File. Pl0.2.l Incident No:

PAL-80-07~NC39 NPDES NONCOMPLIANCE NOTIFICATION Possible Noncompliance With Daily Average/Maximum Li~itation July 25, 1980 Plant:

Palisades Plant Outfall

Description:

Turbine Sump Oil Separator Waste (DOG)

Permit No:

Outfall No:

MI 0001457 800218 Parameter:

Oil and Grease Parameter No:

00556

-\\

1~

Date of Incident:

7/11/80

2.

Identification of specific effluent limitation exceeded:

Oil and Grease Daily Maximum Limitation of 20 mg/I

3.

Description of Incident:

On 7/11/80, oil was detected in the turbine sump oil separator tank and was measured at 35.3 mg/I.

Oil appeared to be in a nonemulsified form and probably was of a short duration.

4.

Apparent Cause:

Various systems in the turbine building were still being cleaned out following the oil spill on 7/2/80.

It is possible that the filter el~ments of the turbine building oil water separator were overloaded.

. 5.

If not immediately corrected, the anticipated time the condition is expected to continue:

NA

6.

Corrective Action - The following corrective action was taken or will be taken to reduce, e.liminate and prevent recurrence:

The oil separator was drained and the filters were changed.

7.

Additional Comments:

NA

8.

Signed: