ML18043B124

From kanterella
Jump to navigation Jump to search
Forwards LER 79-042/01T-0
Date released: 09/25/2019 Download: ML18043B124


Forwards LER 79-042/01T-0
ML19254D803
Person / Time
Site: Palisades 
Issue date: 10/26/1979
From: Bixel D
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To: KEPPLER J G
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML19254D803 (1)
LER 79-042-01T-0:on 791012,during Testing of Pressurizer Code Safety Valves,Lift Setting for Two Valves Were 2,897 & 2,462 Psia,Violating Tech Specs.Caused by Mispositioning of Alignment Pin.Future Testing Will Be Done W/Steam
ML18043B123
Person / Time
Site: Palisades 
Issue date: 10/26/1979
From:
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML18043B123 (3)