenue King of Prussia, Pennsylvania 19406

Dear Mr. Grier:

NRC IE BULLETIN NO. 79-03 NO. 1 AND 2 UNITS SALEM GENERATING STATION In response to your letter of March 12, 1979, transmitting NRC IE Bulletin No. 79-03 which was received on March 13, 1979, we have investigated this matter with respect to applicability to Salem No.*l and 2 Units.

The following are the results of our investiga-tion:

The subject bulletin which questioned incomplete fusion in type 304 and 316 SA-312 welded pipe, manufactured before mid November, 1978 by Youngstown Welding and Engineering Company, has been evaluated by the PSE&G Engineering Department.

PSE&G has determined that Salem Generating Station Units No. 1 and 2 have no safety-related pipe assemblies manufactured from the aforementioned material.

The following procedure was used to arrive at this conclusion.

  • The PSE&G Quality Assurance Department required Youngstown Welding and Engineering Company to list all their heat numbers for the above fusion welded pipe material supplied to the following fabricators and vendors:

79052900~5

Mr. Boyce 4/4/79

1.

Pullman Power Products of Los Angeles

2.

Dravo Corporation

3.

Chicago Bridge and Iron

4.

Flowline Corporation

5.

ITT Grinnell Industrial Piping Inc.

6.

Albert Pipe Supply

7.

Guyon Alloys

8.

Allegheny Ludlum Steel Corporation Youngstown's synopsis of all heat numbers for the above fabricators and vendors was run through Quality Assurance Department's computer at Salem, and no pipe assemblies manufactured from the above welded stainless steel were found to be present.

If you require any further information, we will be pleased to discuss it with you.

Sincerely, CC:

NRC Office of Inspection and Enforcement Division of Reactor Construction Inspection Washington, D. C. 20555 Mr. L. J. Norrholm NRC, Hancocks Bridge, N.J.