consumers Power company General Offices: 212 West Michigan Avenue, Jeckson, Mi 49201 * (617) 788-0650 August 10, 1981 Director, Nuclear Reactor Regulation Att Mr Dennis M Crutchfield, Chief Operating Reactors Branch No 5 U S Nuclear Regulatory Commission Washington, DC 20555 DOCKET 50-255 - LICENSE DPR PALISADES PLANT - SEP TOPIC III-4.C, INTERNALLY GENERATED MISSILES By letter dated July 20, 1981, the NRC transmitted for comment a draft evalua-tion of SEP Topic III-4.C for the Palisades Plant.
Consumers Power Company has reviewed this document and provides the following comments for your consideration:
- 1.
Page 7, first paragraph - Primary Coolant Pump flywheel integrity was addressed in Topic III-10.B.
- 2.
Page 13, second paragraph - 350°F should be 325°F.
- 3.
Page 14, second paragraph - The CCW pumps and heat exchanges are on the 590' elevation which is essentially at grade level.
- 4.
Page 17, last paragraph - This paragraph is somewhat confusing.
Three high pressure air compressors are installed in the plant..
- One is in each engin-eered safeguards room, and the third is in the turbine building.
As stated, the non-safety related turbine building system is normally isolated from the safety-related systems in the engineered safeguards rooms.
The safety-related systems are missile-protected by virtue of their locations in the engineered safeguards rooms.
- 5.
Page 24, first paragraph - The sampie line delay coil has been removed.
Also, it is not clear what steel shield wall protects the sample panel un-less it is. the steel panel enclosure itself.
The panel is located in a small room which has concrete walls.
- 6.
Page 25 - third paragraph - The containment sump gravity drains to the dirty waste drain tank.
( 0108140:281 810810 :-'\\J
\\ PDR ADdCK 05000255
\\ p
- PDR,
{
.l._....,...;..
'\\
August 10, 1981 Page Two
- 7.
Page 26 - third paragraph - It is not clear what is meant by the statement that the battery auxiliary systems are independent.
If auxiliary systems imply the chargers and de busses, this statement is correct.
Robert A Vincent Staff Licensing Engineer CC Director, Region III, USNRC NRC Resident Inspector-Palisades