ML18057B304
| ML18057B304 | |
| Person / Time | |
|---|---|
| Site: | Palisades |
| Issue date: | 09/27/1991 |
| From: | Slade G CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.) |
| To: | NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM) |
| Shared Package | |
| ML18057B305 | List: |
| References | |
| NUDOCS 9110080303 | |
| Download: ML18057B304 (1) | |
Text
- .
(
consumers Power POW ERi Nii MICHlliAN'S PROliRESS Palisades Nuclear Plant:
27780 Blue Star Memorial Highway, Covert, Ml 49043 September 27, 1991 Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 DOCKET 50-255 - LICENSE DPR PALISADES PLANT -
q B Slade General Manager REVISION TO PROPOSED TECHNICAL SPECIFICATION - CONTAINMENT AIR COOLER DESIGN Consumers Power Company _(CPC) submitted a Technical Specification Change Request on October 20, 1986 which included a correction to Specification 5.2.3.a~ The NRC issued Amendment.No. 104 to the Palisades License on March 24, 1987 stating that the proposed change to Specification 5.2.3.a. would be the subject of future action.
On April 30, 1987, CPC submitted a revision to the October 20, 1986 submittal which included a correction to Specification 5;2.3.a., however, no amendment was issued which included this revision.
Since that time, CPC has completed an evaluation of the containment air cooler design.
The results of this evaluation are included in a report (NESE 923) prepared by American Air Filter entitled, "Investigation of Cooler Performance
. Prediction for Containment Air Coolers at the Palisades Nuclear Station", dated October 6, 1989. The results presented in that report indicate that with a total flow of 5580 gpm and an inlet temperature of 85°F the three Containment Air Coolers have a design heat removal rate of 230 x 106 BTU/hr.
Therefore, cpc*
proposes the following change to the previously proposed Specification 5.2.3.a:
"... Three units, with a total cooling water flow of 5580 gpm and with an inlet temperature of 85°F, will remove 230 x 106 BTU/hr of heat."
A corrected page change is included.
- ~/~:C.-...-....__ ____
General Manager CC Administrator, Region III, USNRC NRC Resident Inspector - Palisades Attachments 9110080303 *'9-1092;7
- -PDR---~ADOCK
- 05000255*
- p... *
~- - -PDR vt!l!Ju~
A CMS ENERGY COMPANY