consumers Power POW ERi Nii MICHlliAN"S PRDliRESS General Offices: 1945 West Parnall Road, Jackson,' Ml 49201 * (517) 788-0550 March 1, 1990 Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 DOCKET 50-255 - LICENSE DPR PALISADES PLANT -

VIKING INDUSTRY POTTED CONNECTOR REPLACEMENT SCHEDULE As committed in our docketed correspondence of February 6 and February 7, 1990, we have attached a summary of the current Viking connector replacement sched-ule.

This schedule reflects the results of a review performed by Operations and Engineering personnel to ensure that connectors with the greatest opera-tional significance are replaced on a priority basis.

Although some connectors are not scheduled for replacement until Fall 1990, we are currently working to complete the modification packages for replacement of affect-ed Viking connectors as soon as possible, regardless of modification implemen-tation schedule.

It is our intent to replace as many of the affected Viking connectors as possible during the 1990 Spring Maintenance Outage which is presently sched-uled to begin in mid-April.

Total replacement of these connectors cannot be supported during this outage due to the limited availability of replacement connectors, splice kits, and other related hardware.

It is antici-pated that the replacement connectors, splice kits, and hardware will be available to complete replacement of the affected Viking connectors during the 1990 Fall Refueling Outage, which is scheduled to begin in September.

Brian D Johnson Staff Licensing Engineer CC Administrator, Region III, USNRC NRC Resident Inspector - Palisades OC0290-0294-NL04

~----------

--~

900~1?010~ 900~01

.. L PDR ADOCK 05000255 P

PDC 1

A CMS' ENERGY COMPANY

!11}1

/1~\\'

OC0290-0294-NL04 ATTACHMENT CONSUMERS POWER COMPANY PALISADES PLANT DOCKET 50-255 VIKING INDUSTRY POTTED CONNECTORS CURRENT REPLACEMENT SCHEDULE MARCH 1, 1990 2 Pages

VIKING INDUSTRIES POTTED CONNECTOR REPLACEMENT SCHEDULE Affected EEQ Instrument Circuits:

Canister/Connector Equip ID Replacement Schedule Z-142/4 FE-1039 1990 Fall Refueling Outage Z-142/5 FE-1040 1990 Fall Refueling Outage Z-142/6 FE-1041 1990 Fall Refueling Outage Z-142/7 FE-1042B 1990 Fall Refueling Outage Z-142/8 FE-1043B 1990 Fall Refueling Outage Z-243/2 TE-0122HB 1990 Spring Maintenance Outage Z-243/2 TE-0122CB 1990 Spring Maintenance Outage Z-243/2 TE-0112HB 1990 Spring Maintenance Outage Z-243/2 TE-0112CB 1990 Spring Maintenance Outage Z-243/2 PT-0102B 1990 Spring Maintenance Outage Z-243/6 PT-0104B 1990 Spring Maintenance Outage Z-246/6 LT-0751D 1990 Spring Maintenance Outage Z-246/6 LT-0752D 1990 Spring Maintenance Outage Z-246/6 PT-075 lD 1990 Spring Maintenance Outage Z-246/6 PT-0752D 1990 Spring Maintenance Outage Z-246/8 PT-0102D 1990 Spring Maintenance Outage oco290...:0294-NL04

Affected EEQ Control Canister/Connector Z-121/2 Z-121/2 Z-121/2 Z-121/2 Z-121/9 Z-121/10 Z-121/11 Z-121/12 Z-121/13 Z-121/14 Z-121/23 Z-121/23 Z-221/13 Z-221/14 Z-221/14 Z-221/15 Z-221/15 Z-221/24 Z-221/24 Z-221/24 Z-221/24 Z-221/1 Z-222/2 OC0290-0294-NL04 VIKING INDUSTRIES POTTED CONNECTOR REPLACEMENT SCHEDULE Circuits:

Equip ID Replacement Schedule POS-0867 1990 Spring Maintenance Outage POS-0869 1990 Spring Maintenance Outage SV-0867 1990 Spring Maintenance Outage SV-0869 1990 Spring Maintenance Outage M0-3007 1990 Spring Maintenance Outage M0-3009 1990 Spring Maintenance Outage M0-3011 1990 Spring Maintenance Outage M0-3008 1990 Spring Maintenance Outage M0-3013 1990 Spring Maintenance Outage M0-3010 1990 Spring Maintenance Outage POS-2113 1990 Spring Maintenance Outage SV-2113 1990 Spring Maintenance Outage M0-3062 1990 Spring Maintenance Outage M0-3012 1990 Fall Refueling Outage M0-3064 1990 Fall Refueling Outage M0-3014 1990 Fall Refueling Outage SV-3069 1990 Fall Refueling Outage POS-0864 1990 Fall Refueling Outage POS-0865 1990 Fall Refueling Outage SV-0864 1990 Fall Refueling Outage SV-0865 1990 Fall Refueling Outage M0-3066 1990 Spring Maintenance Outage M0-3068 1990 Spring Maintenance Outage