ML18002A478
| ML18002A478 | |
| Person / Time | |
|---|---|
| Site: | Seabrook |
| Issue date: | 01/02/2018 |
| From: | - No Known Affiliation |
| To: | Division of Operating Reactor Licensing |
| References | |
| 17-953-02-LA-BD01 | |
| Download: ML18002A478 (32) | |
Text
1 SeabrookLANPEm Resource From:
SeabrookLAHearingFile Resource Sent:
Tuesday, January 02, 2018 11:30 AM To:
SeabrookLANPEm Resource Attachments:
North Wall of CEVA Near-Surface Delamiantion DRAFT.pdf.pdf; 170444-L-001 Rev.
0.pdf; 170444-SVR-01-R0.pdf
Hearing Identifier:
Seabrook_LA_NonPublic Email Number:
1198 Mail Envelope Properties (b5b6d764310044409e740655c87a0e40)
Subject:
Sent Date:
1/2/2018 11:30:23 AM Received Date:
1/2/2018 11:30:37 AM From:
SeabrookLAHearingFile Resource Created By:
SeabrookLAHearingFile.Resource@nrc.gov Recipients:
"SeabrookLANPEm Resource" <SeabrookLANPEm.Resource@nrc.gov>
Tracking Status: None Post Office:
HQPWMSMRS01.nrc.gov Files Size Date & Time MESSAGE 3
1/2/2018 11:30:37 AM North Wall of CEVA Near-Surface Delamiantion DRAFT.pdf.pdf 269973 170444-L-001 Rev. 0.pdf 619783 170444-SVR-01-R0.pdf 6252914 Options Priority:
Standard Return Notification:
No Reply Requested:
No Sensitivity:
Normal Expiration Date:
Recipients Received:
DRAFT 30 October 2017 North Wall of Containment Enclosure Ventilation Area (CEVA)
Near-Surface Delamination (Concrete Cover Separation)
(DRAFT 30 October 2017)
Problem Statement Site Visit Report 160268-SVR-05 [1] states that the lower portion of the north wall of the CEVA exhibits bowing into the West Pipe Chase Stairs area, with prominent horizontal cracks at the bowed area; the concrete does not exhibit visual symptom suggestive of internal ASR [2]. The structural analysis of this north wall indicates that the bowing is due to the expansion of the concrete fill at the back side of this wall, and that this portion of wall is not required as part of the load-resisting system of the CEVA. Because of the curvature of this wall, the near-surface delamination (separation of the concrete cover from the core concrete) may have occurred. In order to prevent any areas of delaminated cover concrete from falling and damaging the equipment below, Calculation 160268-CA-05 [3] recommended performing hammer sounding on the wall surface at location with higher curvature and larger horizontal for possibility of concrete cover separation.
Site Visit Report 170444-SVR-01 [4] documented that localized near-surface concrete delamination (as detected by sounding with a masons hammer) is present, primarily within 2 in.
along both sides of prominent horizontal cracks with crack widths larger than 0.06 in.
The purpose of this white paper is to provide the process for identifying locations requiring further surface evaluation, explanation of possible causes of the concrete cover separation (near-surface delamination) and to provide recommendations for further investigation, evaluation, and confirmation.
Prior Investigation and Analyses At the north side of the CEVA, a wall extends from the CEVA base slab (EL +19 ft) to the Mech.
Pen. Floor slab (EL +3 ft), referred here as lower portion of CEVA north wall. The north side of this wall is accessible from within the West Pipe Chase Stairs, and the south (back) side of the wall abuts the concrete fill below the CEVA Building, schematically shown in Figure 1.
The March 2017 field investigation of the CEVA structure [1] did not reveal any cracking suggestive of ASR or other material deterioration (such as surface separation or exposed corroded reinforcement, etc.); however, it did note apparent bowing at the area of prominent horizontal cracks (measuring from 0.03 in. to 0.08 in. wide at the accessible areas) in the original concrete as well as at previously-repaired areas of this wall from approximately EL +11 ft to EL +19 ft. The plumbness measurements at that time indicated an outward bowing with a maximum out-of-plumbness of 1.25 in. occurring from EL +13 ft to EL +17 ft. [1]. Review of the original design calculations and other drawings provided by NextEra Seabrook revealed that the lower portion of the north wall was only designed to resist seismic load due to its self-weight and hydrostatic pressure. Subsequent analysis [3] indicated that the bowing of the wall is likely due to the expansion of the concrete fill on the back (south) side of this wall. Further analysis was performed to determine the adequacy of base slab of CEVA to transfer the vertical loads acting on the CEVA north wall above EL +21.5 ft to the concrete fill below; and the analysis
DRAFT 30 October 2017 showed that the vertical loads acting on the north wall can safely transfer through the base slab and into the concrete fill by formation of compressive diagonal struts with a resulting demand-to-capacity ratio (D/C) of 0.75. Accordingly, calculation 160268-CA-05, Revision 0 [3] concluded that the lower portion of the CEVA north wall (below EL +19 ft) is not required as a part of the load resisting system of the CEVA.
Figure 1 - CEVA North Configuration and Measured Deformed Shape [3].
(Schematic and Not Drawn to Scale)
Although the lower portion of the north wall was determined not to be required as a part of the load resisting system of CEVA, the stability of the wall must be maintained to support the attached equipment and to resist hydrostatic pressure and seismic load if any. To determine the additional bowing that the wall can experience before repairing the wall becomes necessary, a nonlinear FE analysis based on deformed shape of the wall, using the field data (plumbness measurement),
was conducted. The analysis, using moment-curvature of the wall with conservatively neglecting the effect of compression reinforcement, showed the wall can bow out to 1.5 in. Consequently, Calculation 160268-CA-05, Revision 0 [3] recommended more frequent plumbness measurement and hammer sounding of the north face of the wall at every six month.
The subsequent threshold inspection in September 2017 revealed a maximum outward bowing of 1-7/16 in. at EL. +14 ft [4], which indicates that much of bowing margin was consumed.
Accordingly, a more detailed calculation was performed considering; the compression
DRAFT 30 October 2017 reinforcement for moment curvature, constitutive model to represent steel rupture and buckling, and the impact of upward vertical movement of CEVA (due to vertical expansion of the concrete fill below) pulling up the lower portion of the north wall. The analysis concluded that the wall can experience maximum bowing of 2 in. before reaching 90% of curvature for possible potential failure modes [5]. Hence it was recommended that the wall to be retrofitted prior to experiencing 2 in. of bowing.
In summary, the analyses showed that the lower portion of north wall of CEVA north wall can bowed to a limit of 2 in. prior to completion of retrofit, wall bowing need to be performed more frequently, and need to perform hammer sounding on the wall surface to check for any near-surface delamination in order to prevent any concrete spalling off the wall onto the equipment below.
Definition of Delamination and Related Technologies Per ACI Standard CT-13 [6], ACI Concrete Terminology, a delamination is defined as [a] planar separation in a material that is roughly parallel to the surface of the material. ACI 201.1R-08, Guide for Conducting a Visual Inspection of Concrete in Service [7], defines delamination as [a]
separation along a plane parallel to a surface, as in the case of a concrete slab, a horizontal splitting, cracking, or separation with a slab in a plane roughly parallel to, and generally near, the upper surface; found most frequently in bridge decks and caused by the corrosion of reinforcing or freezing and thawing, similar to spalling, scaling, or peeling except that delamination affects large areas and often only detected by non-destructive testing, such as tapping or chain dragging.
Acoustic impact or sounding of materials, typically done with chains, hammers, rods, or other acoustic sounding devices, can be used to identify near-surface/shallow delaminations (typically 1 to 3 in. deep) because the particular sound created by the vibration of the delamination (as excited by the hammer tapping or impact of the chain links on the surface) is within the range of human hearing. Delamination occurring deep within the concrete may not be identified using acoustic impact [8] [9] because the sound created by the vibration cannot be detected by human hearing.
An advanced nondestructive testing (NDT) method to detect delaminations is Impact-Echo (IE).
IE is a technique based on the use of a transient stress (sound) wave created using a short-duration mechanical impact to generate specific frequency stress waves that propagate into the concrete and that are reflected by flaws and external surfaces. IE detects the reflections using a transducer that measures the surface movement caused by the reflection of these waves [10].
The location and type of a variety of defects such as delamination, voids, honey-combing within the concrete elements can be detected using this technique after correlation with at least some destructive testing (such as coring or probes), but caution must be exercised because the IE signals can be affected by the member geometry (corners, edges, etc.), embedded reinforcing steel, or embedded plates. Because of the much greater range of magnitudes and frequencies that the transducer can detect, IE can detect much deeper cracks, delaminations, and internal features than simple sounding that relies on human hearing. Detailed information on this methodology is provided in ACI 228.2R-13 [11].
Mechanism of Near-Surface Delamination
DRAFT 30 October 2017 The concrete delaminations were found at localized areas along prominent horizontal cracks at approximately EL. +13 ft to +18 ft where the large bowing occurs. Because the field work was limited to only acoustic sounding with a masons hammer, the detected delamination could only have been within the near surface detection region (within the 3 in. or so) of the test. The near-surface delamination may be due to a combination of the following:
x The large bowing/bending of the concrete wall causes prominent flexure/horizontal cracks due to the concrete stress reaching and exceeding the tensile strength of concrete at the bowed area, similar to the cracking that occurs in a flexural member as shown in Figure 2 below.
Figure 2 - Flexure Cracks of a Reinforced Concrete Beam or Wall Element with Supports at Both Ends under Uniformly Distributed Loading x
By formation of the flexural cracks stresses transfer from the concrete to reinforcement, as shown in Figure 3. This transfer occurs primarily by chemical adhesion, friction forces arising from the microroughness of the interface, and the mechanical anchorage formed by the interlocking of the concrete and the intentionally created ribs or deformations rolled into the bars during manufacturing. When the vertical reinforcing bars under a high level of tension start to yield, they move with respect to the surrounding concrete; therefore, surface adhesion is lost, and friction force is reduced, requiring all of the unbalanced force to transfer through the ribs, creating compressive and shear stresses on the concrete surface, which can be resolved into tensile stresses that can result in cracking in planes that are both perpendicular and parallel to reinforcement (Figure 4).
Depending on the stress in the vertical reinforcing bars, the concrete cover, bar spacing, or transverse reinforcement, splitting cracks, such as shown in Figure 5, may occur.
[12][13]
DRAFT 30 October 2017 Figure 3 Bond Force Transfer Mechanisms [12]
Figure 4 Cracking and Failure Mode [13]
Figure 5 End View of a Member Showing Splitting Cracks between Bars and through the Concrete Cover [12]
x Simultaneously, since microcracking may have occurred at the plane of the near-surface vertical bars, it could potentially result in a weak plane between the vertical bar surface and the exterior layer (concrete cover). This may lead to localized sliding between the surface layer (concrete cover) and the interior layer along the prominent cracks.
As explained above, the near-surface concrete delamination at the north wall of the CEVA could be a unique case that is related to the deformation of north wall attributed to the concrete fill expansion. This wall need not to be considered as the load resisting system of the CEVA, and it does not contain special reinforcement condition (such as prestressing or post-tensioning tendons that cause internal delamination).
Because of the lack of any visual features indicative of internal ASR (such as map pattern cracking, exudation of gel, cracks in non-tension areas, and lack of surface staining), the observed near-
DRAFT 30 October 2017 surface delaminations do not appear to be related to any internal concrete reaction, such as alkali-silica reaction (ASR).
Proposed Validation Plan The evaluation of the lower portion of the wall to date has included visual observations, measurements of the plumbness of the wall, structural analysis on the as-deformed wall, and additional near-surface delamination survey. To provide additional information and validation that the delamination is only occurring at the near-surface region (concrete cover), SGH proposes the following plan:
x Perform IE testing at the middle portion of the wall (EL +13 ft to +18 ft), from the landing of the stairs, where the wall exhibits highest curvature and horizontal cracks with localized near-surface delaminations to attempt to identify the presence and depth of any indicated delaminations or other features. Note that correlation with core test results (see below) will be required to correlate any IE results to the indicated depths of the features.
x Extract two shallow partial-depth core samples, each at an isolated delaminated area.
The depth of the cores shall be 6 in. minimum to capture any shallow delaminations present.
x If required, extract two additional deep partial-depth core samples, each adjacent to an isolated delaminated area. The desired dimension of the concrete cores may be as deep as 16 in. (2/3 of the wall thickness) in order not to breach the RCA boundary. A borescope may then be used to observe the condition of the interior of the core holes in order to confirm the in-depth concrete condition prior to patching the core holes.
References
[1]
Simpson Gumpertz & Heger Inc., ASR Inspections on Containment Enclosure Ventilation Area, NextEra Energy Seabrook Facility, Seabrook, NH, SGH Site Visit Report No. 160268-SVR-05, Revision 0, 22 March 2017 (FP 101122).
[2]
CSA International, A864-00, Guide to the Evaluation and Management of Concrete Structures Affected by Alkali-Aggregate Reaction, Toronto, ON, Canada, 2000.
[3]
Simpson Gumpertz & Heger Inc., Evaluation of Containment Enclosure Ventilation Area, Calculation No. 160268-CA-05, Revision 0, 22 March 2017 (FP 101121).
[4]
Simpson Gumpertz & Heger Inc., September 2017, Threshold Inspections for the North Wall of the Containment Enclosure Ventilation Area (CEVA), NextEra Energy Seabrook Facility, Seabrook, NH, SGH Site Visit Report No. 170444-SVR-01,Revision A, 25 September 2017.
[5]
Simpson Gumpertz & Heger, License Amendment Request & NRC Review Support, NextEra Energy Seabrook Station, Seabrook, NH, Document No. 170444-L-001, Revision A, 23 October 2017.
DRAFT 30 October 2017
[6]
American Concrete Institute, ACI CT-13, ACI Concrete Terminology, an ACI Standard, Farmington Hills, MI, 2013.
[7]
American Concrete Institute, ACI 201.1R-08, Guide for Conducting a Visual Inspection of Concrete In Service, Farmington Hills, MI, 2008.
[8]
International Concrete Repair Institute, Technical Guidelines, Guide for Nondestructive Evaluation Methods for Condition Assessment, Repair, and Performance Monitoring of Concrete Structures, Guideline No. 210.4-2009, Des Plaines, IL
[9]
Yehai, Abudayyeh, Abdel-Qader, and Zalt, GPR, Chain Drag, and Ground Truth:
Correlation of Bridge Deck Assessment Data, TRB 2008 Annual Meeting, Transportation Research Board, Washington DC.
[10]
Mary Sansalone, Impact-Echo: The Complete Story, ACI Structural Journal, V. 94, No.6 November-December 1997, Farmington Hills, MI.
[11]
American Concrete Institute, ACI 228.2R-13, Report on Nondestructive Test Methods for Evaluation of Concrete in Structures, Farmington Hills, MI, 2013.
[12]
American Concrete Institute, ACI 408R-03 (Reapproved 2012), Bond and Development of Straight Reinforcing Bars in Tension, Farmington Hills, MI, 2003.
[13]
L. Lemnizer, S. Schroder, et al., Bond Behavior between Reinforcing Steel and Concrete under Multiaxial Loading Condition in Concrete Containments, 20th International Conference on Structural Mechanism in Reactor Technology (SMIRT 20), Division II, Page 1734, Espoo, Finland, August 9-14, 2009.
6 November 2017 Mr. Edward Carley Engineering Supervisor - License Renewal NextEra Energy Seabrook, LLC.
P.O. Box 300, Lafayette Road Seabrook, NH 03874 Project 170444 -
License Amendment Request & NRC Review Support, NextEra Energy Seabrook Station, Seabrook, NH Reference -
Evaluation of Containment Enclosure Ventilation Area (CEVA),
Calculation 160268-CA-055HY (FP101122), 22 March 2017 Document Number: 170444-L-001
Dear Mr. Carley:
The structural evaluation of the Containment Enclosure Ventilation Area (CEVA), referenced above, showed that its north wall between EL +3 and +19 ft was bowed outward with a maximum out-of-plumbness of 1.25 in., measured during SGH field observation in February 2017. The referenced calculation showed that the wall can move by an additional 25% (reaching to 1.5 in.
at the point of maximum bowing) before conducting a more robust analysis or repairing the wall becomes necessary.
The bowing limit of 1.5 in. was calculated conservatively in the referenced calculation by neglecting the compression reinforcement in calculating the moment-curvature behavior of the wall. The limit of bowing is recalculated as shown in Attachment A considering the compression reinforcement in the moment-curvature calculation, and including the effects of upward vertical movement of CEVA. The upward movement of CEVA can impose vertical tension in the north wall of CEVA. Accordingly, moment-curvature relationships are calculated at different levels of tension.
At each level of axial force, a limiting curvature is determined to avoid unacceptable behavior. As explained in Attachment A, the curvature value of 0.003 1/in. corresponds either to the buckling of compression reinforcement (for cases with low level of axial tension) or rupture of tension reinforcement (for cases with high level of axial tension). Conservatively, 90% of this curvature value (0.0027 1/in.) is selected for computing the maximum bowing that the wall can resist.
The computed moment-curvature relationships are assigned to a finite element model of the wall, and nonlinear analyses are performed to determine the lateral displacement at which the curvature of the wall at the point of maximum bowing reaches the limiting curvature. Figure A2 in Attachment A shows that 2 in. of lateral wall deformation induces curvature of 0.0027 1/in. in the wall with a low level of axial force, while the same displacement induces curvature of 0.0023 1/in.
in the wall with a high level of axial tension. Therefore, the wall can resist a lateral bowing of 2 in.
Mr. Edward Carley - Project 170444 6 November 2017 Document No. 170444-L-001 Revision 0 before buckling or rupture of the vertical reinforcement will occur (with 10% margin), and it is recommended that the wall be retrofitted prior to it experiencing 2 in. of bowing.
The site visit report (170444-SVR-01-R0, FP101192-00) for the recent measurements indicates that the wall moved outward since the previous measurements; bulging has increased to 1-7/16 in. Additionally, at a localized area, hammer sounding indicated portions of the concrete cover potentially susceptible to separation, especially at areas with larger horizontal cracks. Therefore, sensitive equipment or processes should be protected against possible falling pieces of concrete cover from this wall before it is retrofitted.
Sincerely yours, Said Bolourchi Michael Mudlock, P.E.
Senior Principal Senior Project Manager NH License No. 14808 I:\\BOS\\Projects\\2017\\170444.00-LARS\\Workspace\\CEVA North Wall\\170444-L-001 Rev. 0.docx
PROJECT NO:
170444 DATE:
Nov 2017 CLIENT:
NextEra Energy Seabrook BY:
MR.M.Gargari
SUBJECT:
Evaluation of Additional Displacement for the North Wall of CEVA VERIFIER:
I. Baig ATTACHMENT A MOMENT CURVATURE RELATION FOR THE CEVA NORTH WALL A1.
REVISION HISTORY Revision 0: Initial document.
A2.
OBJECTIVE OF CALCULATION The objective of this calculation is to compute moment-curvature diagrams for the north wall of Containment Enclosure Ventilation Area (CEVA) structure subjected to different tensile force.
A3.
RESULTS AND CONCLUSIONS Figure A2 presents moment-curvature diagram for the wall section subjected to different tensile force. As can be seen from the figure, by increasing the magnitude of tensile force, the failure mode changes from compressive rebar buckling to tensile rebar rupture. For all cases, the point of severe damage initiation approximately corresponds to curvature value of 0.003 (1/in.). Accordingly, this point is selected as a limiting curvature and the wall is allowed to deform up to this curvature.
Figure A3 provides a comparison between two cases, one with accounting for the effect of compressive rebars and the other one without considering the compressive rebars. As can be seen from the figure, including the resistance offered by compressive reinforcement does not affect the ultimate capacity noticeably, however, it increases the ductility of a section.
A4.
DESIGN DATA / CRITERIA See Section 4 of the calculation main body (160268-CA-05 Rev.0).
A5.
ASSUMPTIONS A5.1 Justified assumptions There are no justified assumptions.
A5.2 Unverified assumptions There are no unverified assumptions.
Attachment A
- A Revision 0
A6.
METHODOLOGY To calculate the moment-curvature diagrams, sectional analysis based on fiber section method for integrating over the cross section is used. In this method, the cross section is discretized into fibers (or layers subjected to unidirectional bending), and an appropriate material model is assigned to each fiber.
Figure A1 demonstrates a typical fiber section discretization. In this study, each section is discretized into 20 fibers/layers. The concrete material is represented by Kent and Park [A5] model in compression and Stevens exponential softening model in tension [A3]. Reinforcing steel bars are modeled using elastic perfectly plastic material with strain cutoff of 0.007 in tension and accounting for inelastic buckling model of Kashani et al. [A4] in compression.
Moment-curvature diagrams are then calculated for axial tension of 0, 10, 30 and 60 kips. Each point is derived by selecting an axial force, and then changing curvature value and calculating the moment. Figure A2 presents the computed moment-curvature diagrams.
An additional study is conducted to show the effect of including or excluding compressive reinforcement.
The study shows accounting for the effect of compressive rebars increases the ductility of a member as presented in Figure A3; therefore, the member can accommodate more displacement.
A7.
REFERENCES
[A1]
Simpson Gumpertz & Heger Inc., Evaluation of Containment Enclosure Ventilation Area, 160268-CD-05 Rev. 1, Waltham, MA, Mar. 2017.
[A2]
United Engineers & Constructors Inc., Seabrook Station Structural Design Drawings.
[A3]
Yuan Lu, and Marios Panagiotou. "Three-dimensional cyclic beam-truss model for nonplanar reinforced concrete walls." Journal of Structural Engineering, 2013, 140(3): 04013071.
[A4]
Mohammad M.
- Kashani, Laura N.
- Lowes, Adam J.
- Crewe, Nicholas A.
Alexander, Phenomenological hysteretic model for corroded reinforcing bars including inelastic buckling and low-cycle fatigue degradation, Computer and Structures, 156 (1), 58-71, 2015.
[A5]
Dudley. C. Kent, and Robert Park, Flexural members with confined concrete, ASCE Journal of Structural Division, 97 (ST7), 1969-1990, 1971.
Attachment A
- A Revision 0
A8.
COMPUTATION Geometry Rebar diameter db 1.128in
Reinforcement ratio
2 1 in2 12in 24
in 6.944 10 3
u
Concrete Material Model Compressive strength of concrete fc 3
ksi
Kent & Park Model Strain at Peak compressive strength co 0.002
Strain at 50% compressive strength 50u 3
0.002 fc psi
fc psi 1000
4.5
10 3
u
Model parameter Z
0.5 50u co
200
Residual compressive strength fc.res fc 0.025
75
psi
Steven's Model Young's modulus of concrete Ec 3120ksi
Tensile strength of concrete ft 5
fc psi
273.861 psi
Strain at cracking cr ft Ec 8.778 10 5
u
Model parameter that controls residual M
75mm db 0.018
Model parameter that controls softening slope t
540 M
4.005 103 u
MATconc
( )
min fc.res fc 1 Z
co
¬
º1/4
¬
º1/4
co
if fc 2
co
co
§¨©
- ¸¹ 2
¬
º 1/4
co
d 0
if Ec
0
d cr
if ft 1
M
(
) e t
cr
M
¬
º1/4
cr
d if
Constitutive model for concrete Attachment A
- A Revision 0
0.01
5
10 3
u 0
4
2
0 Strain Stress (ksi)
MATconc c
ksi c
Steel Material Model Yield strength of steel fy 60ksi
Young's modulus of steel Es 29000ksi
Yield strain y
fy Es 2.069 10 3
u
Rupture strain sr 0.07
Account for buckling Buckling 1
Put 0 to ignore, put 1 to consider Kashani Model (buckling)
Unbraced length/Diameter LD 15
Slenderness ratio p
fy 100MPa LD
30.509
Model parameters 1
4.572 p
74.43
65.057
2 318.4 e 0.071
p
36.495
star 3.75 fy LD
15 ksi
Attachment A
- A Revision 0
Constitutive model for steel MATsteel
( )
fy
Buckling 0
=
if star fy star
e 1 2
y
y
¬
º1/4
¬
º 1/4
otherwise
y
if fy y
d sr
if 0
sr
d if Es
otherwise
0.05
0 0.05 50
0 50 Strain Stress (ksi)
MATsteel s
ksi s
Concrete Fibers Width of fibers b
12in
Ref. 2, 2ft thick wall Total thickness or height h
24in
Number of fibers ConcNum 20
Height of fibers ConcH h
ConcNum 1.2 in
Concrete fiber coordinates Concy ansi h
2
ConcH 2
i 1
(
) ConcH
m i
1 ConcNum
for ans
Concrete fiber strain Conc o
ansi o
Concyi
m i
1 ConcNum
for ans
Attachment A
- A Revision 0
Concrete fiber stress Conc o
ansi MATconc Conc o
i
m i
1 ConcNum
for ans
Concrete fiber force ConcF o
ansi Conc o
i b ConcH
m i
1 ConcNum
for ans
Reinforcement/Steel fibers Depth to reinforcement d
20.5in
Ref. 2, 2ft thick wall Area of tensile reinforcement
(#9@12 in.)
As 1in2
Number of reinforcement in row, e.g. equal to 2 for tensile and compressive SteelNum 2
Depth to reinforcement fiber Steely1 d
h 2
§¨©
- ¸¹
8.5
in
Steely2 d
h 2
8.5 in
Area of reinforcement fiber SteelAs1 As 1 in2
SteelAs2 As 1 in2
Steel fiber strain Steel o
ansi o
Steelyi
m i
1 SteelNum
for ans
Steel fiber stress Steel o
ansi MATsteel Steel o
i
m i
1 SteelNum
for ans
Steel fiber force SteelF o
ansi Steel o
i SteelAsi
m i
1 SteelNum
for ans
Attachment A
- A Revision 0
Axial Equilibrium Force o
ans1 0
m ans1 ans1 ConcF o
i
m i
1 ConcNum
for ans2 0
m ans2 ans2 SteelF o
i
m i
1 SteelNum
for ans ans1 ans2
m
Moment Equilibrium Moment o
ans1 0
m ans1 ans1 1
ConcF o
i
Concyi
m i
1 ConcNum
for ans2 0
m ans2 ans2 1
SteelF o
i
Steelyi
m i
1 SteelNum
for ans ans1 ans2
m
Solution Known parameters Axial force P
60kip
Iteration Curvature
0.003 1 in
Solve for strain at centroid Axial strain at centroid (initial guess) xo 0.03
Requires iteration Axial force equilibrium f x
( )
Force x
(
)
P
cent root f xo
xo
0.027
Sectional forces Force cent
60 kip
Moment cent
48.079 kip ft
Attachment A
- A Revision 0
Stress and strain in concrete and steel Steel fiber stress and strain Rebar Steel cent
0.052 1.266 10 3
u
§
¨
©
¸
¹
Rebar Steel cent
60 36.723
§¨©
- ¸¹ ksi
SteelF cent
60 36.723
§¨©
- ¸¹ kip
Concretey Concy
Concrete fiber stress and strain Concrete Conc cent
Concrete Conc cent
Maximum compressive strain in concrete max.comp Rebar2 Rebar1
Steely2 Steely1
h 2
Steely1
§¨©
- ¸¹
Rebar1
9.234
10 3
u
Attachment A
- A Revision 0
A9.
TABLES There are no tables.
A10.
FIGURES Figure A1: Schematic representation of fiber section method Figure A2: Moment - curvature diagrams for different axial force Attachment A
- A Revision 0
Figure A3: Moment - curvature diagram considering the effect of including or excluding compressive rebars Attachment A
- A Revision 0
RI
5(3257$33529$/6+((7
&OLHQW
1H[W(UD(QHUJ\\6HDEURRN
3URMHFW1R
3URMHFW
6XSSRUWIRU3URPSW2SHUDELOLW\\'HWHUPLQDWLRQV32'V1H[W(UD(QHUJ\\6HDEURRN
6WDWLRQ1+
5HSRUW1R
6955
5HSRUW7\\SH
6LWH9LVLW5HSRUW
7LWOH
6HSWHPEHU 7KUHVKROG,QVSHFWLRQV IRU WKH 1RUWK :DOO RI WKH
&RQWDLQPHQW (QFORVXUH 9HQWLODWLRQ $UHD &(9$ 1H[W(UD (QHUJ\\
6HDEURRN)DFLOLW\\6HDEURRN1+
1XPEHURISDJHVLQFOXGLQJWKLVSDJH
$UHWKHUHXQYHULILHGDVVXPSWLRQV<1
1
,VWKLVUHSRUWVDIHW\\UHODWHGSHUFRQWUDFW<1
<
2EMHFWLYH
7RUHSRUW6HSWHPEHUWKUHVKROGPHDVXUHPHQWUHVXOWVRIWKHORZHUSRUWLRQRIWKH1RUWK
- DOO RI WKH &RQWDLQPHQW (QFORVXUH 9HQWLODWLRQ $UHD &(9$ DQG WR GHWHUPLQH ZKHWKHU WKH
WKUHVKROGOLPLWVIRUWKH&(9$1RUWK:DOOKDYHEHHQH[FHHGHG
5HYLVLRQ
'HVFULSWLRQV
,QLWLDO'RFXPHQW
5HYLVLRQ
3UHSDUHU'DWH
,QGHS9HULILHU'DWH
$SSURYHU'DWH
/L\\LQJ-LDQJ
0LFKDHO0XGORFN
0DWWKHZ56KHUPDQ
2FWREHU
2FWREHU
2FWREHU
RI
6,7(9,6,75(325712
'RFXPHQW,'1R6955
5HSRUW%\\/L\\LQJ-LDQJ
'DWHRI6LWH9LVLW
6HSWHPEHU
'DWH5HSRUW,VVXHG
2FWREHU
3URMHFW
.H\\ZRUG
32'6
&RQWUDFW1R
5HOHDVH
([HFXWHG
0DUFK
3URMHFW1DPH6XEMHFW
6XSSRUWIRU3URPSW2SHUDELOLW\\
'HWHUPLQDWLRQV32'V1H[W(UD
(QHUJ\\6HDEURRN6WDWLRQ1+
3XUSRVH
3HUIRUPWKUHVKROGLQVSHFWLRQVIRU
WKHQRUWKZDOORI&(9$DV
UHTXLUHGSHUWKHVWUXFWXUDO
HYDOXDWLRQRIWKH&(9$VWUXFWXUH
0HHWLQJ:RUN/RFDWLRQ
6HDEURRN6WDWLRQ
7LPH+/-
IURP
DP
WR
SP
- HDWKHU
,QGRRUV
$PELHQW7HPSHUDWXUH
)
5HYLHZHG%\\
0LFKDHO0XGORFN
2FWREHU
$SSURYHG%\\
0DWWKHZ56KHUPDQ
2FWREHU
7KLV6LWH9LVLW5HSRUWFRQVLVWVRIWKHIROORZLQJ
5HSRUW&RQWHQW
&RQWHQW
7LWOH
3DJH
&RYHU6KHHW
5HSRUW$SSURYDO6KHHW
0DLQ5HSRUW
6LWH9LVLW5HSRUW1R6955
+/-
3KRWRJUDSKV
3KRWRJUDSKDQG)LJXUH3DJHV
+/-
/LVWRI7DEOHV
&RQWHQW
7LWOH
3DJH
7DEOH
/LVWRI(TXLSPHQWDQG&DOLEUDWLRQ5HFRUG
/LVWRI)LJXUHV
&RQWHQW
7LWOH
3DJH
)LJXUH
3OXPEQHVVSURILOHRI1RUWK:DOORI&(9$IURP(/IWWR(/IW
6LWH9LVLW5HSRUW1R
RI
2FWREHU
'RFXPHQW,'1R6955
5HYLVLRQ
$EEUHYLDWLRQV
x
1((+/-1H[W(UD(QHUJ\\6HDEURRN//&
x
1((+/-6HDEURRN+/-1H[W(UD(QHUJ\\6HDEURRN)DFLOLW\\
x
6*++/-6LPSVRQ*XPSHUW] +HJHU,QF
x
$65+/-$ONDOL6LOLFD5HDFWLRQ
x
&(%+/-&RQWDLQPHQW(QFORVXUH%XLOGLQJ
x
&%+/-&RQWDLQPHQW%XLOGLQJ
x
$=+/-$]LPXWK
x
&(9$+/-&RQWDLQPHQW(QFORVXUH9HQWLODWLRQ$UHD
x
0HFK3HQ+/-0HFKDQLFDO3HQHWUDWLRQ
)LHOG,QVSHFWRUV
x
/L\\LQJ-LDQJ+/-3ULPDU\\)LHOG,QVSHFWRU6*+
x
3L\\XVK*DUJ+/-)LHOG,QVSHFWRU6*+
3HUVRQV&RQWDFWHG
x
-DFO\\Q+XOEHUW+/-1(1*,,/LFHQVH5HQHZDO1((
x
'DYH&DUOLQR,,,+/-1XFOHDU&RQVWUXFWLRQ/HDG1((
5(9,6,21+,6725<
5HYLVLRQ+/-,QLWLDO'RFXPHQW
,1752'8&7,21
1H[W(UD(QHUJ\\6HDEURRN//&1((FRQWUDFWHG6LPSVRQ*XPSHUW] +HJHU,QF6*+WR
SHUIRUP VWUXFWXUDO HYDOXDWLRQ RI VHOHFWHG VWUXFWXUHV DW WKH 1H[W(UD (QHUJ\\ 6HDEURRN )DFLOLW\\
1((6HDEURRN LQ RUGHU WR GHWHUPLQH WKHLU VXVFHSWLELOLW\\ WR FRQFUHWH GHIRUPDWLRQ FDXVHG E\\
$65VZHOOLQJFUHHSDQGVKULQNDJH2Q0DUFK6*+LVVXHGDVWUXFWXUDOHYDOXDWLRQRI
WKH&(9$VWUXFWXUHFRQVLGHULQJVWUHVVHVLQWKHDVGHIRUPHGFRQGLWLRQLQDGGLWLRQWRHDFKRIWKH
ORDG FRPELQDWLRQV LGHQWLILHG LQ WKH 8)6$5 IRU WKH &(9$ VWUXFWXUDO HYDOXDWLRQ 'HWDLOHG
LQIRUPDWLRQLVSURYLGHGLQ6*+'RFXPHQW&$5HYLVLRQ >@LQZKLFK6HFWLRQ
³7KUHVKROG 0RQLWRULQJ 0HDVXUHPHQWV DQG /LPLW' UHFRPPHQGV WKDW DOWKRXJK WKH &(9$
VWUXFWXUHLVHYDOXDWHGDVD6WDJH2QHVWUXFWXUHWKHWKUHVKROGLQVSHFWLRQRIWKHORZHUSRUWLRQRI
WKHQRUWKZDOOEHFRQGXFWHGHYHU\\VL[PRQWKVZLWKWKHIROORZLQJVFRSHRIZRUNDQGDVVRFLDWHG
WKUHVKROGOLPLWV
6LWH9LVLW5HSRUW1R
RI
2FWREHU
'RFXPHQW,'1R6955
5HYLVLRQ
x
0HDVXUHWKHRXWRISOXPEQHVVRIWKHQRUWKZDOOIRUDQ\\LQFUHDVHLQGLVSODFHPHQW,IWKH
FXUUHQWO\\PHDVXUHGPD[LPXPERZLQJRILQUHDFKHVLQFRUUHVSRQGLQJWRD
LQFUHDVHEH\\RQGWKHFXUUHQWPD[LPXPPHDVXUHGERZLQJIXUWKHUHYDOXDWLRQRI
WKHZDOOVWDELOLW\\RURWKHUDSSURSULDWHDFWLRQLVUHTXLUHG
x
+DPPHUVRXQGWKHQRUWKIDFHYLVLEOHIDFHRIWKHZDOOEHWZHHQ(/IWDQG(/IW
WRFKHFNIRUDQ\\QHDUVXUIDFHGHODPLQDWLRQ,IDQ\\DUHDZLWKGHODPLQDWHGFRQFUHWHLV
GHWHFWHG FRQVLGHU UHPRYLQJ DQG UHSDLULQJ RU RWKHUZLVH UHVWUDLQLQJ WKH XQVRXQG
FRQFUHWHWRSUHYHQWDQ\\FRQFUHWHVSDOOLQJRIIWKHZDOORQWRWKHHTXLSPHQWDQGVWDLUV
EHORZ
,Q6HSWHPEHUVL[PRQWKVDIWHU6*+LVVXHGWKHVWUXFWXUDODQDO\\VLVHYDOXDWLRQRIWKH&(9$
VWUXFWXUH1((UHTXHVWHGWKDW6*+SHUIRUPWKHWKUHVKROGLQVSHFWLRQVRIWKH&(9$QRUWKZDOO
SHUWKHVFRSHRIZRUNGHVFULEHGDERYH
(48,30(17$1'&$/,%5$7,216
7DEOHSURYLGHVDOLVWRIHTXLSPHQWZLWKDVVRFLDWHGFDOLEUDWLRQGDWDXVHGIRUWKHWKUHVKROG
PHDVXUHPHQWVGXULQJWKLVWDVN
7DEOH+/-/LVWRI(TXLSPHQWDQG&DOLEUDWLRQ5HFRUG
(TXLSPHQW
$VVHW1R0RGHO,'
/DVW&DOLEUDWLRQ
'DWH
&DOLEUDWLRQ'XH
'DWH
IW7DSH0HDVXUH
3UD]3UHFLVLRQ&UDIWHG
+/-
+/-
IW7DSH0HDVXUH
6WDQOH\\3RZHU/RFN
+/-
+/-
9DLVDOD'LJLWDO+\\JURPHWHU
)/6
$XJXVW
)HEUXDU\\
1RW&DOLEUDWHG3HU1((FDOLEUDWLRQFRQWUROVDUHQRWUHTXLUHGIRUVWDQGDUGRIIWKHVKHOIPHDVXULQJHTXLSPHQWUXOHUV
WDSHPHDVXUHVOHYHOVHWFZKLFKLVQRWOLNHO\\WRFKDQJHRUGULIWGXULQJXVH
1((6HDEURRNFDOLEUDWHGWKLVHTXLSPHQWLQDFFRUGDQFHZLWKWKHLU4$7RSLFDO5HSRUW
6&23(2):25.
2Q 6HSWHPEHU 6*+ SHUIRUPHG WKUHVKROG LQVSHFWLRQV RI WKH QRUWK ZDOO RI WKH &(9$
VWUXFWXUHXQGHU1((6HDEURRN:RUN2UGHUDQG30,'IXUWKHUGHVFULEHG
EHORZ
x
0HDVXUHWKHRXWRISOXPEQHVVRIWKHQRUWKZDOOIRUDQ\\LQFUHDVHLQGLVSODFHPHQW
x
9LVXDOO\\VXUYH\\DQGSHUIRUPDGHODPLQDWLRQVXUYH\\RIWKHQRUWKIDFHYLVLEOHIDFHRIWKH
QRUWKZDOOIURP(/IWWR(/IWZKHUHDFFHVVLEOHWRFKHFNIRUDQ\\QHDUVXUIDFH
GHODPLQDWLRQ
x
'RFXPHQW WKH YLVXDO REVHUYDWLRQV PHDVXUHPHQWV DQG ILQGLQJV LQ D VLWH YLVLW UHSRUW
695WR1((
$ GHODPLQDWLRQ LV DQ\\ SODQDU VHSDUDWLRQ LQ D PDWHULDO WKDW LV URXJKO\\ SDUDOOHO WR WKH VXUIDFH RI WKH
PDWHULDOWKDWLVHVVHQWLDOO\\IRUPHGE\\DFUDFNWKDWLVSDUDOOHOWRWKHVXUIDFHRIWKHZDOO>@
6LWH9LVLW5HSRUW1R
RI
2FWREHU
'RFXPHQW,'1R6955
5HYLVLRQ
216,7(7+5(6+2/',163(&7,216$1'5(68/76
- DOO3OXPEQHVV0HDVXUHPHQWV
6*+ PHDVXUHG WKH RXWRISOXPEQHVV RI WKH QRUWK IDFH RI WKH QRUWK ZDOO IURP (/ IW WR
(/IWXVLQJDSOXPEEREDQGDWDSHPHDVXUH6*+VXVSHQGHGWKHSOXPEEREIURPDVWULQJ
UXQQLQJDORQJWKHZDOOVXUIDFHIURP(/IWWR(/IWWRSRIWKH0HFK3HQDQGPHDVXUHG
WKHGLVWDQFHIURPWKHZDOOVXUIDFHWRWKHFHQWHURIWKHVWULQJVWDUWLQJDW(/IWIWIURPWKH
WRSRIWKH0HFK3HQDQGFRQWLQXLQJWR(/IWIWDERYHWKHWRSRIWKHEDVHVODERIWKH
&(9$%XLOGLQJ3KRWRVDQG6*+SHUIRUPHGWKHPHDVXUHPHQWVIURPERWKVLGHVRIWKH
VWDLUVZKLFKDUHORFDWHGQHDUWKHFHQWHURIWKHZDOO
7KHSOXPEQHVVSURILOHRIWKHQRUWKIDFHRIWKHQRUWKZDOODVLOOXVWUDWHGLQ)LJXUHLQGLFDWHV
RXWZDUGEXOJLQJUHODWLYHWRWKHIDFHRIWKHZDOODW(/IWZLWKD]RQHRIUHODWLYHO\\XQLIRUP
EXOJLQJSUHVHQWIURP(/IWWR(/IWZLWKWKHPD[LPXPRXWZDUGEXOJLQJRILQ
RFFXUULQJDW(/IW
9LVXDODQG'HODPLQDWLRQ6XUYH\\
6*+YLVXDOO\\REVHUYHGWKHHQWLUHIDFHRIWKHQRUWKZDOOZKHUHDFFHVVLEOH3KRWR6*+QRWHG
IUHTXHQWSURPLQHQWKRUL]RQWDOFUDFNVIURP(/IWWR(/IWDFURVVWKHHQWLUHQRUWKZDOO
7KHFUDFNLQJFRQGLWLRQLVPRVWREYLRXVRQWKHHDVWVLGHRIWKHZDOODGMDFHQWWRWKH&(%ZKHUHLW
LVDERYHWKHHTXLSPHQWWKLVSRUWLRQRIWKHZDOOZDVLQDFFHVVLEOHIRUFORVHREVHUYDWLRQDWWKH
WLPHRILQVSHFWLRQ6*+GLGQRWQRWHDQ\\DSSDUHQWVLJQLILFDQWFKDQJHVLQWKHFUDFNLQJFRQGLWLRQ
DVFRPSDUHGWR6*+¶VSULRUVXUYH\\LQ1RYHPEHU>@
6*+SHUIRUPHGDGHODPLQDWLRQVXUYH\\RIWKHDFFHVVLEOHQRUWKIDFHRIWKHQRUWKZDOOIURPWKH
IORRUVODEDW(/IWDQGIURPWKHVWDLUVDWWKHPLGGOHDQGWRSODQGLQJV6*+SHUIRUPHGWKH
GHODPLQDWLRQVXUYH\\E\\VRXQGLQJWKHZDOOZLWKDPDVRQ¶VKDPPHUDQGQRWHGKROORZVRXQGLQJ
DUHDVDWWKHIROORZLQJORFDWLRQV
x
7ZRORFDOL]HGDUHDVDWWKHERWWRPFRUQHUVRIWKH&(9$GRRUDSSUR[LPDWHO\\VTIWDQG
VT IW UHVSHFWLYHO\\ QH[W WR WKH VWDLU SODWIRUP JUDWLQJ DW (/ IW LQ 3KRWRV
DQG
x
0XOWLSOHORFDOL]HGDUHDVDORQJFUDFNVIURP(/ IWWRIWDWWKHZDOODERYHWKH
PLGGOH ODQGLQJ DUHD RI WKH VWDLUV 7KH FUDFNV DW WKH KROORZVRXQGLQJ DUHDV H[KLELW
ZLGWKVJUHDWHUWKDQLQ3KRWRVWKURXJK7KHSRUWLRQVRIWKHFRQFUHWHZDOO
DERYHWKHHTXLSPHQWFRXOGQRWEHVRXQGHGGXHWRDFFHVVUHVWULFWLRQV7KHFUDFNVDW
WKHLQDFFHVVLEOHORFDWLRQVSDUWLFXODUO\\RQWKHHDVWVLGHDGMDFHQWWRWKH&(%DSSHDUWR
EHZLGHUWKDQWKHFUDFNVDVVRFLDWHGZLWKWKHKROORZVRXQGLQJDUHDVDWWKHVWDLUV
6800$5<',6&866,216$1'5(&200(1'$7,216
6*+ SHUIRUPHG WKUHVKROG LQVSHFWLRQV RI WKH QRUWK ZDOO RI WKH &(9$ VWUXFWXUH LQ
6HSWHPEHUDQGIRXQGWKHIROORZLQJ
x
7KH FRQFUHWH VXUIDFH RI WKH QRUWK ZDOO EHWZHHQ (/ IW DQG (/ IW H[KLELWV
H[WHQVLYH KRUL]RQWDO FUDFNV 6*+ QRWHG QR VLJQV RI VLJQLILFDQW FKDQJHV LQ FUDFNLQJ
FRQGLWLRQDVFRPSDUHGWRWKHSULRULQVSHFWLRQLQ1RYHPEHU>@
6LWH9LVLW5HSRUW1R
RI
2FWREHU
'RFXPHQW,'1R6955
5HYLVLRQ
x 7KHUHVXOWVRIZDOOSOXPEQHVVPHDVXUHPHQWVEHWZHHQ(/IWWR(/IWLQGLFDWH DQRXWZDUGEXOJLQJRIWKHZDOOZLWKDPD[LPXPGLVSODFHPHQWRILQDW(/IW
UHODWLYHWRWKHQHDUEDVHRIWKHQRUWKZDOODW(/IW7KHPD[LPXPRXWZDUGEXOJLQJ DSSHDUVWRKDYHLQFUHDVHGIURPWKH1RYHPEHULQVSHFWLRQVZKHQLWZDVLQ
RFFXUULQJDW(/IWWRIW7KHPD[LPXPERZLQJUHPDLQVZLWKLQWKHWKUHVKROGOLPLW
LQ
x
%DVHGRQDGHODPLQDWLRQVXUYH\\XVLQJFRQYHQWLRQDOKDPPHUVRXQGLQJZKLFKLVOLPLWHG LQGHWHFWLRQUDQJHWRQHDUVXUIDFHVKDOORZW\\SLFDOO\\WRLQGHHSGHODPLQDWLRQV>@
6*+QRWHGORFDOL]HGQHDUVXUIDFHFRQFUHWHGHODPLQDWLRQVDWWKHDFFHVVLEOHDUHDVIURP WKHVWDLUZHOOWKDWDUHSULPDULO\\DVVRFLDWHGZLWKYLVLEOHKRUL]RQWDOFUDFNV6*+FRXOGQRW SHUIRUPDGHODPLQDWLRQVXUYH\\DERYHWKHHTXLSPHQWKRZHYHUEDVHGRQWKHREVHUYHG FUDFNLQJFRQGLWLRQLWLVOLNHO\\WKDWDGGLWLRQDOQHDUVXUIDFHGHODPLQDWLRQVDUHSUHVHQWDW WKHSURPLQHQWKRUL]RQWDOFUDFNVDERYHWKHHTXLSPHQW7KHQHDUVXUIDFHGHODPLQDWLRQV PD\\IXUWKHUGHYHORSLQWRFRQFUHWHVSDOOVWKDWFRXOGEUHDNRIIIURPWKHZDOODQGIDOORQWR WKHVWDLUVDQGHTXLSPHQWEHORZ
x 6*+UHFRPPHQGVWKDWFRQFUHWHUHSDLUVRIWKHQRUWKZDOORI&(9$EHSODQQHGIRUWKH QHDUIXWXUHWRDGGUHVVQHDUVXUIDFHGHODPLQDWLRQVDQGSRWHQWLDOIXWXUHVSDOOLQJ,QWKH PHDQWLPH WHPSRUDU\\ SURWHFWLRQ RU FRQFUHWH UHVWUDLQWV FRXOG EH SURDFWLYHO\\ DQG FRQVHUYDWLYHO\\LQVWDOOHGWRSUHYHQWSRWHQWLDOFRQFUHWHVSDOOVIURPFRQWDFWLQJVHQVLWLYH SRUWLRQVRIWKHHTXLSPHQWDQGFDEOLQJ
5()(5(1&(6
>@
6LPSVRQ *XPSHUW] +HJHU,QF Evaluation of Containment Enclosure Ventilation Area, &DOFXODWLRQ1R&$5HYLVLRQ0DUFK)3
>@
$PHULFDQ&RQFUHWH,QVWLWXWH$&,5Guide for Conducting a Visual Inspection of Concrete In Service)DUPLQJWRQ+LOOV0,
>@
6LPSVRQ *XPSHUW] +HJHU,QF ASR Inspections on Containment Enclosure Ventilation Area, NextEra Energy Seabrook Facility, Seabrook, NH, 6*+ 6LWH 9LVLW 5HSRUW1R6955HYLVLRQ0DUFK)3
>@
<HKDL $EXGD\\\\HK $EGHO4DGHU DQG =DOW *35 &KDLQ 'UDJ DQG *URXQG 7UXWK
&RUUHODWLRQ RI %ULGJH 'HFN $VVHVVPHQW 'DWD 75% $QQXDO 0HHWLQJ
7UDQVSRUWDWLRQ5HVHDUFK%RDUG:DVKLQJWRQ'&
6LWH9LVLW5HSRUW1R
RI
2FWREHU
'RFXPHQW,'1R6955
5HYLVLRQ
3KRWR
6*+PHDVXULQJWKH
SOXPEQHVVRIWKH
ZDOOZLWKDSOXPE
EREDWWDFKHGWRD
VWULQJ
3KRWR
9LHZGRZQWKH
SOXPEEREVWULQJ
\\HOORZDUURZ
H[WHQGLQJIURP
(/IWWRIW
6LWH9LVLW5HSRUW1R
RI
2FWREHU
'RFXPHQW,'1R6955
5HYLVLRQ
3KRWR
2YHUDOOYLHZRIWKHQRUWKIDFH
RIWKHQRUWKZDOO
3KRWR
&RQFUHWHGHODPLQDWLRQDWWKH
VWDLUSODWIRUP(/IWWR
WKHOHIWRIWKHGRRUDVVKRZQ
E\\WKHEOXHKDWFKLQJ
6LWH9LVLW5HSRUW1R
RI
2FWREHU
'RFXPHQW,'1R6955
5HYLVLRQ
3KRWR
&RQFUHWHGHODPLQDWLRQDWWKH
VWDLUSODWIRUP(/IWWR
WKHULJKWVLGHRIWKHGRRUDV
LQGLFDWHGE\\WKH\\HOORZ
DUURZ
3KRWR
6*+VXUYH\\HGWKHSRUWLRQRI
WKHZDOOEHWZHHQ(/IW
DQGIWIURPWKHPLGGOH
VWDLUODQGLQJ
6LWH9LVLW5HSRUW1R
RI
2FWREHU
'RFXPHQW,'1R6955
5HYLVLRQ
3KRWR
&RQFUHWHGHODPLQDWLRQDORQJ
FUDFNVRQWKHZDOOVKRZQLQ
EOXHKDWFKHGDUHD
3KRWR
&RQFUHWHGHODPLQDWLRQDORQJ
FUDFNVRQWKHZDOOVKRZQLQ
EOXHKDWFKHGDUHD
6LWH9LVLW5HSRUW1R
RI
2FWREHU
'RFXPHQW,'1R6955
5HYLVLRQ
)LJXUH3OXPEQHVVSURILOHRIWKHQRUWKIDFHRIWKH1RUWK:DOORI&(9$IURP(/IWWR(/IW
1RUWK:DOO)DFH 7RSRI0HFK3HQ6ODE
&(9$)ORRU6ODE
0HDVXUHPHQW +/-
DWHDVWVLGHRIWKH
VWDLUZHOO
0HDVXUHPHQW +/-
DWZHVWVLGHRIWKH
VWDLUZHOO