consumers Power l'OWEIUll&

MICHlliAll"5 l'IUl&llOS Palisades Nuclear Plant: 27780 Blue Star Memorial Highway, Covert, Ml 49043 June 21, 1995 U S Nuclear Regulatory Commission ATTN:

Document Control Desk Washington, DC 20555 DOCKET 50-255 - LICENSE DPR PALISADES PLANT KurtM. Haas Plant Safety and Licensing Director LICENSEE EVENT REPORT 95-003 - MAIN-FEEDWATER PUMP TRANSIENT RESULTING IN A REACTOR TRIP Licensee Event Report {LER)95-003 {Main Feedwater Pump Transient Resulting in a Reactor Trip) is attached. This event is reportable to the NRC per 10CFR50.73{a){2){iv).

SUMMARY

OF COMMITMENTS This letter contains 3 new commitments. These commitments are as follows:

1.

The failure mode of the "A" Main Feedwater Pump {MFP) layshaft lockwasher locking tab will be determined and appropriate changes to both MFPs will be made.

2.

The feedwater control system changes suggested by a 1992 ABB report will be evaluated.

Proposed changes on the response of the feedwater system for other events will be evaluated and appropriate changes implemented.

3.

The MFP governor control setpoint of 5250 RPM and its relationship to the overspeed trip setpoint will be evaluated and suitable changes implemented.

.{;vvv~--

Kurt M Haas Plant Safety and Licensing Director CC Administrator, Region III, USNRC Project Manager, NRR, USNRC NRC Resident Inspector - Palisades 0 ~1r1 -"'

Attachment '* / u l' 9506290192 950621 PDR ADOCK 05000255 S

PDR

,..q CH5 E'NE'RGY COMP~NY