Southern Nuclear JAN 3 0 2018 Docket No.:

52-026 U.S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555-0001 Michael J. Yox Regulatory Affairs Director Vogtle 3 & 4 7825 River Road Waynesboro, GA 30830 706-848-6459 tel 410-474-8587 cell myox@southernco.com ND-18-0114 10CFR 52.99(c)(1)

Southern Nuclear Operating Company Vogtle Electric Generating Plant Unit 4 ITAAC Closure Notification on Completion of ITAAC 2.2.04.08a.i [Index Number 2351 Ladies and Gentlemen:

In accordance with 10 CFR 52.99(c)(1), the purpose of this letter is to notifythe Nuclear Regulatory Commission (NRC) of the completion of Vogtle Electric Generating Plant (VEGP)

Unit 4 Inspections, Tests, Analyses, and Acceptance Criteria (ITAAC) Item 2.2.04.08a.i [Index Number 235] for verifying that the sum of the rated capacities recorded on the valve vendor code plates of the steam generator safety valves exceeds 8,240,000 Ib/hrper steam generator.

The closure process for this ITAAC is based on the guidance described in NEI 08-01, "Industry Guideline for the ITAAC Closure Process under 10 CFR Part 52," which was endorsed by the NRC in Regulatory Guide 1.215.

This letter contains no new NRC regulatory commitments. Southern Nuclear Operating Company (SNC) requests NRC staff confirmation of this determination and publication of the required notice in the Federal Register per 10 CFR 52.99.

If there are any questions, please contact Tom Petrak at 706-848-1575.

Respectfully submitted.

Michael J. Yox Regulatory Affairs Director Vogtle 3&4

Enclosure:

Vogtle Electric Generating Plant (VEGP) Unit 4 Completion of ITAAC 2.2.04.08a.i [Index Number 235]

MJY/LBP/amw

U.S. Nuclear Regulatory Commission ND-18-0114 Page 2 of 3 To:

Southern Nuclear Operating Company/ Georgia Power Company Mr. D. A. Bost (w/o enclosures)

Mr. M. D. Rauckhorst (w/o enclosures)

Mr. M. D. Meier Mr. D. H. Jones (w/o enclosures)

Mr. D. L. McKinney Mr. M. J. Yox Mr. D. L. Fulton Mr. J. D. Williams Mr. F. H. Willis Ms. A. L. Pugh Mr. A. 8. Parton Mr. W. A. Sparkman Mr. 0. E. Morrow Ms. K. M. Stacy Mr. M. K. Washington Mr. J. P. Redd Ms. A. C. Chamberlain Mr. D. R. Culver Mr. R. L. Beiike Mr. T. G. Petrak Document Services RTYPE: VND.LI.L06 File AR.01.02.06 cc:

Nuclear Reaulatorv Commission Mr. W. Jones (w/o enclosures)

Ms. J. M. Heisserer Mr. C. P. Patel Mr. M. E. Ernstes Mr. G. J. Khouri Mr. T. E. Chandler Ms. S. E. Temple Ms. P. Braxton Mr. T. C. Brimfield Mr. A. J. Lerch Mr. C. J. Even Mr. F. D. Brown Mr. B. J. Kemker Ms. A. E. Rivera-Varona Oalethoroe Power Corporation Mr. R. B. Brinkman Municipal Electric Authoritv of Georgia Mr. J. E. Fuller Mr. S. M. Jackson

U.S. Nuclear Regulatory Commission ND-18-0114 Page 3 of 3 Dalton Utilities Mr. T. Bundros Westinahouse Electric Company. LLC Dr. L. Oriani (w/o enclosures)

Mr. D. 0. Durham (w/o enclosures)

Mr. M. M. Corletti Ms. L. G. Iller Mr. D. Hawkins Ms. 8. DiTommaso Mr. J. L. Coward Ms. N. E. Deangelis Other Mr. J. E. Hosier, Bechtel Power Corporation Ms. L. Matis, Tetra Tech NUS, Inc.

Dr. W. R. Jacobs, Jr., Ph.D., GDS Associates, inc.

Mr. 8. Roetger, Georgia Public Service Commission Ms. 8. W. Kernizan, Georgia Public Service Commission Mr. K. C. Greene, Troutman Sanders Mr. 8. Blanton, Baich Bingham

U.S. Nuclear Regulatory Commission ND-18-0114 Enclosure Page 1 of 4 Southern Nuclear Operating Company ND-18-0114 Enclosure Vogtle Electric Generating Plant (VEGP) Unit 4 Completion of ITAAC 2.2.04.08a.l [Index Number 235]

U.S. Nuclear Regulatory Commission ND-18-0114 Enclosure Page 2 of 4 ITAAC Statement Desion Commitment:

S.a) The SGS provides a heat sink for the RCS and provides overpressure protection in accordance with Section III of the ASME Boiler and Pressure Vessel Code.

Inspections. Tests. Analvses:

i) Inspections will be conducted to confirm that the value of the vendor code plate rating of the steam generator safety valves is greater than or equal to system relief requirements.

Acceptance Criteria:

i) The sum of the rated capacities recorded on the valve vendor code plates of the steam generator safety valves exceeds 8,240,000 Ib/hr per steam generator.

ITAAC Determination Basis Multiple inspections, tests and analysis (ITAAC) are performed to verify that the Steam Generator System (SGS) provides a heat sink for the Reactor Coolant System (RCS) and provides overpressure protection in accordancewith Section III ofthe American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code. This ITAAC requiresan inspection to confirm thatthe sum of the rated capacities recorded on the valve vendor code plates ofthe steam generator safety valves exceeds 8,240,000 Ib/hr per steam generator.

An inspection ofthe ASME Code Datafor the steam generatorsafetyvalves listed in the Combined License (COL) Appendix C, Table 2.2.4-1 (Attachment A) was performed (Reference 2).

The ratedcapacities recorded on the ASME NV-2 Code plates ofthe safetyvalveswere summed and exceed 8,240,000 Ib/hr per set of valves for each steam generator. The steam generator safety valve flow capacity recorded onthe valve ASME Code plate was certified by ASME through the National Board of Boiler and Pressure Vessel Inspectors (NBBPVI). Article NC-7700 of the ASME Boiler and Pressure Vessel Code,Section III (Reference 1) describes the methods required to certify the relief device capacity and determine a coefficient used in determining capacity in subsequently manufactured valves. The safety valve flow capacity for the steamgenerator safety valves was calculated bya set ofequations using the coefficient found in NC-7700 and also in NB-18, "Pressure Relief Device Certification" from the NBBPVI.

The ASME Code data plateforeach steam generatorsafety valve recordsthe rated capacity based on the set pressures as shown in Attachment A. The sum ofthe ratedcapacities recorded on the valve vendor code plates of the steam generator safety valves is 10,937,764 Ib/hr for each steam generator which exceeds 8,240,000 Ib/hr per steam generator and meets the \\7AAC acceptance criteria.

U.S. Nuclear Regulatory Commission ND-18-0114 Enclosure Page 3 of 4 ITAAC Finding Review In accordance with plant procedures for ITAAC completion, Southern Nuclear Operating Company (SNC) performeda review of all ITAAC findings pertaining to the subject ITAAC and associated corrective actions. This review found that there are no relevant ITAACfindings associated with this ITAAC. The ITAAC completion review is included in the Vogtle Unit4 ITAAC Completion Package for ITAAC 2.2.04.08a.i (Reference 3) and available for NRC inspection.

ITAAC Completion Statement Based on the above information, SNC hereby notifiesthe NRCthat ITAAC 2.2.04.08a.i was performed forVEGP Unit 4 that the prescribed acceptance criteria are met.

Systems, structures, andcomponents verified as part of this ITAAC are being maintained in their as-designed, ITAAC compliant condition in accordance with approved plant programs and procedures.

References (available for NRC inspection)

1. American Society ofMechanical Engineers Boiler &Pressure Vessel Code,Section III, 1998 Edition with 2000 Addenda
2. SV4-PV65-VQQ-001 Rev 1, "Quality Release and Certificate of Conformance for PV65 MSSV's"
3. 2.2.04.08a.i-U4-CP-Rev 0, Completion Package for Unit 4 ITAAC 2.2.04.08a.i[COL Index 235] (SGS Safety Valves Code Plate Rating)

U.S. Nuclear Regulatory Commission ND-18-0114 Enclosure Page 4 of 4 Attachment A Steam Generator System Steam Safety Valves

^Equipment Name

  • Tag No.

Serial No.

Quality Reiease and Certificate of Conformance Code Piate Rated Capacity (Ib/hr)

Set Pressure (psig)

Main Steam Safety Valve SG01 SGS-PL-V030A JX-16-CN0023 JX-16-CN0029 SV4-PV65-VQQ-001 1,781,854 1185 Main Steam Safety Valve SG02 SGS-PL-V030B Main Steam Safety Valve SG01 SGS-PL-V031A JX-16-CN0024 JX-16-CN0030 SV4-PV65-VQQ-001 1,799,683 1197 Main Steam Safety Valve SG02 SGS-PL-V031B Main Steam Safety Valve SG01 SGS-PL-V032A JX-16-CN0025 JX-16-CN0031 SV4-PV65-VQQ-001 1,817,513

. 1209 Main Steam Safety Valve SG02 SGS-PL-V032B Main Steam Safety Valve SG01 SGS-PL-V033A JX-16-CN0026 JX-16-CN0032 SV4-PV65-VQQ-001 1,835,342 1221 Main Steam Safety Valve SG02 SGS-PL-V033B Main Steam Safety Valve SG01 SGS-PL-V034A JX-16-CN0027 JX-16-CN0028 JX-16-CN0033 JX-16-CN0034 SV4-PV65-VQQ-001 1,851,686^

1232 Main Steam Safety Valve SG02 SGS-PL-V034B Main Steam Safety Valve SG01 SGS-PL-V035A Main Steam Safety Valve SG02 SGS-PL-V035B Sum of rated capacities of the safety valves for each steam generator 10,937,764 1 - Sum Includes code plate capacity times 2

  • Excerptfrom COL Appendix C Table 2.2.4-1