a me Elastic Moduli of Intact Rock Core Specimens in Uniaxial Compression ASTM 07012-10 Project Name: Clinch River SMR Project Number: 6468-13-1072 Tested By: Mike Hamilton lttH Test Date:...:.1:..::/2;.:;0/c.::o20.:..1:....;4 ____
-Sf lja~/l'l Reviewed By: Allen Cottingham
.,.,/tC Review Date: 1/27/2014 1-~1-1'1 Rock Type Moisture Condition Specimen Diameter,Jin)
Specimen Length, (in)
Length/Diameter Ratio Specimen Conforms with Dimensional Requirements?
Sample No.: L7-20 BH Boring No.: MP-410 Run. No.: N/A Sample Depth (ft): 67.4-67.9 Page 1 of 2 (See boring log)
Laboratory Alr-Dry 2.39 5.04 2.1 No 11l As-Tested Unit Weight, (pcf) 1it6:"l I (gO jJeJ.- ~
~
~
IJ)
~
Loading Rate (lb/sec) 160 v
Test Duration to Failure, (min) 3 Uniaxial Compressive Strength, (psi) 4,000 Type of Break Shear on plane Young's Modulus, (psi) 1,930,000 Poisson's Ratio 0.26
-4,500
-4.000
-3.500
\\
-3.000
-2.500
-2.000
-1,500
- 1,000
-500
\\
~
\\
I
- I I
i-
\\
_l I
\\
/
\\I 7
\\
--AdJ. Channel #2 I
l Axial Strain (in/in) 1-I
--Adj. Channel #4
[
Circum. Strain (in/in) 0 0.0020 0.0010 0.0000
.0.0010
.0.0020 Axial Strain (-], (In/In]
-0.0030 lateral Strain ( + ], (In/In)
Comments:
Young's Modulus and Poisson's Ratio determined using linear least-squares of stress-strain data from 30% to 60%
of the uniaxial compressive strength (data points used are indicated on the figure above).
Axial Strain Is negative; Lateral Strain is posilive.
Load direction wilh respect to li!hology; Vertical (I ) Specimen did not meet side straightness, end perpendicularity, and end flatness requirements of ASTM 04543-08. Aulhorization to proceed with test received from John Damm.
Clinch River Data Report Rev. 4 CRP-1112.16 Page G.2-70 of 91
a me Elastic Moduli of Intact Rock Core Specimens in Uniaxial Compression ASTM 07012-10 Project Name: Clinch River SMR Project Number: 6468-13-1072 Tested By: Mike Hamilton
,.-~d Test Date: 1/20/2014
//1tPlf
~~~~----------
Reviewed By: Allen Cottingham 1"111-c Review Date: 1/27/2014 l*ll
- l~
Comments:
Specimen Prior to Testing
("MP-410 L7-20 BH before test.jpg"):
Clinch River Data Report Rev. 4 CRP-1112.16 Page G.2-71 of 91 Sample No.: L7-20 BH Boring No.: MP-410 Run. No.: N/A Sample Depth (ft): 67.4-67.9 Page 2 of 2 Specimen After Testing
("MP-410 L7-20 BH after test.jpg"):
a me Elastic Moduli of Intact Rock Core Specimens in Uniaxial Compression ASTM 07012-10 Project Name: Clinch River SMR Project Number: 6468*13-1072 Tested By: Mike Hamilton MH Test Date:...:1=2/...:4:..:/2:..:.0..;..13=--------=-'t.:./!ljtlf Reviewed By: Allen Cottingham flo/It Review Date: 1/29/2014
-"l*?*t'\\
Rock Type Moisture Condition Specimen Diameter, (In)
Specimen Length, (in)
Length/Diameter Ratio Sample No.: L7-23 BH Boring No.: MP-410 Run. No.: N/A Sample Depth (ft): 166.0-167.0 Page 1 of 2 (See boring Jog)
Laboratory Air-Dry 2.40 5.39 2.2 Specimen Conforms with Dimensional Requirements?
No 111
- .e
.b C/)
iO
~
-8.000
- 7.000
-6,000
- 5,000
-4,000
-3,000
-2,000
-1.000 0
0.0020 Comments:
As-Tested Unit Weight, (pcf)
Loading Rate (lb/sec)
Test Duration to Failure, (min)
Uniaxial Compressive Strength, (psi)
Type of Break Young's Modulus, (psi)
Poisson's Ratio
\\
I
\\
I I
I l
I I 7
I -,
(
0.0010 0.0000 Lateral Strain [ + J, (In/in)
I
~
- I'
-0.0010
-%T-:9-I (of} ~J 160 v
4.3 6,960 Shear 5,950,000 0.25 I
j --Average Adjusted Axial I Strain (infln) 1-
~ -- Average Adjusted I
Lateral Strain (lnfln) 1
-0.0020 Axial Stroln! * ), (lnfln)
-0.0030 Young's Modulus and Poisson's Ratio determined using linear least-sguares of stress-strain data from 40% to 60%
of the uniaxial compressive strength (data points used are indicated on the figure above).
Axial Strain is negative; Lateral Strain is positive.
Load direction with respect to lithology: Vertical
<*I Specimen did not meet End Perpendicularity and end flatness reguiremenls of ASTM 04543-08. Authorization to proceed with test received from John Damm.
Clinch River Data Report Rev. 4 CRP-1112.16 Page G.2-72 of 91
a me Elastic Moduli of Intact Rock Core Specimens in Uniaxial Compression ASTM 07012-10 Project Name: Clinch River SMR Project Number: 6468-13-1072 Tested By: Mike Hamilton m,tl Test Date: 12/4/2013 lbi/Jl{
Reviewed By: Allen Cottingham l(lrst, Review Date: 1/29/2014
\\~Vl
- l'l Comments:
Specimen Prior to Testing
("MP-410 L7-23 BH before test.jpg"):
Clinch River Data Report Rev. 4 CRP-1112.16 Page G.2-73 of 91 Sample No.: L7-23 BH Boring No.: MP-410 Run. No.: N/A Sample Depth (ft): 166.0-167.0 Page 2 of 2 Specimen After Testing
("MP-410 L7-23 BH after test.jpg"):
a me Elastic Moduli of Intact Rock Core Specimens in Uniaxial Compression ASTM 07012-10 Project Name: Clinch River SMR Project Number: 6468-13-1072 Tested By: Mike Hamilton
!>>l'l Test Date:...:.1:.=/2:..:;1/:.=2..:..01;...:4'---------'fl/11} /l(
Reviewed By: Allen Cottingham l""z, Review Date: _1.;./2_9..;../2_0_1_4 ______ ~_,_,~
Rock Type Sample No.: L7-19 BH Boring No.: MP-412 Run. No.: N/A Sample Depth (ft): 166.4-166.9 Page 1 of 2 (See boring log)
Moisture Condition Laboratory Air-Dry Specimen Diameter, {in) 2.39 Specimen Length, (in) 5.32 Length/Diameter Ratio 2.2 Specimen Conforms with Dimensional Requirements?
No rl As-Tested Unit Weight, (pcf)
~
1~7 /:t>.1- ~
Loading Rate (lb/sec) 160 v
Test Duration to Failure, (min) 6 Uniaxial Compressive Strength, (psi) 7,990 Type of Break Columnar Young's Modulus, (psi) 3,150,000 Poisson's Ratio 0.21
-9,000 r--------:--------:--------,--------:-------,
I I
-8.000
~------~==;:;;:::::---t------~-------r------- 1
-7.000 1---j---\\ --\\-!----!-----!:---__
c--,
\\
I
/
-6,000 1--+--------+.-\\ -i----1 --t-----+---
/
~/_;___
-5,000 l-------+----------1r--------l---------+--7-------l
\\
/v
- l---r--l ---~~------~- /
1
-2.ooo 1-------i-i------~-t'-l*------..,._-/'---.---_._------,- l
/
I-- Average Adjusted Axial Strain (infln)
i~+---/
---/'-r-1---~~ -- Average Adjusted Lateral Strain (infln) I oL---------~'----------lL---L~--------~============:=J
-1,000 0.0020 0.0010 0.0000 Latoral Strain I+], fin/In)
Comments:
-0.0010
-0.0020 Axial Strain 1-], (In/In)
-0.0030 Young's Modulus and Poisson's Ratio determined using linear least-squares of stress-strain data from 60% to 80%
of the uniaxial compressive strength (data points used are indicated on the figure above).
Axial Strain is negative; Lateral Strain is positive.
Load direction with respect to lithology: Vertical t*l Specimen did not meet Side Strightness, End Perpendicularity and end flatness requirements of ASTM 04543-08. Authorization to proceed with test received from John Damm.
Clinch River Data Report Rev. 4 CRP-1112.16 Page G.2-74-of 91
a me Elastic Moduli of Intact Rock Core Specimens in Uniaxial Compression ASTM 07012-10 Project Name: Clinch River SMR Project Number: 6468-13-1072 Tested By: Mike Hamilton rt~lf Test Date:....;1,;,:/2o..;,1;.;:;/2~0..;....14'------Y I /c..:.;1/~~
Reviewed By: Allen Cottingham Review Date: 1/29/2014 1-1/1
- 111 Comments:
Specimen Prior to Testing
("MP-412 L7-19 BH before test.jpg"):
Clinch River Data Report Rev. 4 CRP-1112.16 Page G.2-75 of 91 Sample No.: L7-19 BH Boring No.: MP-412 Run. No.: N/A Sample Depth (ft): 166.4-166.9 Page 2 of 2.
Specimen After Testing
("MP-412 L7-19 BH after test.jpg"):
a me Elastic Moduli of Intact Rock Core Specimens in Uniaxial Compression ASTM 07012-10 Project Name: Clinch River SMR Project Number: 6468-13-1072 Tested By: Mike Hamilton Test Date: 1/26/2014 Reviewed By: Allen Cottingham MLJ I ("(tptf Review Date:....:1.:.:/3:..:0.:.:/2:..:0_:1_:4 _____ _
Rock Type Moisture Condition Specimen Diameter, (in)
Specimen Length, (in)
Length/Diameter Ratio Specimen Conforms with Dimensional Requirements?
As-Tested Unit Weight, (pcf)
Loading Rate (lb/sec)
Test Duration to Failure, (min)
Uniaxial Compressive Strength, (psi)
Type of Break Young's Modulus, (psi)
Poisson's Ratio Sample No.: L3-66 BH Boring No.: MP-415 Run. No.: N/~
Sample Depth (ft): 133.9-134.9 Page 1 of 2 (See boring log)
Laboratory Air-Dry 2.40 5.50 2.3 No"'
-468-:1"" I (.lJ JfW 160 6.3 12,340 Complete Break 8,270,000 0.26
-14,000,--------:-----...,.,------,-
-12,000 ---
I
-10,000 1--t-----\\1- -+------t-1-//----t---1
\\
v
- ~
I
~ --
~ -
~.~
\\ I
'I
-l --~~~~~1~n~~~usted Axial I
-2.000 t----..___ __ ---H-,;;-/----+-1-- '
f--
-6.000 I I 1
1--Average Adjusted j
Lateral Strain (in/in) o L-------------------~--------------~============~
0.0020 0.0010 Lateral Strain [ + ). (In/In)
Comments:
0.0000
-0.00 10
-0.0020 Axial Strain [ -], (In/In)
Young's Modulus and Poisson's Ratio determined using linear least-squares ol stress-strain data from 40% to 60%
of the uniaxial compressive strength (data points used are indicated on the figure above).
Axial Strain is negative; Lateral Strain is positive.
Load direction with respect to lithology: Vertical
<*l Specimen did not meet End Flatness requirements ol ASTM 04543-08. Authorization to proceed with test received from John Damm.
Clinch River Data Report Rev. 4 CRP-1112.16 Page G.2-76 of 91
-0.0030
a me Elastic Moduli of Intact Rock Core Specimens in Uniaxial Compression ASTM 07012-10 Project Name: Clinch River SMR Project Number: 6468-13-1072 Tested By: Mike Hamilton 111 Ji Test Date: 1/26/2014
//?1 /Jif Reviewed By: Allen Cottingham
!("~
Review Date: 1/30/2014 1 * "11
- 1~
~~~--------------
Comments:
Specimen Prior to Testing
("MP-415 L3-66 BH before test.jpg"):
Clinch River Data Report Rev. 4 CRP-1112.16 Page G.2-77 of 91 Sample No.: L3-66 BH Boring No.: MP-415 Run. No.: N/A Sample Depth (ft): 133.9-134.9 Page 2 of 2 Specimen After Testing
("MP-415 L3-66 BH after test (3).jpg"):
a me Elastic Moduli of Intact Rock Core Specimens in Uniaxial Compression ASTM 07012*10 Project Name: Clinch River SMR Project Number: 6468-13-1072 Tested By: Mike Hamilton ntA Test Date: 1/26/2014 1/~1{Jtf Reviewed By: Allen Cottingham I'~
Review Date: 1/30/2014 t-31-l't
~~~~------------
Rock Type Moisture Condition Specimen Diameter, (in)
Specimen Length, (in)
Length/Diameter Ratio Specimen Conforms with Dimensional Requirements?
Sample No.: L3-69 BH Boring No.: MP-416 Run. No.: N/A Sample Depth (ft): 179.2-180.6 Page 1 of 2 (See boring log)
Laboratory Air-Dry 2.40 5.33 2.2 No 11l As-Tested Unit Weight, (pet)
~
f(pq f/<<J Loading Rate (lb/sec) 160 1/
Test Duration to Failure, (min) 7 Uniaxial Compressive Strength, (psi) 13,400 Type of Break Columnar Young's Modulus, (psi) 10,200,000 Poisson's Ratio 0.43
-9,000
-8,000
-7,000
-6,000
-5,000 s
~
~
-4,000
~
-3,000 I
I I
~-\\
I r-----
~---
I I
\\
I I
I j
I
-~
- 1G I
I I~
-2,000 I
~---
-- Average Adjusted Axial I
-1,000 0
0.0020 Comments:
I If I
0.0010 0.0000 Lateral Strain [+], (In/In)
-0.0010 Strain (innn)
--Average Adjusted _j Lateral Strain (infln)
-o.0020 Axial Strain ( - ], (In/In)
-0.0030 Young's Modulus and Poisson's Ratio determined using linear least-squares of stress-strain data from 20% to 40%
of lhe uniaxial compressive strength (data points used are indicated on the figure above).
Axial Strain is negative; Lateral Strain is positive.
Load direction with respecl to lithology: Vertical (1) Specimen did not meet End Flatness requirements of ASTM 04543-08. Authorization to proceed with test received from John Damm.
Clinch River Data Report Rev. 4 CRP-1112.16 Page G.2-78 of 91
a me Elastic Moduli of Intact Rock Core Specimens in Uniaxial Compression ASTM 07012-10 Project Name: Clinch River SMR Project Number: 6468-13-1072 Tested By: Mike Hamilton itrU Test Date:..:1.:..:12.:..:6.:..:12'-:-0-'-14'--,--------'-'-'
'/3//IIl Reviewed By: Allen Cottingham
~
Review Date: 113012014 1-111 -1~
Comments:
Specimen Prior to Testing
("MP-416 L3-69 BH before test.jpg"):
Clinch River Data Report Rev. 4 CRP-1112.16 Page G.2-79 of 91 Sample No.: L3-69 BH Boring No.: MP-416 Run. No.: NIA Sample Depth (ft): 179.2-180.6 Page 2 of 2 Specimen After Testing
("MP-416 L3-69 BH after test.jpg"):