DONALDC. COOK NUCLEARPLANTUNIT 1 CYCLE 16

.CORK OPERATING LIMITSREPORT (COLR)

Revision 0 April 1997 9704i50249 970409 PDR ADOCK 050003ih P

PDR

COLR for DONALDC. COOK NUCLEARPLANTUNIT I CYCLE 16 - APRIL 1997 1.0 CORE OPERATING LIMITSREPORT This Core Operating Limits Report for the Donald C. Cook Nt.clear Plant Unit I Cycle 16 redesign has been prepared in accordance with the requirements ofTechnical Specification 6.9.1.11.

The Technical Specifications affected by this report are listed below:

3/4.1.1.4 3/4.1.3.1 3/4.1.3.3 3/4.1.3.4 3/4.1.3.5 3/4.2.1 3/4.2.2 3/4.2.3 3/4.2.6 Moderator Temperature Coefficient Movable Control Assemblies Group Height Rod Drop Time Shutdown Rod Insertion Limits Control Rod,Insertion Limits Axial Flux Difference Heat Flux Ilot Channel Factor Nuclear Enthalpy Hot Channel Factor Allowable Power Level Page I of 11 Revision 0

COLR for DONALDC. COOK NUCLEARPLANTUNIT 1 CYCLE 16-APRIL 1997 The cycle-specific parameter limits for the specifications listed in Section 1.0 are presented in the following subsections.

These limits have been developed using the NRC-approved methodologies specified in Technical Specification 6.9.1.11.

2.1 Moderator Tern erature Coefficient (Specification 3/4.1.1.4) 2.1.1 The Moderator Temperature Coefficient (MTC) limits are:

The BOL/ARO MTC shall be less positive than the value given in Figure l.

The EOL/ARO/RTP-MTC shall be less negative than -4.54F:4 hk/k/'F.

Tile EOL/ARO/RTP MTC liinit is based on a Tavg prograin witli IIFP Tavg of 553 F (Note 1) where:

ARO stands for AllRods Out BOL stands for Beginning ofCycle Life EOL stands for End ofCycle Life RTP stands for Rated Thermal Power HFP stands for Hot Full Thermal Power 2.1.2 The MTC Surveillance limitis:

The 300 ppm/ARO/RTP-MTC should be less negative than or equal to - 3.84E-4 hk/k/'F at a vessel average temperature of553'F. (Note 1)

Note I -Unit 1 Cycle 16 willbe run with a Tavg of556'F Revision I oftile COLR willrevise tile EOL/ARO/RTP-MTC and the 300 ppm/ARO/RTP-MTC limits to reflect the 556'F Tavg by May 15, 1997. This new value was not available at the time of issuance of Revision 0 because ofthe late decision to change Tavg due to the as found steam generator condition.

Page 2 of 11 Revision 0

C COLR for DONALDC. COOK NUCLEARPLANTUNIT I CYCLE 16 - APRIL 1997 2.2 Rod Dro Time Dro Hei ht (Specification 3/4.1.3.3) 2.2.1 Allrods shall be dropped from 225 steps.

2.3 Shutdown Rod Insertion Limit(Specification 3/4.1.3.4) 2.3.1 The shutdown rods shall be withdrawn to 225 steps.

2.4 Control Rod Insertion Limits (Specifications 3/4.1.3.5 and 3/4.1.3.1) 2.4.1 The control rod banks shall be limited in physical insertion as shown in Figure 2.

2.4.2 Successive Control Banks shall overlap by 97 steps.

The sequence for Control Bank withdrawal shall be Control Bank A, Control Bank B, Control Bank C, and Control Bank D.

2.5 Axial Flux Difference (Specification 3/4.2.1) 2.5.1

. The Allowable Operation Limits are provided in Figure 3.

2.5.2 The AXIALFLUXDIFFERENCE (AFD) target bai:d during base load operations is+3%,

-3% (not applicable for this cycle).

2.5.3 The AFD target band is+5%, -5% for a cycle average accumulated burnup > 0.0 MWD/MTU.

Page 3 of 11 Revision 0

0 COLR for DONALDC. COOK NUCLEARPLANTUNIT I CYCLE 16-APRIL 1997 Heat Flux Hot Channel Factor -Fq(Z) (Specification 3.2.2)

FQ(Z) <

  • K(Z) for P >0.5 CFQ P

FQ(Z) < 2

  • CFQ
  • K(Z) forP<0.5 THERMALPOP'ER RATED THERMALPOP'ER 2.6.1 CFq = 2.15 for Westinghouse fuel 2.6.2 K(Z) is provided in Figure 4 for Westinghouse fuel Page 4 of 11 Revision 0

COLR for DONALDC. COOK NUCLEARPLANTUNIT 1 CYCLE 16 - APRIL 1997 2.7 Nuclear Enthal Rise Hot Channel Factor - FNgH (Specification 3/4.2.3)

N F

< CF

  • (1+ PF
  • (1 -P))

THERMALPOWER RATED THERMALPOWER 2.7.1 CFISH = 1.49 for Westinghouse fuel 2.7.2 PFgH = 0.3 Page 5 of 11 Revision 0

COLR for DONALDC. COOK NUCLEARPLANTUNIT 1 CYCLE 16 - APRIL 1997 2.8 Allowable Power Level - APL (Specification 3.2.6) cF,

  • z(z)

APL= min over Z for 2.8.1 V(Z) is provided in Table 1 for+ 5% AFD target band 2.8.2 CFq and K(Z)are provided in COLR Sections 2.6.1 and 2.6.2, respectively 2.8.3 The followingtable shows FP values which correspond to Fq margin decreases that are greater than 2% per 31 Effective Full Power Days (EFPD).

These values shall be used to adjust APL as per Surveillance Requiremellt 4.2.6.2. A 1.02 penalty factor shall be used at all cycle burnups that are outside this range.

~Burne Penalty

~Multi lier 775 900 1025 t 150 1275 1400 1525 1650 1775 1900 2025 2150 1.0200 1.0231 1.0229 1.0227 1.0225 1.0229 1.0238 1.0243 1.0235 1.0222 1.0210 1.0200 The burnup range only covers where Fp exceeds 1.02. Linear interpolation is adequate for intermediate cycle burnups.

Page 6 of 11 Revision 0

I COLR for DONALDC. COOK NUCLEARPLANTUNIT I CYCLE 16-APRIL 1997 FIGURE< 1 MODERATORTEMPERATURE COEFFICIENT (MTC) 1.00 0.90 0.80 0.70

UNACCEPTABLE OPERATION 0.60 0.50 0.40 0.30 0.20 0.10 0.00

-Q 1Q V

~ -0.20 h

ACCEPTABLE OPERATION

-0.30

-0.40

-0.50

-0.60

-0.70

-0.80

-0.90

-1.00 0

10 20 30 40 50 60 70 80 90 100 PERCENT RATED THERMALPOWER Page 7 of 11 Revision 0

COLR for DONALDC. COOK NUCLEARPLANTUNIT 1 CYCLE 16 - APRIL 1997 FIGURE 2 ROD BANKINSERTION LIMITSVERSUS THERMALPOWER FOUR-LOOP OPERATION 250 225 200 (0,51 3,225) 9 7 STEP OVERLAP (1.0, 189) 175 K0 g

150

~

125 g

100 C50 CC 75 i (0, 128)

, (BANKC)

(BANKD) 50 25 (0, 0) 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 FRACTION OF RATED THERMALPOWER Page S of 11 Revision 0

0

COLR for DONALDC. COOK NUCLEARPLANTUNIT 1 CYCLE 16 - APRIL 1997 FIGURE 3 AXIALFLUXDIFFERENCE LIMITSAS A FUNCTION OF RATED THERMALPOWER 100 90

-11.90;

'1.90:

O SO 70 60 50 40 30 E

C g

20 O

gO 0

10 UNACCEPTABLE OPERATION

-31.50 ACCEPTABLE OPERATION

, UNACCEPTABLE OPERATION 1.50

-50

-40

-30

-20

-10 0

10 20 30 40 50 Flux Difference (Delta I), %

Page 9 of 11 Revision 0

0 COLR for DONALDC. COOK NUCLEARPLANTUNIT 1 CYCLE 16-APRIL 1997 FIGURE 4 K(Z) - NORMALIZEDFQ(Z) AS A FUNCTION OF CORE HEIGHT FOR WESTINGHOUSE FUEL 1.2 (0.0, 1.0),

.",:,;.,(6.0, 1.0) 0.8 UK ga 0.6 A

hl 2

CC0K 0.4 I'

t. ~

I I '

N 12.0, 0.925) i 0

0 CORE HEIGHT (FT) 10 12 Page 10 of 11 Revision 0

COLR for DONALDC. COOK NUCLEARPLANTUNIT I CYCLE 16 - APRIL 1997 I.

2.

3.

5.

6.

7.

8.

9.

IO.

I I.

12.

13.

14.

15.

16.

17.

IS.

19.

20 21.

22.

23.

24, 25.

26.

27.

28.

29.

30.

31, 32.

33.

34.

35.

36.

37.

38.

39.

40.

41.

42.

43.

44.

45.

46.

47.

48, 49.

50.

51.

52.

$3.

$4, 55.

$6.

$7.

58.

59.

60, 61.

IIEIGHT 0.0 0.2 0.4 0.6 0.8 1.0 12 1.4 1.6 1.8 2.0 2.2 2A 2.6 2.8 3.0 3.2 3.4 3.6 3.8 4.0 4.2 4A 4.6 4.8 5.0 5.2 5A 5.6 5.8 6.0 62 6.4 6.6 6.8 7.0 72 7A 7.6 7.8 8.0 8.2 8.4 8.6 8.8 9.0 9.2 9A 9.6 9.8 10.0 10.2 10.4 10.6 10.8 I I.O 11.2 11.4 I 1.6 11.8

'12.0 1$0 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0992 1.0988 1.0983 1.0977 1.0969 1.0959 1.0948 1.0934 1.0919 1.0902 1.0885 1.0875 1.0870 1.0864 1.085$

1,0851 L.0852 1.0853 1.0853 1.0852 1,0850 I.OS46 1,0840 1.0831 1.0818 1.0803 1.0784 1.0761 1.0733 1.0701 1.0663 1.0640 1,0668 1.0695 1.0715 1.0734 1.0748 1.0757 1.0779 1.0818 1,0865 INI0 1.0957 1.1003 1.1046 1.1087 1.1125 1.1159 1.1190 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 IA894 1.0991 1.0986 1.0980 1.0971 1.0962 1.0950 1.0936 1.0921 1.0903 1.088$

1.0872 1.0863 1.0855 1.0846 1.0843 1.0844 1.0844 1.0844 1.0843 1.0842 1.0838 1.0832 1.0822 1.0810 1.079$

1.0775 1.0753 1.0732 1.0709 1.0682 I nrt65 t.tr690 1.0714 1.0728 1.0740 1.0750 1.0760 1.0784 1.0824 1.0872 1.0918 1.0965 I.IOI0 1.1053 1.1093 1.1131 1.116$

1.1196 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 3000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.1006 1.1002 1.0997 1.0990 1.0980 1.0970 1,0956 1.0941 IA623 1.0904 1.0885 I.OS66 1,0850 I.0S41 1.0834 1.0833 1.0833 1.0833 1.0833 1.0834 1.0834 1.0830 1.0825 1.0816 1.0803 1.0787 1.0767 1.0745 1.0736 1.0731 1.0724 1.07 IS 1.0736 1.0751 IN54 1.0752 1.0756 I.0769 1.0797 1.0840 1.0889 1.0936 1.0984 1.1029 1.1070 1.1109 1.1146 1.1179 1.1209 1.0000 1.0000 1.0000 1.0000

'.0000 1.0000 2000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0999 1.0996 1.0991 1.0984 1.0975 1.0965 1.0953 1.0938 1.0922 1.0904 1.0885 1.0869 L.0856 1,0847 1.0839 1.0837 1.0837 1.0837 1.0837 1,0837 1.0836 1.0832 1.0826 1.0817 1.0805 1.0789 1.0769 1.0747 1.0732 1.0720 I.%04 1.0693 1.0714 1.0734 1.0741 1.0746 1.0753 1.0764 1.0790 1,0832 1.0880 1.0927 1.0974 1.1019 1.1061 I.I I0 I 1.1138 1,1172 1.1202 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 TABLEI DONALDC. COOK UNIT I CYCLE 16 REDESIGN V(Z)FUNCTION BURNUP (hAVDrbflU) 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.1038 1.1033 1.1026 1.1015 1.1003 1.098 S 1.0971 1.0951 1.0929 1.0906 1.0883 1.0860 I.OS40 1.0834 1.0833 1.0837 1.0840 1.0842 L.OS44 1.0847 1.0849 1.0848 1.0844 1.0836 I.OS23 1.0807 1.0785 1.0764 1.0763 1.0771 1,0780 I 0783 1.0790 1.0792 1.0782 1.0768 1.0767 1.0785 1.0820 1.0866 1.091'7 1.096$

1.1012

'1.1056 1.1096 1.1134 1,1169 1.1202 1.1231 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 10000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.1109 1.1100 1.1087 1.1070 I.L050 1.1027 1.1000 1.0971 1.0938 IN06 1.0876 1.0854 1,0846 L.0853 1.086$

1.0880 1.0891 IASOI 1.0910 1.0919 1.0925 1.0928 IA626 IN20 1.0909 1.0892 1.0869 1.0844 L.0839 1.083&

I.OS42 L,OS43 1.0833 1.0817 I.0S02 1.0788 1.0787 1.0814 1.0857 1.0906 1.0957 1.1004 1.1049 1.1092 1.1132 1.1170 1.1204 1.123$

1.1261 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 12000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.1158 1.1145 1.1128 1.1106 I.IOS I 1.1051 1.1019 1.0983 1.0944 1.0905 1.0871 I 0853 L.0857 1.087$

1.0896 1.0917 1.0936 1.0952 1.096$

1.0977 1.0987 1.0992 1.0993 1.0988 1.0977 1.0960 1.0936 IN09 I.0S94 1.0877 I.0S67 1.0861 I.OS42 1.0817 I.0S03 1.0797 1.0799 1.0832 1,0878 IA629 1.0979 1.1025 1.1067 1.1110 1.1151 1.1189 1.1223 1.1252 1.1278 1,0000 1.0000 1.0000 1.0000 1.0000 1.0000 14000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.1214 1.1196 1.1175 1.1148 1.1116 I.IOSO 1.1040 1.0997 1.0950 1.0903 L.0865 1.0852 1.0873 INOI 1.093$

1,0965 1.0992 1.101$

1.1035 1.1051 1.1064 1.1072 1.1075 1.1071 1.1061 1.1044 1.1020 1.0990 1.0959 1.0920 1.0888 1.0871 I.0S42 1.0808 1.0799 1.0806 1.0812 1.0851 1.0902 1.0953 1.1001 1.1045 1.1085 1.1128 1.1170 1.1209 1.1243 1.1271 1.1294 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 18160 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.1324 1.1298 1.1268 1.1230 1.1186 1.1137 1.1082 1.1024 1.0962 1.0900 1,0854 1.0850 1.0903 1,0959 I.I0 I I 1.1057 1.1100 1.1137 1.1169 1.1192 1.1211 1.1226 1.1233 1.1232 1.1224 1.1207 I.II8 I 1.1144 1.1087 1.1007 1.0936 I.0S99 1.0850 1.0796 1.0795 1.0823 1.0839 1.0890 1.0949 1.1002 1.1047 1.1088 1.1123 1.1165 1.1209 1.1251 1.12S4 1.1309 I.)329 1.0000 1.0000 1.0000 1.0000 1,0000 1.0000 Top and bottom 10'/e ofcore crrcludcd as pcr Tcchniul Spccilications.

Page 11 of 11 Revision 0