ACCELEtu;"D DOCUMENT DISTBUTION SYSTEM REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)

ACCESl ljlN NBR:9302100244 DOC.DATE: 93/01/28-NOTARIZED: NO DOCKET FACIL:50-250 Turkey Point Plant, Unit 3, Florida Power and Light C 05000250 50-251 Turkey Point Plant, Unit 4, Florida Power and Light -C 05000251 AUTH.NAME AUTHOR AFFILIATION PLUNKETT,T.F.

Florida Power

& Light Co.

RECZP.NAME 'ECIPIENT AFFILIATION Document Control Branch, (Document Control Desk)

D NOTES:

SUBJECT:

Provides documentation re FPL current capabilities for offsite communications in event of radiological emergency.

Offsite.communications capabilities at facility prior to Hurricane Andrew were comprised to diverse sys.

S DISTRIBUTION CODE:

ZE35D COPIES RECEZVED:LTR ENCL ~

SIZE:

0 i

7 RECIPIENT ID CODE/NAME PD2-2 PD INTERNAL: AEOD/DOA/IRB NRR/PMAS/ZLRB12 O~CA-G ZIL 02 COPIES LTTR ENCL 1'

1 1

RECIPIENT ID CODE/NAME RAGHAVAN,L NRR/DREP/PEPB9D NUDOCS-ABSTRACT OE DIR RGN2 FILE 01 COPIES LTTR ENCL D

,D EXTERNAL: NRC PDR NSIC D

A D

NOTE TO ALL"RIDS" RECIPIENTS:

PLEASE HELP US TO REDUCE WASTE! CONTACT THE DOCUMENT CONTROL DESK, ROOM Pl-37 (EXT. 504-2065) TO ELIMINATEYOUR NAME FROM DISTRIBUTION LISTS FOR DOCUMENTS YOU DON'T NEED!

0 TOTAL NUMBER OF COPIES REQUIRED:

LTTR 12 ENCL D

P.O. Box 029100, Miami, FL, 33102-9100 L-93-21 10 CFR 50 Appendix E

U.S. Nuclear Regulatory Commission Attention:

Document Control Desk.

Washington, D.C.

20555 Gentlemen:

Subject:

Turkey Point Units 3 and 4

Docket Nos.

50-250 and 50-251 Offsite Communications S stems and Ca abilities The purpose of this letter is to document Florida Power

& Light Company's (FPL) current capabilities for offsite communications in the event of a radiological emergency at Turkey Point Unit 3 or 4. Additionally, this letter pr'ovides an update of FPL's plans to further enhance the diversity and redundancy of offsite communications capabilities at Turkey Point Plant.

FPL's offsite communications capabilities at Turkey Point Plant prior to the advent of Hurricane Andrew at the site on August 24,

1992, were comprised of diverse systems.

The majority of the communications systems at Turkey Point before Hurricane Andrew were telephone or telephone line controlled-systems.

These systems either used Southern Bell's overhead copper wire or FPL's corporate fiber-optic system.

Additionally, there were two radio systems located on-site for offsite communications.

)he Local Government Radio.(LGR) system, designed to establish communication with the county Emergency Operations Center (EOC) and FPL's Emergency Offsite Facility (EOF), operated remotely from the control room.

The Very High Frequency (VHF) system was operated by the Turkey Point Security Department and was designed to allow communications with the local law enforcement authorities via the Metro Dade County police radio system.

Additionally, six cellular telephones were install'ed at Turkey Point Plant for emergency use.

These cellular telephones had antennas installed on top of the plant support buildings and were provided with backup power from the Security emergency diesel generator.

Post-Hurricane

Andrew, FPL developed enhancements to the offsite communications systems to provide additional means for notification to offsite locations during times of off-normal and emergency events.

Several enhancements to the telephone communications systems have been completed.

The Southern Bell overhead copper wire system was replaced with a buried fiber-optic cable which contains the dedicated circuits for state, federal and local notifications.

A microwave link between Turkey Point and the FPL General Office (the Turkey Point EOF) haa been

, (,

9302100244 930128 F

PDR ADOCK 05000250

".'1 0 '3

"'DR JO<V Yc,.

all Fpi Gloop colnpany

L-93-21 Page 2

installed to provide a backup to the FPL corporate fiber-optic system.

Enhancements to the radio systems designed to provide redundancy to the existing systems include the addition, of.two radio systems.

The VHF system and an Ultra High Frequency (UHF)

system, capable of short range communication within the company and to state and local governments, have been installed.

Replacement antennas for the radio systems have been purchased to allow recovery of the radio communication systems in the event the installed antennas are;damaged.

With the implementation of these enhancements and the restoration of the communications systems existing prior to Hurricane Andrew (i.e., the LGR system, the Security Department VHF system, the cellular telephones, and the fiber optic telephone/telephone line controlled systems),

the Turkey Point offsite communications capabilities exceed the requirements described in the Turkey Point Radiological Emergency Plan.-

FPL plans to further enhance capabilities at Turkey Point Plant by installing a High Frequency Automatic Link Establishment (HF-ALE) radio system.

The HF-ALE system will provide the capability for long range'communications with the NRC in Atlanta as well as state and local governments.

Installation of the.HF-ALE system is now scheduled to be completed by April 30, 1993.

In summary, FPL has restored and enhanced the communications systems existing at Turkey Point Plant prior to Hurricane Andrew and will further enhance communications capabilities by installing an HF-ALE radio system by April 30, 1993.

If you have any questions regarding this information, please contact us.

Very. truly yours, T. F. Plunkett Vice President Turkey Point Nuclear TFP/ejw cc:

Stewart D. Ebneter, Regional Administrator, Region II, USNRC-Ross C. Butcher, Senior Resident Inspector,

USNRC, Turkey

~ Point Plant