ML18025B114

From kanterella
Jump to navigation Jump to search
Forwards LER 80-038/03L-0
Date released: 09/27/2018 Download: ML18025B114


LER 80-038/03L-0:on 800911,during Refueling Outage W/Unit in Cold Shutdown,Hpci Check Valve 2-73-609 Failed Local Leak Rate Test.Caused by Buildup of Residual Matl on Body,Causing Disc of Hcpi Valve to Be Cocked Open.Matl Removed
ML18025B116
Person / Time
Site: Browns Ferry Tennessee Valley Authority icon.png
Issue date: 10/07/1980
From:
TENNESSEE VALLEY AUTHORITY
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML18025B116 (3)
Forwards LER 80-038/03L-0
ML18025B112
Person / Time
Site: Browns Ferry Tennessee Valley Authority icon.png
Issue date: 10/07/1980
From: Calhoun J
TENNESSEE VALLEY AUTHORITY
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML18025B112 (2)