GaneRI Offlcm: 212 Wmt Michigan Avenue, Jeckson, Michigan 49201 * (5171 788-01560 August 21, 1979 Bulletins/Orders Ta.sk Force

. Att :

Mr N Villalva

  • us Nuclear Regulatory Commission

.Washington, DC *20555

. REGULATORY DOCKET RLE COPY DOCKET 50-255 ~ LICENSE DPR PALISADES PLANT - ELECTRICAL SUPPLY TO PRESSURIZER HEATERS Ref (1) -*Letter from D P Hof:f'ma.n to N Villalva dated August 8, 1979 In reference ( 1) Consumers Power Company stated that no credit could be taken for pressurizer heaters following* a LOCA and loss of offsite power.

However, after conversing with 'members of. your staff, ve can provide the following in-formation:

Fifty percent ( 50%) of.the pressurizer heaters ( 750 kw) are supplied from the emergency bus "]* D".

These heaters are stripped from the bus. and locked out on a safety injection actuation signal.

They can be energized by bypassing the lockout relay using sliding °link tenninal blocks in the control panels.

  • This manual evolution would take approximately 5-10 minutes.

There would be enough po-.,er available from the diesel generator to energize all of the heat-ers. on bus 1 D provided the lov pressure safety injection (LPSI) pumps 'W'ere not energized.

In the event of a loss of offsite power not followed by a LOCA or safety injection actuation signal, the heaters on bus 1 D could be energized normal-ly (proportional heaters-automatically, backup heaters manually) provided the

  • LPSI pumps vere not'energized.

It should be noted that the press'urizer heater control* transformers are located inside containment and are n~t environmentally: qualified.

/Ly-'J(JJ~

David P Hoff"J-Assistant Nuclear Licensing Administrator CC:

Director, Office of Nuclear Reacter Ro~ation Director, Office of Inspection arid Enforcement