Informs NRC of Change in Scope of Integrated Schedule (is) Mod 1246,consisting of Elimination of Off Position on Switch to Total Elimination of Turbine Runback Selector Switch & Turbine Runback Function on Dropped Rod
ML17349A756
Person / Time
Site: Turkey Point 
Issue date: 03/16/1993
From: Plunkett T
FLORIDA POWER & LIGHT CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
L-93-40, NUDOCS 9303220197
Download: ML17349A756 (6)


Text

',. at--.eKX,Ka.m OOCvMZm o>Sr prox SVSxZM REGULA Y INFORMATION DISTRIBUTI YSTEM (RZDS)

ACCESSION NBR:9303220197 DOC.DATE: 93/03/16 NOTARIZED: NO DOCKET FACIE:50-251 Turkey Point Plant, Unit 4, Florida Power and Light C 05000251 AUTH.NAME AUTHOR AFFILIATION PLUNKETT,T.F.

Florida Power

& Light Co.

RECIP.NAME RECIPIENT AFFILIATION Document Control Branch (Document Control Desk)

R

SUBJECT:

Informs NRC of change in scope of integrated schedule (ZS) mod 1246,consisting of elimination of OFF position on switch to total elimination of turbine runback selector

switch, turbine runback function on dropped rod.

DISTRIBUTION CODE:

AOOID COPIES RECEIVED:LTR

(

ENCL 0 SIZE:

TITLE:,OR Submittal: General Distribution D

S NOTES:

RECIPIENT ID CODE/NAME PD2-2 LA RAGHAVAN,L COPIES LTTR ENCL RECIPIENT ID CODE/NAME PD2-2 PD COPIES LTTR ENCL A

D INTERNAL: NRR/DE/EELB NRR/DRCH/HICB NRR/DSSA/SPLB NUDOCS-ABSTRACT OGC/HDS3 EXTERNAL: NRC PDR NRR/DORS/OTSB'RR/DSSA/SCSB NRR/DSSA/SRXB

- C~&S REG FIL 01 NSIC D

NOTE TO ALL"RIDS" RECIPIENTS:

PLEASE HELP US TO REDUCE WASTE! CONTACT THE DOCUMEN'I'ONTROLDINK, ROOM Pl-37 (EXT. 504-2065) TO ELIMINATEYOUR NAME FROM DISTRII3UTION LISTS FOR DOCUMENTS YOU DON'T NEED!

TOTAL NUMBER OF COPIES REQUIRED:

LTTR 16 ENCL

~ 1

~

1

'Ik tr r, 1

~r.',t

P.O. Box 029100, Miami, FI33102-9100 NR 16 19q3 L-93-40 U. 'S. Nuclear Regulatory Commission Attn:

Document Control Desk Washington, D. C.

20555 Gentlemen:

Re:

Turkey Point Unit 4 Docket No. 50-251 Inte rated Schedule Modification No.1246 The purpose of this letter is to inform the Nuclear Regulatory Commission of a change in scope of Integrated Schedule (IS)

Modification No. 1246.

By letter L-91-259, dated September 24, 1991, Florida Power and Light Company (FPL) provided its final schedular update to the rema'ining open items in the Turkey Point Units 3 and 4 Integrated Schedule (IS).

IS MOD No. 1246, Replacement of the Turbine Runback Selector Switch for Unit 4, specified an expected completion date of June 3,

1993.

This modification was scheduled for implementation during the Unit 4 Cycle 14 refueling outage.

IS Modification No.

1245, Replacement of the Turbine Runback Selector Switch for Unit 3, was completed in May 1990.

IS Modifications 1245 and 1246 were designed to address a Human Factors item and involved the replacement of the four position Turbine Runback Selector Switch with a three position keylocked Turbine Runback Selector Switch.

The existing Unit 4 Turbine Runback Selector

Switch, which allows the operator to choose inputs desired for the turbine governor and load limit runback initiating logic, is a four position switch with the following positions:

NIS Selects Nuclear Instrumentation System inputs to the turbine runback initiating logic.

RP I Selects Rod Position Indication inputs to the turbine runback initiating logic.

NIS/RPI Selects both NIS and RPI inputs.

OFF Disables the NIS and RPI inputs.

IS Modification No.

1246 consisted of eliminating the "Off" position on the Turbine Runback Selector Switch.

FPL has evaluated the turbine runback function and determined that the turbine runback function on dropped rod is not required for reactor protection and affects plant availability.

9303220i97,,930316

',PDR ',ADDCK'0000025K P

'"'. 'DR an FpL Group company.

lIIII ],

1 II t

.1 vl I

O'8 F309'g

L-93-40 Page 2 of 2 Therefore, the scope of IS Modification No.

124'6 has been changed from elimination of the "Off" position on the existing switch to the total elimination of the Turbine Runback Selector Switch and the turbine runback function on dropped rod.

The revised scope is scheduled for implementation during the Unit 4 Cycle 14 refueling outage, meeting the original commitment date of IS Modification No.

124,6.

Elimination of the turbine runback feature on dropped rod for Unit 3 will be implemented during the Cycle 14 refueling outage currently scheduled to start in February 1994.

If there are any questions, please contact us.

Very truly yours, T. F. Plunkett Vice President Turkey Point Nuclear TFP/OIH Attachment cc:

Stewart D. Ebneter, Regional Administrator, Region II, USNRC Ross C. Butcher, Senior Resident Inspector,

USNRC, Turkey Point Nuclear Plant

If pt II Wl if