SUBJECT:
Special rept: on 880106,breached fire barriers
& other fire protection sys impairments discovered.
DISTRIBUTION CODE:
IE22D COPIES RECEIVED:LTR <<i ENCL ASSIZE:
TITLE: 50.73 Licensee Event Report (LER), Incident Rpt, etc.
NOTES:
RECIPIENT ID CODE/NAME PD2-2 LA McDONALD,D INTERNAL: ACRS MICHELSON AEOD/DOA AEOD/DSP/ROAB ARM/DCTS/DAB NRR/DEST/ADS NRR/DEST/ELB NRR/DEST/MEB NRR/DEST/PSB NRR/DEST/SGB NRR/DLPQ/QAB NRR/DREP/RAB RR DRI SIB RES TELFORD,J RGN2 FILE 01 EXTERNAL: EG&G GROH,M H ST LOBBY WARD NRC PDR NSIC MAYS,G COPIES LTTR ENCL 1
1 1
1 1
1 1
1 2
2 1
1 1
0 1
1 1
1 1
1 1
1 1
1.
1 1'
1 1
1 1
1 1
1 5
5 1
1 1
1 1
1 RECIPIENT ID CODE/NAME PD2-2 PD ACRS MOELLER AEOD/DSP/NAS AEOD/DSP/TPAB DEDRO NRR/DEST/CEB NRR/DEST/ICSB NRR/DEST/MTB NRR/DEST/RSB NRR/DLPQ/HFB NRR/DOEA/EAB NRR/DREP/RPB NRR/PMAS/ILRB RES DEPY GI RES/DE/EIB, FORD BLDG HOY,A LPDR NSIC HARRIS,J COPIES LTTR ENCL 1
1 2
2 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 2
2 1
1 1
1 1
1 1
1
,1 1
1 R
I S
TOTAL NUMBER OF COPIES REQUIRED:
LTTR 46 ENCL 45
P. O.
8 14000, JUNO BEACH, FL 33408 0420 JANUAlK 6
1988 L-88-3 U. S. Nuclear Regulatory Commission Attn:
Document Control Desk Washington, D.
C.
20555 Gentlemen:
Re:
Turkey Point Units 3 and 4
Docket Nos.
50-250 and 50-251 Special Report Breached Fire Barriers and Other Fire Protection S stem Im airments In accordance with Technical Specification 6.9.3 the attached Special Report is provided for your information.
Should there be any questions on this information, please contact us.
Very truly yours,
~ Executive Vice President COW/SDF/gp Attachment cc:
Dr. J. Nelson Grace, Regional Administrator, Region II, USNRC Senior Resident Inspector, USNRC, Turkey Point Plant SDF/009.BFB 880ii20i47 880106 PDR ADOCK 05000250 8
SPECIAL REPORT JANUARY 6, 1988 FIRE PROTECTION SYSTEM IMPAIRMENTS REQUIRING NRC NOTIFICATION
~Pur ose:
Technical Specification (TS) 3.14.5.b requires the submission of a report to the NRC if a non-functional fire barrier penetration is not returned to functional status within 7 days.
TS 3.14 also states that certain other conditions require NRC notification.
In accordance with the above requirements, this special report is being generated in order to notify the NRC.
This report is being updated on a
30 day basis.
Event:
Turkey Point has been and is continuing to implement plant modifications.
Fire Protection System (FPS) impairments are, at times, incurred during the performance of these"modifications.
Occasionally, certain FPS features fail due to random component failure.
Cause and Corrective Actions:
The primary cause of the impairments is the number of modifications being performed.
Many of these modifications require the impairment of certain FPS features for their completion.
The secondary cause for the impairments is FPS equipment malfunction.
Because Turkey Point incurs a variable number of impairments, the plant is reporting the impairments in a monthly report, rather than on a case-by-case basis.
The impairments reported this month may be either open or closed at the present time, however they were open in excess of the Technical Specification permitted time limit.
This report includes impairments not reported previously which were:
1) opened prior to January and 2) stayed open for longer than the time permitted by the Technical Specifications, and 3) are either still open or were closed prior to January.
The closed impairments have been reported at the time opened, unless noted otherwise.
The plant continues to implement the compensatory measures as applicable.
FIRE PROTECTION SYSTEM IMPAIRMENTS OPENED SINCE NOVEMBER REPORT WHICH HAVE BEEN OPEN FOR LONGER THAN TECH SPEC LIMITS Imp f/
1254 1262 1267 1257 Description Thermo lagging Detection Fire Door 106-1 Fire barrier Open 12/07/87 12/17/87 12/22/87 12/08/87 Closed 12/31/87 FIRE PROTECTION SYSTEM IMPAIRMENTS CLOSED SINCE NOVEMBER REPORT BUT WERE OPEN FOR LONGER THAN TECH SPEC LIMITS Imp if 1232 1293 87-0318 87"0320 87-0325 87-0330 Description Fire detection Conduit Pen.
Seal 106F-E279 Raceway protection R.P. A384-30-0181-3271 Raceway protection Open 11/05/87 11/17/87 07/17/87 07/23/87 07/30/87 09/15/87 Closed 12/21/87 12/31/87 12/17/87 12/10/87 12/11/87 12/10/87