TENNESSEE VALLEYAUTHORITY CHATTANOOGA. TENNESSEE 37401 5N 157B Lookout Place May 12, 1986 U.S. Nuclear Regulatory Commission Region II ATTN:

Dr. J.

Nelson Grace, Regional Administrator 101 Marietta Street, NW, Suite 2900 Atlanta, Georgia 30323

Dear Dr. Grace:

BROWNS FERRY NUCLEAR PLANT UNITS 1, 2, NRC-OIE REGION II INSPECTION REPORT 50-259/86-08, 50-260/86-08,

-296/86-08

RESPONSE

TO VIOLATIONS Enclosed is our response to J.

A. Olshinski's April 16, 1986 letter to S.

A. White transmitting IE Inspection Report Nos. 50-259/86-08, 50-260/86-08, and 50-296/86-08 for our Browns Ferry Nuclear Plant which cited TVA with one Severity Level V Violation.

If you have any questions, please get in touch with R.

E. Rogers at FTS 858-2723.

To the best of my knowledge, I declare the statements contained herein are complete and true.

Very truly yours, TENNESSEE VALLEY AUTHORITY Enclosure cc:

Mr. James Taylor, Director (Enclosure)

Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, D.C.

20555 R.

H. Shell Nuclear Engineer 8606020150 860512 PDR ADOCK 05000259 8

PDR An Equal Opportunity Employer 1 \\

MEO I

~

~

ENCLOSURE

RESPONSE

NRC INSPECTION REPORT NOS.

50-259/86>>08, 50-260/86-08, AND 50-296/86-08 JOHN A. OLSHINSKI'S LETTER TO S. A. WHITE DATED APRIL 16, 1986 Item 1

'10 CFR 50, Appendix B, Criterion XIII and the accepted Quality Assurance (QA)

Program (TVA Topical Report TVA-TR75-1A), Section 17.2.13, require that items in the gA program be stored to prevent damage or deterioration.

The QA program commits to Regulatory Guide 1.38, Revisi.on 2, which endorses ANSI N45.2.2-1972, Packaging, Shipping, Receiving,

Storage, and Handling of Items for Nuclear Power Plants.

Section 6.4.2(1) of this standard requires that items in storage have all

covers, caps, or plugs or other protective closures intact.

Contrary to the above, during a tour of the Engineering Change Notice (ECN) warehouse on March 5, 1986, the inspector identified that most stainless steel tubing (AMG 1384) and a solenoid valve (Contract Number 84PJ5-834065) were not protected as required.

Further visual inspection also identified additional examples of items in storage that were not. protected as required.

This is a Severity Level V violation (Supplement, I).

1.

Admission or Denial of the Alle ed Violation TVA admits the violation.

2.

Reasons For the Violation A lack of attentiveness to protective coverings for every item in storage.

3.

Corrective Ste s Which Have Been Taken and Results Achieved Employee meetings held at the Engineering Change Notice warehouse on March 13 and March 20, 1986 emphasized the mandatory requirement that.

protective covers be maintained on components, including piping, fittings, and valves, in accordance with ANSI N45.2.2-1972.

A walkdown of the entire warehouse has been completed and any deficiencies in protective coverings have been corrected.

The central receiving office has been notified of the violation and will ensure that shipments are properly protected before being, placed in storage.

4.

Corrective Ste s Which Will Be Taken to Avoid Further Violations A followup program has been developed that will require a designated individual to check components on a weekly basis for protective covers which may have inadvertently become unsecured due to such factors as material handling or weather conditions.

5.

Date When Full Co liance Will Be Achieved Full compliance has been achieved

S