  • consumers Power company
  • Area Code 517 788-0550 March 28, 1980 Director,.Nuclear Reactor-,Regulation Att Mr Dennis L Ziemann, Chief Operating Reactors Branch No 2 US Nuclear Regulatory Commission Washington, DC 20555 DOCKET 50-255 - LICENSEDPR PALISADES PLANT - TMI MODIFICATIONS -

ROSEMONT PRESSURE TRANSMITIERS Consumers Powe'r Company was requested by Mr G Imbro (NRG) on March 27, 1980 to -

provide additional information on the Palisades Plant pressurizer pressure tr~nsmitters. Rosemont (Model 1151) pressure transmitters are presently being used.

The manufacturer states that these transmitters are reliable for a

. 5 x 105 rad.field and could be seismically qualified by a similarity process.

Consumers Power believes that these transmitters are acceptable for the interim.

Rosemont {Model 1153). pressure transmitters,* which are seismically qual:~.f.:i.. ~d

  • and re.liable_ for a. 108 rad. field; are on order.

The.delivery time is ap-proximately seven months.

These transmitters will replace the Rosemont 1151 transmitters*the first time the Palisades Plant is taken to cold shutdown after the material and certification is received on site.

lJ Roger W Huston Senior Licensing Engineer CC JGKeppler, USNRC 8004020 "