consumers

  • power company General Offices: 212 West Michigan Ave.nue, Jackson, Michigan 49201
  • Area Code 517 7.88-0550 June.16, 1980

~rr James G Keppler Office of Inspection and Enforcement Region III U S Huclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, IL 60137 DOCKET 50-255 - LICENSE DPR PALISADES PLANT - SPECIAL RADIO-ACTIVE ENVIRONMENTAL MONITORING E:i:.'.PORT Attached is an NPDES Noncompliance Notification issued by Consumers Power Company on June 6, 1980. It is being submitted to you in accordance with Technical Specification 6.9.3.l.D.

David P Hoffman Nuclear Licensing Administrator Dir*ector, Office of Nuclear Reactor Regulation Director, Office of Inspection and Enforcement NRC Resident Inspector - Palisades JUN 1 81980

(

  • F~No Pl0.2.1 IiRl&ent No:

PAL-80-05-NC37 NPDES NONCO~tPLIANCE NOTIFICATION Possible Noncompliance With Daily Average/Maximum Limitation.

June 6, 1980 Plant:

Palisades Outfall

Description:

Turbine Sump Oil Separator (000/00G)

Parameter:

Oil and Grease

1.

Date of Incident:

05/27/80 Permit No:

n!-0001457

  • Outfall N'o:

800218 Parameter No:

00556

2.

Identification of specific effluent limitation exceeded:

Oil and grease shall not exceed 15 mg/l monthly average or 20 mg/l daily maximum.

3.

Description of Incident:

The weekly grab sample for oil and grease collected on 05/27/80 measured 84.0 mg/1.

It is believed to be a one time noncompliance.

The sample was collected on 05/29/80 to verify level below 20 mg/l.

The monthly average oil and grease was 20.7.

4.

Apparent Cause:

During start-up of the plant, excess oil entered the turbine sump and the filter in the oil separator unit may also have been plugged.

5. If not immediately corrected, the anticipated time the condition is expected to continue:

NA

6.

Corrective Action - The following corrective action was taken or will be taken to reduce, eliminate and prevent recurrence:

Maintenance order routed to inspect and replace (if necessary) the oil separator filter arid check remainder of system.

7.

Additional Comments:

NA

8.

Signed:

Ronald L Fobes

~-:z,~

...