Forwards Rev 1 to LER 94-008,providing Details Re Primary Containment Penetrations & MSIV Leak Rates Exceeding TS Limits
Date released: 09/27/2018 Download: ML18038B150


LER 94-008-01:on 941002,containment Penetration & MSIV Leak Rates Exceeded TS Limits.Caused by Abnormal Rib Guide Wear. MSIVs Repaired & Retested.Maint Instructions Will Be Written for Valves to Address Proper Shimming Requirements
ML18038B151
Person / Time
Site: Browns Ferry 
Issue date: 02/27/1995
From: Jay Wallace
TENNESSEE VALLEY AUTHORITY
To:
References
Download: ML18038B151 (18)
Forwards Rev 1 to LER 94-008,providing Details Re Primary Containment Penetrations & MSIV Leak Rates Exceeding TS Limits
ML18038B149
Person / Time
Site: Browns Ferry 
Issue date: 02/27/1995
From: Machon R
TENNESSEE VALLEY AUTHORITY
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
Download: ML18038B149 (6)