Amends 107,101 & 74 to Licenses DPR-33,DPR-52 & DPR-68, Respectively,Changing Tech Specs to Allow Operation for 30 Days w/16 Main Steam Tunnel High Temp Switches Bypassed
ML18026B170
Person / Time
Site: Browns Ferry  
Issue date: 08/09/1984
From: Vassallo D
Office of Nuclear Reactor Regulation
To:
Tennessee Valley Authority
Shared Package
ML18026B171 List:
References
DPR-33-A-107, DPR-52-A-101, DPR-68-A-074 NUDOCS 8408210004
Download: ML18026B170 (13)


Text

ggS RECIj

~C+

Wp0 Cy pW~

'+~

+w**+

t UNITEDSTATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 TENNESSEE VALLEY AUTHORITY.

DOCKET NO. 50-259 BROWNS FERRY NUCLEAR PLANT, UNIT 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.

107 License No. DPR-33 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by Tennessee Valley Authority (the licensee) dated November 3, 1982, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act),

and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C

C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment and paragraph 2.C(2) of Facility Operating License No. DPR-33 is hereby amended to read as follows:

(2)

Technical S ecifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 107, are hereby incorporated in the license.

The licensee shall operate the facility in accordance with the Technical Specifications.

Bg082iO<g 050002 000< 8"0 Se pop pgo po p

3.

This license amendment is effective as of the date of issuance.

FOR THE NUCL'EAR REGULATORY COMMISSION

/

g(PAW~-

Domenic B. Vassallo, Chief Operating Reactors Branch ¹2 Division of Licensing

Attachment:

Changes to the Technical Specifications Date of Issuance:

August 9, 1984

ATTACHMENT TO LICENSE AMENDMENT NO.

1Q7 FACILITY OPERATING LICENSE NO.

DPR-33 DOCKET NO. 50-259 Revise Appendix A as follows:

1.

Remove the following pages and replace with identically numbered pages.

61 2.

The marginal lines on these pages denote the area being changed.

~

~

0 ~

Channel shared by RPS and Primary Containment 5 Reacto Vessel Isolation Control System.

.A channel failure may be a channel failure in each system.

7.

A train is considered a trip system S.

Two out of three SGTS trains required.

A failure of more than one will require action A. and P.

9.

There is only one trip system with auto " ansfe>> to two. powe sources'0.

Refer to Table 3.7.A end its eatee for e Listing of IsoLetion Uelve Croupe end their Mitiating signals.

A channel may be placed in an inoperable status for up to four hours for required surveillance without placing the trip system in the tripped condition provided at least one OPERABLE channel in the same trip system is monitoring that parameter.

Power operations permitted for up to 30 days with 15 of the 16 temperature switches operable.

V A channel contains four sensors, all"'of.which must be operable for the channel to be operable.

Atgendment No,

, 107

~~~ 4~Cu~

0 Cl

~Pe 0

W**~4 t

UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 TENNESSEE VALLEY AUTHORITY DOCKET NO. 50-260 BROWNS FERRY NUCLEAR PLANT, UNIT 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. l0l License No. DPR-52 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by Tennessee Valley Authority (the licensee) dated November 3, 1982, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act),

and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or-. to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended~by changes to the Technical Specifications as indicated in the attachment to this license amendment and paragraph 2.C(2) of Facility Operating License No.

DPR-52 is hereby amended to read as follows:

(2)

Technical S ecifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No. 10l, are hereby incorporated in the license.

The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of the date of issuance.

FOR THE NUCLEAR REGULATORY COMMISSION Domenic B. Vassallo, Chief Operating Reactors Branch ¹2 Division of Licensing

Attachment:

Changes to the Technical Specifications I

Date of Issuance:

August 9:, 1984

ATTACHMENT TO LICENSE AMENDMENT NO.

101'ACILITY OPERATING LICENSE NO. DPR-52 DOCKET NO. 50-260 Revise Appendix A as follows:

1.

Remove the following pages and replace with identically numbered pages.

61 2.

The marginal lines on these pages denote the area being changed.

6.

channel shared by Rps and primary containment 5 Reactor Vessel Isolation Control System.

A channel failure may be a

channel faiLuze in each system.

7.

A train is considered a trip system.

8.

Two out of three SGTS trains zequized A failure of moze than one will require action A and F.

9.

Theze is only one trip system with auto t ansfer to two paver sources.

10.

Rater to Table 3.7.A and its notes Xor a listing of Isolation Valve Creeps and their initiating signals.

A channel may be placed in an inoperable status -for up to four hours for required surveillance without placing the trip system in the tripped

'ondition provided at least one OPERABLE channel in thc same trip system is monitoring"that parameter.

Power operations permitted for up to 30 days with 15 of the 16 temperature switches operable.

A channel contains four sensors, all "of, which must be operable for the channel to be operable.

Amendment No,,

10.1

AS Racy

~

~y gv

+w*e+

t UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 TENNESSEE VALLEY AUTHORITY DOCKET NO. 50-296 BROWNS FERRY NUCLEAR PLANT, UNIT 3 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.

74 License No.

DPR-68 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by Tennessee Valley Authority (the licensee) dated November 3, 1982, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act),

and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There. is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment and paragraph 2.C(2) of Facility Operating License No.

DPR-68 is hereby amended to read as follows:

(2)

Technical S ecifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No.

74

, are hereby incorporated in the license.

The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of the date of issuance.

FOR THE NUCLEAR REGULATORY COMMISSION Domenic B. Vassallo, Chief Operating Reactors Branch ¹2 Division of Licensing

Attachment:

Changes to the Technical Specifications Date of Issuance:

August 9., 1984

ATTACHMENT TO LICENSE AMENDMENT NO.

74 FACILITY OPERATING LICENSE NO.

DPR-68 DOCKET NO. 50-296 Revise Appendi x A as follows:

1.

Remove the following pages and replace with identically numbered pages.

63 2.

The marginal lines on these pages denote the area being changed.

3.

There are. four channels per steam line of which two must be operable.

4.

Only requi"ed in Run Node (interlocked with Rode Switch).

5.

Not required in Run Aode (bypassed

'iy mode switch).

6.

Channel shared by RPS and Primary Containment 6 Reac or Vessel Isolation Control System.

A channel failure may be,a channe3.

failure in each system.

7.

A train is considered a t=ip system.

8.

Two out of three SOS trains required.

than one wi13. require action A and P.

A failure of mo-e 9.

There 's only one t ip system with auto t answer to two pere sources.

10.

Refer to Table 3.7.A and its notes ior a listing oi Isolation Valve Czoups and their initiating signaLs.

11.

A channe3.

may be placed in an inoperable status for up to four hours for required surveillance vithout placing the trip system in the tripped condition provided at least one OPERABLE channel in the same trip system is monitoring that parameter.

12:

A channel contains four sensors, all 'of which must be operable for the channel to be operable.

Power operations permitted for up to 30 days vith 15 of the 16 temperature'switches operable.

Amendment No, >>