ENCLOSURE

1

NOTICE OF VIOLATION

l

Tennessee

Valley Authority

Browns Ferry

Docket Nos. 50-259,

260 and

296

License

Nos.

DPR-33,

52 and 68

The following violations

were identified during

an

inspection

conducted

on

January

26 - February

25,

1985.

The Severity Levels were assigned

in accordance

with the

NRC Enforcement Policy (10 -CFR Part 2, Appendix C).

Technical Specification 6.3.A requires

that detailed written procedures,

including applicable

check-off lists,

shall

be

prepared,

approved

and

adhered to for operations

and surveillance

requirements.

Contrary to the above, this requirement

was not met in that the Surveillance

Instruction 4.2. F.18 ("Main Steam Relief Valve Thermocouple

and Acoustic

Flow Monitor") did not include appropriate

acceptance criteria to ascertain

whether

the

recorded

values

met the "consistency

and nominally expected

value" criteria.

Contrary to the

above;

the requirement

was not met in that the required

. position of dampers

0-30-503,

504,

505

and

506 in the valve checklist

contained

in Operating Instruction

30 "Ventilation System"

was ambiguously

~

stated

("OPEN

TO

PRESET

POSITION" )

such that operators

were

unable- to

'etermine

the correct required position.

This was

a contributing cause to a

damper

misalignment event, on January

14,

1985 which resulted

in airborne

radioactivity in the

radwaste

building in excess

of 10

CFR

20

maximum

permissible concentration

(Xe 135).

This.'is

a Severity Level

V violation (Supplement I) applicable to all units.

Pursuant

to

10

CFR 2.201,

you are required to submit to this office within 30

days of the, date of this Notice,

a written statement

or explanation in reply,

including:

(1) admission

or denial of the alleged violations; (2) the reasons

for the violations if admitted;

(3) the corrective

steps

which have

been

taken

and the results

achieved;

(4) corrective

steps

which will be taken to avoid

further violations

and (5) the date

when full compliance will be achieved.

Security

or safeguards

information should

be

submitted

as

an

enclosure

to

facilitate withholding it from public disclosure

as required

by 10

CFR 2.790(d)

or 10

CFR 73.21.

8506270598

850322

PDR

ADOCK 05000259

Q

PDR

/