ML17334A448

From kanterella
Jump to navigation Jump to search
Forwards Addl Info Re Range of Steam Dump to Atmosphere Monitor,Per NUREG-0737,Item II.F.1,in Response to Varga 811120 Request
ML17334A448
Person / Time
Site: Cook  
Issue date: 09/22/1982
From: Hering R
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To: Harold Denton
Office of Nuclear Reactor Regulation
Shared Package
ML17334A447 List:
References
RTR-NUREG-0737, RTR-NUREG-737, TASK-2.F.1, TASK-TM AEP:NRC:0586A, AEP:NRC:586A, NUDOCS 8211120481
Download: ML17334A448 (2)


Text

INDIANA & MICHIGAN ELECTRIC COMPANY P. O. BOX 18-BOWLING GR E EN STATION NEW YORK, N. Y. 10004 September 22, 1982 AEP:NRC:0586A Donald C.

Cook Nuclear Plant Unit Nos.

1 and 2

Docket Nos. 50-315 and 50-316 License Nos.

DPR-58 and DPR-74 NOBLE GAS RADIATION MONITORS-STEAM DUMP TO ATMOSPHERE MONITORS Mr. Harold R. Denton, Director Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Washington; D. C.

20555

Dear Mr. Denton:

This letter and Attachment 1 transmits our response to Mr. Varga's letter of November 20,~ 1981 requesting information on the Radiation Monitoring System at the Donald C. Cook Nuclear Plant.

Attachment 1 contains the additional information requested concerning the range of the steam dump to atmosphere monitor as required by NUREG 0737, Item II.F.1 Attachment 1.

This document has been prepared following Corporate procedures which incorporate a reasonable set of controls to ensure its accuracy and completeness prior to signature by the undersigned.

Very truly yours,

/sag Attachment R. F. Hering Vice President cc:

John E. Dolan R. S. Hunter M. P. Alexich R.

W. Jurgensen R.

C. Callen G. Charnoff W. G. Smith, Jr.

Bridgman Joe Williams, Jr.

NRC Resident Inspector at Cook Plant Bridgman 82iii20481 82ii05 poR Aooov oooooszo i j PDR

ATTACHMENT 1 TO AEP: NRC: 0586A The Model SA-ll detector, used to monitor steam releases through the Steam Generator's Power Operated Relief Valve (PORV),

has a vendor supplied value for the maximum range equivalent to approximately 110 uC1/cc noble gas which is based on a particular vendor geometry calibration that is not representative of the proposed plant installation, As Mr. Varga's letter points out, NUREG-0737, Item II,F.l requires an upper range of 1000 uCi/cc.

We have completed a

mock-up and field geometry calibration for the SA-11 detector.

Based upon linearity and mock up measurements, the Xe-133 range for this monitor meets the requirements of NUREG-0737.

This monitor can accurately detect concentrations in the Steam Generator PORV line o 2 x 105 uCi/cc.

The data and calculations to )ustify the use of the Eberline SA-ll detector system at the Donald C.

Cook Plant have been documented in a report prepared by Research

Concepts, Inc., oui consultant for the cal'bration

'f this monitor.

A typographical omission on Table 1 entitled "Equipment Description" which was attached to our letter AEP:NRC:00586 dated July 10,

1981, has resulted in a question in Mr. Varga's letter as to whether atmospheric steam dump valve discharges are being monitored.

This table should indicate that the monitoring of the effluent is on the Steam Generator Safety/Relief Valves which means Safety Valves and Atmospheric Steam Dump Valves on Main Steam Leads 81, 2, 3, and 4.

The detector will monitor the effluents in the PORV line to the atmosphere.