consumers Power company General Offices: 212 West Michigan Avenue, Jackson, Michigan 49201
- Area Code 517 788-0550 May 17, 1979 Mr James G Keppler Office of Inspection and EnforGement Region III US Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, IL 60137 DOCKET 50-255 - LICENSE DPR PALISADES PLANT - IE BULLETIN 79-09 Consumers Power Company's response to IE Bulletin 79-09 is as follows:
ITEM 1
© Determine whether or not GE type AK-2 breakers are used or planned for use in safety-related systems at your facility(ies).
RESPONSE
No GE type AK-2 circuit breakers are used or planned for use in safety-related systems at Palisades.
ITEM 2 If such circuit breakers are used or planned for use, identify the safety system involved and provide in written form your plans for. developing a preventive maintenance program which will assure design performance with the GE type AK-2 circuit breaker.
RESPONSE
Not applicable - see Response 1.
ITEM 3 The program shall include as a minimum but not be limited to the following:
- a.
Establish and adhere to a preventive maintenance schedule regarding the subject circuit breakers.
790629017<6 oc0579-0341a~13
!...'.Y 211$79
- b.
Have the maintenance performed by qualified personnel.
The GE power circuit breaker instruction manual should be used as guidance in setting up the maintenance procedures.
- c.
During the preventive maintenance, perform the recommended corrective actions described in the enclosed GE Service Alert Letter No 175(CPDD) 9.3, dated April 2, 1979.
A copy of this letter is enclosed for your information and appropriate use.
RESPONSE
Not applicable - see Response 1.
David P Hoffman (Signed)
David P Hoffman Assistant Nuclear Licensing Administrator CC Director, Office of Nuclear Reactor Regulation Director, Office of Inspection and Enforcement oc05 79-0341a-13 2