LER 80-038/03L-0:on 800911,during Refueling Outage W/Unit in Cold Shutdown,Hpci Check Valve 2-73-609 Failed Local Leak Rate Test.Caused by Buildup of Residual Matl on Body,Causing Disc of Hcpi Valve to Be Cocked Open.Matl Removed