CATEGORY 1 REGULAT INFORMATION DISTR'IBUTIQN TEM (RIDS)
ACCBSSION NBR:9709030354 DOC.DATE: 97/08/28 NOTARIZED: NO DOCKET ¹ FACIL:50-315 Donald C.
Cook Nuclear Power Plant, Unit 1, Indiana M
05000315 50-316 Donald C.
Cook Nuclear Power Plant, Unit 2, Indiana M
05000316 AUTH.NAME AUTHOR AFFILIATION FITZPATRICK,E.E American Electric Power Co., Inc.
RECIP.NAME RECIPIENT AFFILIATION Document Control Branch (Document Control Desk)
SUBJECT:
Informs of discovery of error in calculation performed as part, of 1996 DC Cook, Unit 2,uprating program. Revised RHR is being performed 6
NRC will be notified if unfavorable results occur.
DISTRIBUTION CODE:
A001D COPIES RECEIVED:LTR ENCL SIZE:
TITLE: OR Submittal: General Distribution A
T NOTES:
RECIPIENT ID CODE/NAME PD3-3 LA HICKMANiJ INTERNA.
E GEN'TER 01 NRR/DE/EMCB NRR/DSSA/SPLB NUDOCS-ABSTRACT EXTERNAL: NOAC COPIES LTTR ENCL RECIPIENT ID CODE/NAME PD3-3 PD NRR/DE/ECGB/A NRR/DRCH/HICB NRR/DSSA/SRXB OGC/HDS2 NRC PDR COPIES LTTR ENCL 0
D NOTE TO ALL "RZDS" RECIPIENTS:
PLEASE HELP US TO REDUCE WASTE. TO HAVE YOUR NAME OR ORGANIZATION REMOVED FROM DISTRIBUTION LISTS OR REDUCE THE NUMBER OF COPIES RECEIVED BY YOU OR YOUR ORGANIZATION, CONTACT THE DOCUMENT CONTROL DESK (DCD)
ON EXTENSION 415-2083 TOTAL NUMBER OF COPIES REQUIRED:
LTTR 13 ENCL
p r
~%<<
I, 4
Ew'4 0
indiana Michigan Power Company 500. Circle Drive Buchanan, Ml 491071395
à INQMMSl MICNl6AM PQWM August 28, 1997 Docket Nos.:
50-315 50-316 AEP: NRC: 1223L U.
S. Nuclear Regulatory Commission ATTN:
Document Control Desk Washington, D.
C.
20555 Gentlemen:
Donald C.
Cook Nuclear Plant Units 1 and 2
UNIT 2 UPRATE SUBMITTAL NOTIFICATION A calculation was performed as part, of the 1996 unit 2 uprating program to demonstrate Cook Nuclear Plant is capable of cooling to 200' in thirty-six hours with one train of residual heat removal (RHR) and component cooling water (CCW).
An error in the RHR and CCW flowrates was discovered in this calculation during the course of answering questions from the NRC architect engineer design inspection team.
At our request, Westinghouse performed a review of inputs to the calculation, and has determined that our TEMA-E CCW heat exchangers were inappropriately modeled as counter-flow in both the RHR cooldown and containment analyses.
A revised RHR cooldown analysis is being performed.
In addition, as part of our corrective action, an evaluation is being performed to demonstrate that the acceptance criteria for the containment integrity analysis performed as part of the uprating program remain valid.
The NRC staff will be notified in a timely fashion should the revised cooldown analysis or containment evaluation yield unfavorable results.
Sincerely, E.
E. Fitzpatrick Vice President vlb A. A. Blind A. B. Beach MDEQ -
DW & RPD NRC Resident Inspector J.
R. Padgett'.;
1 rv L>4
~
IIIIIIILIIilllIIIlllILliiIlIIIIIIIlIIIII 9'709030354 970828 PDR ADQCK 050003l5 P