Text
General Offices: 212 West Michigan Avenue, Jackson, Michigan 49201 * (617) 788-<1650 June 2, 1981 Director, Nuclear Reactor Regulation Att Mr Dennis M Crutchfield, Chief Operating Reactors Branch No 5 US Nuclear Regulatory Commission W~shington, DC 20555 DOCKET 50-255 - LICENSE DPR PALISADES PLANT - EDITORIAL CHANGES TO TECHNICAL SPECIFICATIONS CHANGE REQUEST - S/G INSPECTION PROGRAM Consumers Power Company submittal of May 5, 1981 requested changes to Palisades Technical Specification 4.14, Steam Generator Inspection Program.
Since that submittal we have determined that the following editorial changes should be made to the text:
(1).
Page 2 of submittal, Table 4.14.1 - change 440 KHz to 400 KHz.
( 2).
Page 3 of submittal, paragraph 4.14.. 4.should be changed to read;_
"Sleeves shall be installed such that, considering the axial location tolerances, swagging does not take place in an area of known degrada-tion.
A baseline ET inspection of all newly installed sleeves shall be performed.
In addition, all previously installed sleeves shall be inspected or plugged during subsequent steam generator tube inspections."
Brian D Johnson Senior Licensing Engineer CC Director, Region III, USNRC NRC Resident Inspector-Palisades Plant
/Joo/
lo