A>"CESSION NBR FAC IL: 50-2se 50-260
.50-296 AUTH. NAME R IVERS> M. E.
RECIP. NAME HORN> C.
REGULATORY '~ORMATION"DISTRIBUTION SY (RlliS) 8706220295 DOC. DATE: 87/06/16 NOTARIZED:
NO Bv owns Ferry Nuclear Powev Station>
Unit 1>
Tennessee Browns Fevv g Nuclear'Power Station>
Unit 2>
Tennessee Bv owns Ferry Nuclear Power Station>
Unit 3>
Tennessee AUTHOR AFFILIATION Tennessee Valley Authov itg RECIPIENT AFFILIATION Alabama>
State of DOCKET 050002sw 05000260 05000296
SUBJECT:
NPDES noncompliance notification: on 870425> identified unpermitted discharge from mobile w'ater treatment plant being operated fov TVA bg Memphis Mobile. Design changes started for installation new pevmanent water treatment, plan.
DISTRIBUTION CODE:
IE23D COPIES RECEIVED: LTR I
ENCL 0 SIZE:
TITLE: Environmental Event Repov t (pev'ech Specs)
NOTES: Zwolinski 5 cg.
1 cg ea to:
Axelrad> Ebneter> S. Richardson>
Liaw>.G. Zec h > OI > OIA.
Zwolinski 5 cg. ice ea to:
Axelrad> Ebneter> S. Richardson>
Liaw> G. Zech> OI> OIA.
Zwolinski 5 cg. icy ea to:
Axelrad> Ebneter> S. Richardson>
Liaw> G. Zech> OI> OIA.
05000259 05000260 050002'P6 RECIPIENT ID CODE/NAME JAMERSON> C GEARS> G COP IES LTTR ENCL REC IP IENT ID CODE/NAME PD STANQ> J COPIES LTTR ENCL INTERNAL: ACRS AEOD/DSP/TPAB NRR/DEST/ADE NRR/DREP/EPB NRR/PMAS/ ILRB OGC/HDS" RGN2 FILE 01 EXTERNAL:
LPDR NSIC
- EOD/DOA AEOD/PTB NRR/DOEA/EAB NRR/DREP/RPB
/
PTSB R
F 2/DRSS/EPRPB NRC PDR 1
1 1
NOTES:
12 TOTAL NUMBER OF COPIES REQUIRED:
LTTR 37 ENCL
TENNESSEE VALLEY AUTHORITY KNOXVILLE.TENNESSEE 37902 JUN J6 198T Mr. Charles Horn, Director Water Division Alabama Department of Environmental Management 1751 Federal Drive Montgomery, Alabama 36130 Attention:
Ms. Treena G. Piznar
Dear Mr. Horn:
BROWNS FERRY NUCLEAR PLANT (BFN) -
NPDES PERMIT NO.
AL0022080 NOTIFICATION OF UNPERMITTED DISCHARGE On April 25, BFN environmental staff identified an unpermitted discharge from a mobile water treatment plant being operated for TVA by Memphis
- Mobile, a
private contractor.
The water treatment plant was discharging to the intake forebay via the yard drainage system during backflushing and startup operations.
Memphis Mobile has operated the facility intermittently since December 1983.
Since January 27, this water treatment plant has been BFN's sole source of demineralized water.
Since December
- 1983, TVA has contracted to have approximately 10 million gallons of demineralized water produced.
The backflush consists of particulate matter and alum and would exceed the effluent limits for low volume wastes.
Two samples o'f the backflush collected on April 25 contained 29 and 62 mg/1 of oil and
- grease, 38 and 56 mg/1 of total suspended
- solids, and both had a
pH of 7.1 s.u.
The water discharged during startup is demineralized water used to flush raw water from the system and would meet effluent limits for low volume wastes.
The discharge from the mobile plant to the yard drain was terminated on April 25.
The discharge during backflushing has been temporarily routed to the waste sump in the intake pumping station, which in turn discharges to the sedimentation pond.
This is the flow path identified in the permit application for waste from the permanent water treatment plant which was taken out of service on January 27.
Design changes are underway for installation of a
new permanent water treatment plant.
When this design has been finalized, TVA will submit a
proposed permit revision for this discharge if it is different from the old permanent water treatment plant.
8706220295 870626 PDR ADQCK 05000259 8
PDR ggg 9
<(o An Equal Opportunity Employer
Mr. Charles Horn JUN 16 1987 If you have any questions concerning this matter, please call Madonna Martin of my staff at (615) 632-6695 in Knoxville.
Sincerely, Martin E. Rivers, Director Environmental Quality cc:
Mr. Bruce R. Barrett, Director Water Management Division U.S. Environmental Protection
- Agency, Region IV 345 Courtland Street, NE.
Atlanta, Georgia 30365 U.S. Nuclear Re ulator Commiss'ttention:
Document Control Desk Washington, D.C.
20555 Mr. G.
G. Zech, Assistant Director Regional'npsections Division of TVA Projects Office of 'Special Projects U.S. Nuclear Regulatory Commission, Region II 101 Marietta Street NW, Suite 2900 Atlanta, Georgia 30323 Mr. J. A. Zwolinski, Assistant Director for Projects Division of TVA Projects Office of Special Projects U.S. Nuclear Regulatory Commission 4350 East West Highway EWW 322
- Bethesda, Maryland 20814
1