ML18057B189

From kanterella
Jump to navigation Jump to search
Requests Withdrawal of 910325 & 0501 Tech Spec Change Requests Re Local Leak Rate Testing of Personnel & Emergency Escape Airlocks.Util Will Continue Practice of Seal Contact Check & Seal Fluffing
ML18057B189
Person / Time
Site: Palisades 
Issue date: 07/29/1991
From: Slade G
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 9108050259
Download: ML18057B189 (1)


Text

consumers Power POW ERi Nii NllCHlliAN'S PROliRESS Palisades Nuclear Pla_nt:

27780 Blue Star Memorial Highway, Covert Ml 49043 July 29, 1991 Nuclear Regulatory Commission

~ LICENSE DPR PALISADES PLANT -

GB Slade

-GeneriirManager --

WITHDRAWAL OF TECHNICAL SPECIFICATIONS C~ANGE REQUEST - LOCAL LEAK RATE

.JESTING OF-THE PERSONNEL AND EMERGENCY *ESCAPE AIRLOCKS

.~.:

Consumers, Pbwer Company requests withdrawal of the Technical Specification Change Request (TSCR) dated March 25~ 1991 and supplemented on May 1, 1991*

concerning the Local Leak Rate Testing of the Personnel and Emergency Escape Airlocks.*

Review of the lSCR by the NRC Technical Staff resulted in a number of concerns being raised.

Re solution of those concerns necessitates* further act i.on by the plant staff~ These actions include; (1) additional testing to determine whether or not reduced pressure between the seals testing, at a pressure less than the current 10 psig allowed by our Technical Specifications, can be successfully performed on the emergency escape airlock and (2) evaluating a modification, based on the results of (1), to the emerg~ncy escape airlock to facilitate reduced pressure between the seals testing. Furthermore, until items (1) ~nd (2) above are resolved, we will continue the practice of performing a seal contact check and seal fluffing (when necessary) as described in ~ur previous correspondence dated June 30, 1989.

Although the concerns appear to be resolvable, we do not wish to pursue further action on this issue at this time.

~

GBSlade General Manager CC Administrator, Region III,.USNRC NRC Resident Inspector, Palisades A CMS' ENERGY COMPANY