ML17345B260

From kanterella
Jump to navigation Jump to search
Groundwater Monitoring & Interceptor Ditch Operation Procedure
ML17345B260
Person / Time
Site: Turkey Point  NextEra Energy icon.png
Issue date: 07/31/1983
From:
FLORIDA POWER & LIGHT CO.
To:
Shared Package
ML17345B259 List:
References
PROC-830731, NUDOCS 8309190213
Download: ML17345B260 (46)


Text

FLORIDA POWER R LIGHT COMPANY TURKEY POINT, FLORIDA GROUND WATER MONITORING AND INTERCEPTOR DITCH OPERATION PROCEDURES REVISED JULY, 1983 t

83091902

.pg00025 XS>>

0'>g YOGI pQR ~

P

I' fi

/ l J

1.0 INTRODUCTION

This procedures manual applies to field work presently being conducted at Turkey Point for the Ground water Monitoring Program west of the Cooling Canal System and Interceptor Ditch Operation.

The procedures presented in this Revised Operations Manual reflect new agreements between Florida Power R

Light Company and South Florida Water Management District.

Reference is also made to the 1983 Turkey Point Agreement between the above mentioned parties, dated 2.0 KEY PARTICIPANTS'he following tabulation gives the key parties involved in this project for Florida Power 2 Light Company and their relative responsibilities:

Comvanv Resoonsibilitv Florida Power R Light Co.

Environmental Affairs Department P. O. Box 14000 700 Universe Boulevard Juno B'each, Florida 33408 Overall Program Direction and Contact Phone:

(305) 863-3624 Land Utilization Department P. O. Box 1565 Homestead, Florida 33030 Program Operations

.Data Processing Phone:

(305) 248-4740 Consultant Dames R Moore 301 W. Camino Gardens Blvd.

Plaza 6, Suite 201 Boca Raton, Florida 33432 Data Verification and Review Phone:

(305) 392-9070

0

3.0 GROUND WATER MONITORING PROGR'AM 3.1 Monitorin Locations The following wells'shall be monitored during this program:

L-3 and'L-5; G-21 and G-28. G-6, G-27 and G-35 shall not be monitored, but shall be capped and maintained in a ready condition.

These wells are located. as shown on Figures 1 and 2.

3;2 Monitorin Freauenc The wells specified in Section 3.1 shall be monitored 4 times a year during the months of October, January, April, and July.

3.3 Parameters The following data shall be collected at each well at the times specified in the preceding section:

ao Ground water Elevation (ft.)

Measured inside the casing from top of casing.

Elevation of top of casing is known.

b.

Surface Water Elevation (ft.) - Measured outside the casing from top of casing.

C.

d.

e.

Conductivity (umhos/cm)

Measured at one (1) foot intervals for the total well depth.

Temperature

( C) - Measured the same as conductivity.

Water Sample Collection Two water samples per well will be obtained for laboratory titration of chloride ion content.

Depth of sample collection is not constant, but approximately half the water samples should be obtained

-from within the first twenty feet of the water column in the well.

Generally, this portion of the water column contains the transition from water of low chlorinity to water of higher chlorinity.

These

samples,

.in combination with water samples from deeper depths, should provide chloride data which generally spans the entire spectrum of chloride ion encountered.

0 li

, ~

~ t

3.4 Monitorin Procedure The followingprocedure shall be followed in collection of field data:

ao b.

Co d.

e.

Calibrate the Conductivity-Temperature Meter.prior to each day of the monitoring using two standard saline solutions of 15,000 umhos/cm and 90,000 umhos/cm.

The instrument will be calibrated in accordance with the procedures establi'shed,in Section 3.7, Equipment Calibration.

M'easure both surface water elevation and ground-water surface elevation at each well by measuring from top of well casing.

Insert probe to a depth of.one (1) foot below water level in well; when meter needle stabilizes, read and record conductivity and temperature.

Repeat procedure in Step c. at intervals of one (1) foot to bottom of weQ.

Obtain water sample for chloride ion titration in accordance with recommendations in Section 3.3e.

Water samples are obtained with a Masterflex Pump or equivalent system.

- When taking a sample with the pump, a minimum of 1000 ml of water tram the desired sampling depth shall be pumped through the line to insure the sample is representative and not contaminated by water left in the line from a previous sampling station.

Sample water will be pumped directly into clean, dry bottles which will be tightly capped to prevent contamination of the sample.

f..

After every. well is monitored, calibration of the field monitoring unit will be checked with the 90,000 umhos/cm standard saline solution in accordance with procedures described in Section 3.7.

Note;

however, that the instrument shall not be adjusted at this time.

After each day of monitoring, the conductivity of the 90,000 umhos/cm standard solution and the calibration of.the field monitoring unit will be checked in accordance with procedures in Section.3.7.

II'

3.5 Data Verification In order to check the validity of the conductivity data, the relationship of conductivity versus chloride will be determined for each monitoring period by regression analysis.

This analysis requires the use of an independent variable (true variable) and a dependent variable.

Chloride content determined by laboratory titration will be used as the true variable and the conductivity variable will be adjusted to the line of best fit by the method of least squares.

In order to reduce the possibility of error, the raw titration data and raw conductivity data will be immediately plotted on the historical conductivity-chloride relationship as shown on Figure 3.

The majority (75 percent) of the plotted raw data points should fall within the variance'hown for the historical relationships.

The remaining 25 percent of the points should be reasonably close to the historical relationship.

For conductivities less than 10,'000 umhos/cm, the historical relationships are less definitive.

For those conductivities, the ratio of the raw titration value (parts per thousand) to the corresponding raw conductivity value (umhos/cm) should be reasonably close to the following historical ratios:

Conductivity umhos/cm Ratio Less than 2000 2000-6000 6000-10000 0.100 0'.237 0.314 In addition to these two check methods, the raw points will.be inspected for direct proportionality.

In other

words, the chloride content increases with increasing conductivity.

Any two relative data points which reverse this relationship will be checked for probable error.

If, at any.time, data are suspected to be in error, the following steps shall be taken:

0 I'

I

ao Retitrate the suspect water sample to d'etermine chloride content.

Replot the titration data versus the corresponding conductivity data and reinspect for direct proportionality.

b.

If data are still suspected to be in error after the retitration, then the well(s) in which the suspect data occur shall'e remonitored in accordance with the procedures set forth in Section 3.4.

The conductivity, temperature, water level and titration data will be transmitted to FPL's consultant.

The consultant willrecheck the. titration data for proportionality and variance from the historical relationship in. accordance with methods presented in previous paragraphs.

The water

level, temperature and conductivity data will be compared with historical data from periods of similar seasonal conditions.

(Water level fluctuations, precipitation,and air temperature are among the factors to be considered when choosing times of similar seasonal conditions,)

If any water level, temperature and/or conductivity data exhibit abnormal changes, the wells in which. these changes occur will be remonitored in accordance with.procedures set forth'in Section 3.4.

Suspect wells

,will be remonitored and checked until the consultant is satisfied that the data represent actual ground-water conditions.

At this time, the data will be processed in accordance with Section 3.6.

The initiation of the monitoring each quarter will allow sufficient time for checking suspect field data.

Therefore, the monitoring,.should be initiated at least five working days prior to the 1st of each quarterly month.

The raw field data shall be entered on standard forms (Figure 4).

Distribution of the data shall be in accordance with the following.

h.

Original - To FPL Environmental Affairs Department b.

One Copy - Retained on file at Land Utilization Department at Turkey Point

4i I'

c.

One Copy - Forwarded to FPL's consultant.

3.7 Equi ment Calibration The following calibration procedures apply to the Conductivity-Temperature Meter.

Conductivity Calibration Prior to each day of monitoring, the instrument shall be calibrated in accordance with the following procedures and the appropriate information entered on the Calibration Log (Figure 5) in the space designated "Before Monitoring"'.

The calibration of the conductivity meter is accomplished by the use of two potassium chloride (KCl) solutions prepared in accordance with ASTM D1125-64, Standard Methods of Test for Electrical Conductivity of Water.

The procedure is as follows:

a.

Prepare one solution of approximately 90,000 umhos/cm conductivity.

1.

Dissolve approximately 60.0 g of KC1 to 1 liter of Category III Water.

2.

Determine the conductivity of the KCl solution using a conductivity bridge and certified cell to determine the "true" conductivity of the solution.

b.

3.

Calibrate the upper end of the field units conductivity range using the KC1 conductivity standard as prepared above.

Prepare one solution of approximately 15,000 umhos/cm conduc'tivity.

2.

Dissolve approximately-7.50 g of KCl to 1 liter of Category III Water.

Determine the conductivity of the KCI solution using a conductivity bridge and certified cell to determine the "true" conductivity of the solution.

3.

Read conductivity of solution using the field unit.

If the reading obtained with the field unit differs from the reading for the low conductivity solution more than 1,000 umhos/cm, the conductivity of the 90,000

II 0

l

umhos/cm solution will be rechecked with the conductivity bridge and the procedure repeated.

Calibrating, the field. unit with a solution of high conductivity reduces the percent error, introduced.when calibrating the instrument at the, lower end of the conductivity range.

The 15,000 umhos/cm solution serves as a check on the accuracy of calibration at 90,000 umhos/cm.

In order to insure that the instrument maintains calibration throughout each day of monitoring, the 90,000 umhos/cm standard saline solution used in the initial calibration will be carried to the field and.the solution will be read after monitoring every well. The reading given by the 'nstrument will be recorded in the Calibration Log in spaces designated "During Monitoring". However, the instrument SHALL NOT be adjusted in the field to the reading given by the standard'solution.

Upon returning to the laboratory after each day of monitoring the conductivity of the 90,000 umhos/cm solution will be checked with the conductivity bridge to assure that the conductivity of the standard solution has not changed throughout the day.

The standard solution shall then be read with the field unit., This calibration sequence willbe entered on the Calibration Log in the space labeled'"After Monitoring".

The Calibration. Log can be used to develop "drift curves" in order to correct "instrument drift".

If the "After Monitoring" calibration sequence yields a reading deviation exceeding five (5) percent of the total reading, the data shall be corrected using the drift curve.

In summary, the maximum allowable reading'eviation for a 90,000 umhos/cm solution would be -4,500 umhos/cm.

+

Tem erature Calibration Calibrate the field unit using the following procedure or equivalent:

a.

Turn the instrument to "temperature zero" and adjust to read -5 degrees C.

b.

Turn the instrument to "temperature calibrate"'nd adjust to read 45 degrees C.

c.

Prepare two H 0 solutions at temperatures of approximately 20 degrees C

do e.

and 30 degrees C respectively.

Compare the temperatureS measured with the field unit to. those obtained with a highly accurate laboratory thermometer.

If the field unit and the. thermometer agree within 0.5 degrees C, the temperature meter is considered calibrated.

If the two do not agree, use the following procedure:

3'.

Adjust the field unit to read the results given by the thermometer in the 20 degrees C solution..

Read the 30 degrees C solution with the field unit and thermometer.

If the readings differ, adjust the field unit to read the same as<he thermometer.

Again read the 20 degrees C solution with both instruments.

If there is a difference, adjust the field unit to equal the thermometer reading.

4.

Repeat this alternating procedure until the field unit will read both solutions within 0.5 degrees C.

4.0 INTERCEPTOR DITCH'OPERATION 4.1 Introduction The'urpose of the Interceptor Ditch is to restrict inland movement of cooling canal water by maintaining a seaward ground water gradient during times when a natural seaward gradient does, not exist.

During the wet season and the early part of the dry

season, a natural seaward gradient usually does exist.

During the rest of the year, however, it is necessary to artificially generate a seaward gradient east of Levee 31

'Borrow Canal by pumping water out of the Interceptor Ditch.

The procedure

~ for monitoring'the ground'ater gradient and operation of the Interceptor Ditch is presented

'8

4>

II

in the following sections.

4.2 Monitorin Locations Surface water elevations shall be monitored at staff gages located in the West Feeder Canal of the Canal System, Levee 31 Borrow Canal and the Interceptor Ditch at.

five locations relative to Lines A, B, C,.D and E, as shown on the inset, Figure 2.

When pumping of the Interceptor Ditch commences, additional data shall be obtained at each of the two ID pump stations.

Locations of the pump stations are also shown on Figure 2.

4.3 Monitorin Fre uenc Water elevation data shall be collected at the fifteen locations twice a month during non-pumping periods.

These elevations will be measured on or about the 1st of each month and again near the middle of the month.

Non-pumping periods reflect the wet season high water levels i.e., June through November.

During the period December through May, water elevation data will be collected once a

week except during periods when pumping is necessary to create a seaward gradient.

When pumping is required, water surface elevation data will be collected at least twice weekly.

Adequate surveillance shall be set up to assure proper Interceptor Ditch operation.

Data on pump run time and segments being pumped will be recorded in the Interceptor Ditch Pump Operation Log (Figure 9).

As long as a natural seaward ground-water gradient

exists, pumping of the Interceptor Ditch is not required.

The following crjteria define when a natural seaward gradient exists and when the Interceptor Ditch must be pumped to create an artificial gradient east of Levee 31 Borrow Canal.

Seaward Gradient A natural seaward gradient exists when the Levee 31 water surface elevation (ft.,MSL) minus the West Feeder Canal water surface elevation

0

(ft.,MSL) is greater than 0.20 ft.

If this criterion is not met, a natural seaward gradient still exists if the Levee 31 water surface elevation (ft.,MSL) minus the Interceptqt'itch water surface elevation (ft.,MSL) is greater than 0.30 ft.

Landward Gradient - If a natural. seaward gradient does not exist, pumping of the Interceptor Ditch must be initiated to artificially create a seaward gradient.

Pumping shall be adjusted so that the water surface elevation (ft.,MSL) in the Interceptor Ditch is maintained on the order of 0.30 feet lower than the water surface elevation (ft.,MSL) in Levee 31.

Pumping can be terminated when the criteria for a natural seaward gradient is met.

The flow chart on Figure 6 depicts the requirements for pump operation.

%his chart should be referred to each time water elevation data are obtained in order to,more easily determine when pumping is or is not required.

As can be seen on Figure 2 the pump stations divide the Interceptor Ditch into three segments.

Each segment is evaluated separately with respect to the operating criteria.

One

segment, therefore, might require pumping while another might not.

Pumping shall be initiated when any of the lines of staff gages governing that segment fails to meet the specified criteria for a seaward gradient.

Adjustable intake gates (stop-logs) in each pump intake basin allow for various pump combinations to drawdown specific Interceptor Ditch segments.

"i"K Data shall be compiled on the forms provided (Figures 7-9). Field data will be kept for 24 months.

Field data shall be distributed as follows:

a.

Original-FPL Environmental Affairs Department.

b.

One Copy'- Retain on file at FPL Land Utilization Department. at Turkey Point.

10

0

c.

One Copy-Forwarded to FPL's Consultant.

An Annual Summary Report covering the preceding year's monitoring and operations data will be compiled and subsequently submitted to the South Florida Water Management District by the end of August of each. year.

These reports, to be retained for the life of the Interceptor Ditch Program, will consist of the following elements:

ao a

description of any operational or structural changes made to the b.

C.

d.

e.

Interceptor Ditch System, a description of climatological conditions, including any unusual events, a description of the results of the previous year's monitoring program, updated time-history plots for all wells and parameters monitored and, time-history plots for each Interceptor Ditch pumping station.

Distribution shall be in accordance with the following.

One Copy - Forward to South Florida Water Management District 4.8 Equipment Maintenance Occasional cleaning of the staff gages is required when algae and other marine growths inhibit reading of the staff gages.

Care must be taken when cleaning to prevent damage to.or movement of the staff gages.

11

I I

1.

G oundwater Monitor'ing Program well'ocations.

2; Interceptor Ditch, Levee-31 Well and Pump Locations.

3.

Historical conductivity-chloride relationship.

4.

Raw Data Forms.

5.

Calibration Log.

6.

Interceptor Ditch Program Operational Flow Diagram.

7.

Interceptor Ditch, Levee-31, Canal 32'Water Level,Data.

8.

Interceptor Ditch, Levee-31, Canal 32 Water Level Data.

9.

Interceptor Ditch Pump Operation Log.

4l II

PA?A DRIVE

~ G-35 0

0

'0 0

G-21

'-28.

G-27

~

06 C-107 S 20 G-6

~

l//

'/

/

S20A

//

/f//

/

COOLZNG

/

CJQVQ SYSTEH

'/

L-S; '/

PO4~R PLA'iT I

I I

BZS~Yh~ BA>

I I

I I

I.

I c7 I

I I

I I

, I I

I I

SEA DADE CANAL CARD SOU&)

FEET 1000 0 1000 2000 Figure 1.

Groundwater Monitoring Program 'Yell Locati.ons

~I a'

C ~,

~

'Feet 2PPO '1000 0 1000 S2OA

'-3 North Pumo Station Pumps 1&2 o

4 g

e P'

L-5 oa outh Pump Station Pumps 3&4 Palm Drive

'S 20 Line A I

Line Line C II Line D

I t

ine E

I L e o

~ a

'e

~aae ana

, ~

I iscayne Bay Card Sound Figure 2.

Interceptor Ditch~ Levee-31 4'ell and Pump Locations

4l II I

WMWWWMWWMMEWENMEEEWMWSWWWRMMMWWMMWMMMEMMWWMMMWWWWMWWWEMMMMM WWWWWMSWWOWWWMWWWWWWWWWWWWMMMWWMMWMMWWMMWWWMMWWWWNSWWWMMMSM WRWSOMWWWWREWMRWWWWWWOWWWWWMMWWMWWMMWWMSWWWMMWEWEMEEMWWMMMM EMMESM855MMSEMWWEQEWEEWMEEMMMWWMMWMWWMMMWEMSWWWWMRWMWWMWWW alsagagaaalalsllakalkaaakaklamaaaa all/a aasskasssarsaaasss

~saaaaaalaaaaa sk aaaaaa a Ilaalsa al sasssgsIIksssaaass Pallasaal) 'gll/I l'Pak/

aassIIsaf II aaasaaasLaaidakssssssasssasss salmalr'sal Ila lr aa

~ Illlkllk-Isllallllllllllllll WWWWMEWW WWWWW WEW WW EW MW kglÃ5$%

N 5MWMMEWMEEEWMRMMMME NWWWMEMW MNMWWW W RWWSWM MP 540645WM MMWMWWWMWWWEMMMMEWM WWEWEEWM WOSMWEE EW OWMERM 1<1HRWMMMMM MMMMMWWMWWWWMMMMMMM

II Ol I'

I

RIM

~

~

g

~

III

'I l~

I I

y

~

l R

I

~55 Illl

~

Ilail%~

IHIWI

~ WIMI IIW%5l IIIIII'II~SI IIWMI~~

~

Wl IIEKIWSW&RW IRW

~qua ~naaraaaaaa mama

~

~IMIISISIRIIIIMl IIIlWIIRIIIISII

~MRIIII&MIIIIIIItltl Ill

%El WIIlliEIIIIMKII55%iSIRlil%WRll ll fllkllllllllSR1RRillSRltlllSliSIll SIIMWIMMW MSR IlRRll&5%&

CALXBRATION LOG I

I Instrument:

Date/Time:

Technician:

Checked By,:

1.

Before Monitoring (Laboratory)

Conductivity Temperature Calibration Standard Meter Reading Meter Adjusted to Read 2.

During Monitoring A.

B.

C.

D.

3.

After Mo'nitoring (Laboratory)

Calibration Standard Meter Reading Deviation Correction Applied (Explain):

,L

iNTERCEPTOR DiTCH PROGRAM OPERATiONAL FLOH DT.AGRAM Bea L-an ana Hater Level Elevations L-31 Elev.

Magnus C-32 Elev.'reater Than 0.'20 'feet ev.

anus C-32 Elev. Less Than 0.20 feet Pumping o

. ZD Not Required or Terminated.

ompare an Elevations L-E ev.

Hxnus

.ID Elev. Less Than 0.30 feet ev.

~ nus ID Elev. Greater Than 0.30 feet Pumping of D

Required to Increase Differential to 0.30 feet umping of Not Required or Terminated Figure 6.

0

~l

t E kl Sl E55515E555155 5

EREEIEERkRI R R RRRI Rrar R

REE ERSR E

RRRR RRraR RRRRIRRRar R

RRREIE R R R ESEEIE 8 E RRRRIR Rar RRRRIR rarl R RRRRIR Rarl IERREIE SREI

!ERSEIEE5551 IRRRRIRRrarl IRRRRIRRRart RR IESEEIEESkRI EEER 8 Sl RE I

kklk ak I

a Ia a ak krk a atr a a a kl raa a a ata aaa a R alkyl Rkklaak klan kkklkRkkklk5 al R art R

I a aa rk I kkk

j kl

55$55I555$

5ESE) EE EE 5aaa E

El EEL I )

EEEEI E

E EIE E 1EE EI))

58EE)I)$

srrrrrrr rara

)Earl 1aaar EE E 5588k ES)

El mrrrrlrrrr 5REEEIEE

%)E))l)E I

E )

R))

rr rr L L

R )

~ l55S RIOR R

) Sl 8

)

I il L IL LL

) )

))LI

)) 8)

WIL ILI)

W&&

85&W&WWWWWW&&

~5&WWWW&WWWWW 5%WWWW&MW&&&W NRW&WWW&WWW&W

~RW&WWWWWW&WW

~RW&&W&&W&&&&

~5&&WW&WWWW&W 55W&&&&&WWWWW RRM&&&WW&WW&W g5&WWW&WW&&WW gRW&WWWW&W&W&

~a&&W&W&&&W&&

RS&&W&W&&&WW&

~SWWWW&WW&WWW RS

&WWW&W&&&&

&WWWW&WWW&&

RRWWWWWW&WWWW RSWWWWW&WWW&&

RRW&& &&&&&&&

W&WWWWW 55&W&WWWWWWWW R5&WWWWWWW RSW&&&&&&&WW RSW&W&&WWW&&W WWW&WW&WW&WW

%%&&WWW&WWWW&

WWWWW

4>

a

~

a,-

ATTACHMENTC No Si nificant Hazards Determination The proposed ground water monitoring deletion would not change any current limitations related to the operation of the plants.

Since no operational limitations are being changed, this proposed amendment does not involve a significant increase in the probability or consequences of an accident;previously evaluated, does not create the possibility of a new or different accident from any occident previously evaluated and does not involve a significant, reduction in a margin of safety.

Therefore, it is determined that this amendment does not involve a significant hazards consideration.

4l