ML18064A861

From kanterella
Jump to navigation Jump to search
Redundant DG Circuits Not Being Separated Per App R,Resulting in Condition Outside Design Basis of Plant.Two New Commitments Listed
ML18064A861
Person / Time
Site: Palisades Entergy icon.png
Issue date: 08/14/1995
From: Haas K
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML18064A862 List:
References
NUDOCS 9508210071
Download: ML18064A861 (1)


Text

consumers Power POW ERi Nii lllllCHlliAN"S l'IUlliRESS Palisades Nuclear Plant: 27780 Blue Star Memorial Highway, Covert, Ml 49043 August 14, 1995 U S Nuclear Regulatory* Conunission Document Control Desk Washington, DC 20555 DOCKET 50-255 - LICENSE DPR PALISADES PLANT KurtM. Haas Plant Safety and Licensing Director LICENSEE EVENT REPORT 95-004 - REDUNDANT DIESEL GENERATOR CIRCUITS NOT SEPARATED PER APPENDIX R Licensee Ev~nt Report (LER} 95-004 is attached. This event is reportable in accordance with 10 CFR 50.73(a}(2}(ii}(B} as a condition outside the design basis of the plant.

SUMMARY

OF COMMITMENTS This letter contains two new conunitments as follows.

1.
Provide a resolution for the lack of proper Appendix R circuit

. separation between the diesel generator 1-2 power and control circuits routed in the air intake pl~num to diesel generator 1-1 room.

2.

Maintain an hourly fire tour for diesel generator room 116 until a permanent resolution is provided for Appendix R circuit separation between the diesel generator 1-2 power and control circuits routed in the air intake plenum to diesel generator 1-1 room.

Kurt M. Haas Plant Safety and Licensing Director

. CC Admiriistrator, Region III, USNRC.

Project Manager, NRR, USNRC NRC Resident Inspector - Palisades Attachment n

J 9508210071 950814 PDR ADOCK 05000255 S

PDR A CMS' ENERGY COMPANY