ML17338A832

From kanterella
Jump to navigation Jump to search
Forwards LER 79-008/03L-0
Date released: 07/31/2018 Download: ML17338A832


LER 79-008/03L-0 on 790526:emergency Diesel Generator Stopped Due to Lockout Relay Actuation.Caused by Improper Settings on Undervoltage Time Delay Relays.Relays Reset & Tested.Test Procedures Will Be Revised
ML17338A833
Person / Time
Site: Turkey Point NextEra Energy icon.png
Issue date: 06/25/1979
From: Schoppman M
FLORIDA POWER & LIGHT CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML17338A833 (2)
Forwards LER 79-008/03L-0
ML17338A831
Person / Time
Site: Turkey Point NextEra Energy icon.png
Issue date: 06/25/1979
From: Schmidt A
FLORIDA POWER & LIGHT CO.
To: OREILLY J P
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
Download: ML17338A831 (2)