TENNESSEE VALLEY AUTHORITY l<NOXVILLE.TENNESSEE 37902 TVA Hailroom JU1 28 1983
~ ~BC rug~
Hr. John Maria
, Chief Facilities P
formance Branch Water Mana ement Division U.S. Env'nmental Protection Agency Region V
345 urtland Street, NE.
At anta, Georgia 30365
Dear Mr. Marlar:
NOTIFICATION OF NONCOMPLIANCE WITH EFFLUENT LIMITATIONS -
NPDES PERMIT NO. AL0022080 -
BROWNS FERRY NUCLEAR PLANT Descri tion of the dischar e--Discharge No.
006 Sewage'reatment plant effluent.
A grab sample collected on July 12 and reported from the laboratory on July 18 contained 76 mg/L of total suspended solids (TSS},
exceeding the permit limitations of 45 mg/L.
Cause and eriod of the noncom liance--Analysis of the sample for the required parameters yie ded the following results.
Parameter Concentration
- 'axilltullt Permi t Limitati on BOD TSS Fecal Col iform Chlorine Residual 36 mg/L 76 mg/L 10 N/100 ml 1.5 mg/L 45 mg/L 45 mg/L 400 N/10(j ml N/A The instantaneous flow at the time of sample collection was 88,848 gpd and the daily totalizer flow averaged 53,600 gpd for two days before and including the date of sample collection.
This high flow caused light, relatively inert solids to be washed over the clarifier weir causing the temporary noncompliance.
Ste s taken to reduce, eliminate, and revent recurrence of the noncom 1 in
~dsschar eT e system overloa as een stud>ed and design changes are currently being reviewed.
We plan to finalize the modification proposals in the near future.
Sincerely, Original Signed By M. Paul Schmierbach
/>@6 FP 8308030252 5000259 8g07g8 ppR APOCK ppR S
cc:
See page 2
Hohamed T. El-Ashry, Ph.D.
Director of Environmental Qual ity 1983-TVA 50'ANNlVERSARY Asi Equal Opposttsitity Employer
~l"
Mr. John Marlar JUL'8 1983 cc:
Mr. Joe B. Broadwater, Director Alabama Department of Environmental Management State Capitol Montgomery, Alabama 36130 i
fLi U.S. Nuclear Regulatory Commission Washington, D.C.
20555
v 'I I