e ENCLOSURE 2
NOTICE OF DEVIATION Florida Power and Light Company Turkey Point Units 3 and 4
Docket Nos.
50-250, 50-251 License Nos.
DPR-31, DPR-41 The following deviation was identified during a Nuclear Regulatory Commission (NRC) inspection conducted on October 29, through November 23, 1988.
The Final Safety Analysis Report
( FSAR),
Appendix 9.6A, paragraph
- 3. 1.2(c),
states in part that control valves shall be capable of isolating portions of the fire main for maintenance or repair without shutting off the entire system.
Paragraph 2.4, Conformance to Branch Technical Position 9.5-1 Guidelines, Item A.4, states that the piping and valving is arranged such that a single break will not prevent the water supply from reaching a possible fire, and Item C.5, states that testing is conducted in accordance with procedures and verified by inspection and audit to demonstrate conformance to design and system readiness requirements.
Test results are evaluated and acted upon.
Contrary to the
- above, as of October 29,
- 1988, no test program had been established to demonstrate conformance to design and system readiness requirements as demonstrated by the inability to isolate and repair a hole in the fire main piping.
Please provide to the U.
S.
Nuclear Regulatory Commission, ATTN:
Document Control Desk, Washington, DC 20555, with a copy to the Regional Administrator, Region II, in writing, within 30 days of the date of this notice, the reasons for the deviation, the corrective steps which have been taken and the results
- achieved, the corrective steps which will be taken to avoid further deviations, and the date when your corrective action will be completed.
Where good cause is shown, consideration will be given to extending the response time.
FOR THE NUCLEAR REGULATORY COMMISSION Bruce A. Wilson, hief Reactor Projects Branch 2