Forwards SER Re Util 851120 Proposed Tech Specs Rev,Deleting Requirement for Annual Smoke Detector Sensitivity Checks. Denial Recommended Due to Inadequate Sensitivity Testing Procedures & out-of-date Detectors
ML18032A249
Person / Time
Site: Browns Ferry  
Issue date: 05/22/1987
From: Liaw B
NRC OFFICE OF SPECIAL PROJECTS
To: Zwolinski J
NRC OFFICE OF SPECIAL PROJECTS
Shared Package
ML18032A251 List:
References
TAC-60246, TAC-60247, TAC-60248, NUDOCS 8705290200
Download: ML18032A249 (3)


Text

i Docket Nos. 50-259/260/296 I

I MEMORANDUM FOR:

J.

A. Zwolinski, Assistant Director for Projects Division of TVA Projects FROM:

SUBJECT:

B. D. Liaw, Assistant Director for Technical Programs Division of TVA Projects BROWNS FERRY NUCLEAR PLANT UNITS 1, 2, AND 3 - PROPOSED TECHNICAL SPECIFICATION CHANGE REGARDING FIRE DETECTOR SURVEILLANCE (TAC NO. 60246,

60247, AND 60248)

By letter dated November 20, 1985 (TS-215)

TYA proposed a change to the Technical Specification which would delete the requirement for annual checks of smoke detector sensitivity to be made in accordance with the manufacturer's instruction.

We have reviewed TYA's request and the additional information

'ent in response to our RFI (Gridley to Ebneter, 3/19/87).

From a telephone conversation between R. Wescott (the F.

P. Reviewer) and a

representative of Fenwell Corporation (the detector vendor) it was determined that the detectors were out of date and should be replaced and that TVA's sensitivity testing procedure was not adequate, in the opinion of the vendor.

It is our understanding that John Stang of your staff discussed this matter with TVA and that TVA has informally agreed to replace the detectors, although no written commitments have been received thus far.

It is our recommendation that the existing request from TVA be denied.

Our SER is attached.

y~/

8705290200 870522 PDR ADOCK 05000259 F

PDR

Enclosure:

As stated DISTRIBUTION bOOFi Local PDR J. Axelrad S. Ebneter S. Richardson

~

J. 'Zwolinski B. D. Liaw

,.G. Zech, RII S.

R. Connelly, OIA B. Hayes, OI ACRS (10)

J. Partlow F. Miraglia OGC-BETH Projects Rdg.

. "Pl nt Rdg.

T

-BETH B. D. Liaw, Assistant Director for Technical Programs Division of TVA Projects C. Jamerson G. Gears J.

Stang W

NAME q:BDLiaw A

DATE:

/Q/87 4:~ / g87

V

~I

~ v ~

I

4 Docket Nos. 50-259/260/296 MEMORANDUM FOR:

J.

A. Zwolinski, Assistant Director for Projects Division of TVA Projects FROM:

SUBJECT:

B. D. Liaw, Assistant Director for Technical Programs Division of TVA Projects BROWNS FERRY NUCLEAR PLANT UNITS 1, 2, AND 3 -

PROPOSED TECHNICAL SPECIFICATION CHANGE REGARDING FIRE DETECTOR SURVEILLANCE (TAC NO. 60246,

60247, AND 60248)

By letter dated November 20, 1985 (TS-215)

TVA proposed a change to the

'echnical-Specification which would delete the requirement for annual checks of smoke detector sensitivity to be made in accordance with the manufacturer's instruction.

We have reviewed TVA's request and the additional information sent in response to our RFI (Gridley to Ebneter, 3/19/87).

From a telephone conversation between R. Wescott (the F. P. Reviewer) and a

representative of Fenwell Corporation (the detector vendor) it was determined that the detectors were out of date and should be replaced and that TVA's sensitivity testing procedure was not adequate, in the opinion of the vendor.

It is our understanding that John Stang of your staff discussed this matter with TVA and that TVA has informally agreed to replace the detectors, although no written commitments have been received thus far.

It is our recommendation that the existing request from TVA be denied.

Our SER is attached.

rs/

B. D. Liaw, Assistant Director for Technical Programs Division of TVA Projects

Enclosure:

As stated'ISTRIBUTION Local PDR J. Axelrad S. Ebneter S. Richardson J. Zwolinski B. D. Liaw G. Zech, RII S.