PRIORITY 1 (ACCELERATED RIDS PROCESSING)

REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)

ACCESSION NBR:9509290010 DOC.DATE: 95/09/26 NOTARIZED: NO DOCKET FACIL:50-315 Donald C.

Cook Nuclear Power Plant, Unit 1, Indiana M

05000315 50-316 Donald C.

Cook Nuclear Power Plant, Unit 2, Indiana M

05000316 AUTH.NAME AUTHOR AFFILIATION FITZPATRICK,E.

Indiana Michigan Power Co. (formerly Indiana

& Michigan Ele RECIP.NAME RECIPIENT AFFILIATION Document Control Branch (Document Control Desk)

SUBJECT:

Provides clarification re power shape used in large break loss of coolant accident analysis.

DISTRIBUTION CODE:

AOOID COPIES RECEIVED:LTR l ENCLj SIZE:

TITLE: OR Submittal:

General Distribution NOTES RECIPIENT ID CODE/NAME PD3-1 LA HICKMAN,J INTERNAL.

ILE C ~Rssss 1

RCH/HICB NRR/DSSA/SRXB OGC/HDS2 COPIES LTTR ENCL 1

1 1

1 1

1 1

1 1

1 1

0 RECIPIENT ID CODE/NAME PD3-1 PD NRR/DE/EMCB NRR/DSSA/SPLB NUDOCS-ABSTRACT COPIES LTTR ENCL 1

1 1

1 1

1 1

1 EXTERNAL: NOAC 1

1 NRC PDR 1

1 NOTE,TO ALL "RZDS" RECIPIENTS:

PLEASE HELP US TO REDUCE WASTE!

CONTACT THE DOCUMENT CONTROL

DESK, ROOM OWFN 5DS (415-2083)

TO ELIMINATE YOUR NAME FROM DISTRIBUTION LISTS FOR DOCUMENTS YOU DON'T NEED!

TOTAL NUMBER OF COPIES REQUIRED:

LTTR 12 ENCL 11

1 1

Indiana Michigan Power Company P.O. Box 16631 Columbus, OH 43216 N

'September 26, 1995 AEP:NRC:1207A Docket Nos.

50-315 50-316 U. S. Nuclear Regulatory Commission Document Control Desk Washington, D.C.

20555 Gentlemen:

DONALD C.

COOK NUCLEAR PLANT UNITS 1 AND 2 LICENSE NOS.

DPR-58 AND DPR-74 CLARIFICATION OF POWER SHAPE USED IN LOCA ANALYSIS This letter and its attachment provide clarification regarding the power shape used in the large break loss of coolant accident (LBLOCA) analysis provided as part of our submittal dated May 26, 1995 and identified as AEP:NRC:1207.

Submittal AEP:NRC:1207 requested approval for technical specification changes associated with our effort to license operation of Unit 1 with up to 30% of the steam generator tubes plugged.

We recently received notification from the vendor performing the LBLOCA analysis, Westinghouse Electric Corporation, that the power shape methodology for LBLOCA analyses has been revised.

We have submitted a 10CFR50.46 report describing the impact of the revised methodology on the analyses of record as submittal AEP:NRC:1118J.

We have also discussed with Westinghouse the potential impact of the revised power methodology on the LBLOCA analysis submitted with AEP:NRC:1207. It has been concluded that the revised power shape methodology does not have any effect on the limiting PCT for the LBLOCA analysis submitted in AEP:NRC:1207.

This conclusion is included in the attachment to this letter.

This is provided for your information only.

Sincerely, u/.4.

E.

E. Fitzpatrick Vice President Attachment "G0002 950'F290010 950926 PDR ADOCK 05000315 P

'PDR

e 4W U. S. Nuclear Regulatory Commission Page 2

AEP'NRC'1207A cc:

A. A. Blind G. Charnoff H. J. Miller NFEM Section Chief NRC Resident Inspector

- Bridgman J.

R. Padgett

ATTACHMENT TO AEP'NRC: 1207A WESTINGHOUSE DOCUMENT DESCRIBING POWER SHAPE RELATIONSHIP FOR LBLOCA ANALYSIS SUBMITTED IN AEP'NRC'1207

Attachment 4'ffect of LOCA Axial Power Shape Sensitivity Model on the Vnit 1 Large Break LOCA analysis for 30% SGTP Westinghouse has recently notified American Electric Power Seivice Corporation that the Power Shape Sensitivity Model (PSSM), which was applied to ensure that the cosine axial power distribution used in large break LOCA analyses remains limiting, is being withdrawn effective October 30, 1995.

PSSM is being replaced by an alternate axial power shape methodology (ESHAPE) which is based on explicit analysis of a set of skewed axial power shapes.

The purpose of this letter is to inform you of the effect of this change on the large break LOCA analysis which has been submitted to support the 30% Steam Generator Tube Plugging (SGTP) Program for D. C. Cook Unit l.

The large break LOCA analysis for the 30% SGTP Program was performed using a cosine axial power distribution, with the intent of applying PSSM to ensure that the cosine distribution remained limitingduring operation.

Since PSSM is being withdrawn, an evaluation was performed to determine the impact on the analysis ifthe ESHAPE methodology is applied.

This evaluation included a "compensatory benefit" which was developed by Westinghouse to reduce or eliminate 'the: ""

PCT penalty associated with the change from PSSM to ESHAPE. This compensatory benefit results from the incorporation of the hot leg nozzle gap into the BASH Methodology.

The evaluation for the 30% SGTP analysis demonstrated that the PCT for skewed power shapes, in conjunction with the application of the hot leg nozzle gap model, would be less than the PCl'or the existing analysis performed with a cosine axial power shape with the application of,the hot leg nozzle gap model.

Thus, the existing large break LOCA analysis with a cosine power shape remains limiting and there'is no PCI'enalty for skewed power shapes.

It is noted that the hot leg nozzle gap is not required for the cosine shape analysis, and was only used to demonstrate that the cosine shape analysis remains limiting.

The reason that the large break LOCA analysis for 30% SGTP is not affected is that the impact of skewed power shapes is less pronounced for relatively early PCTs (less than approximately 100 seconds),

and the benefit from the hot leg nozzle gap is also less sigriificant for early PCTs.

For the limiting large break LOCA analysis case for 30% SGTP, the calculated PCT with a cosine power shape. is 2164.'F at approximately 77 seconds, An analysis for this case with the limiting skewed power shape resulted in a delay in the PCI'ime to approximately 265 seconds with a PCI'ncrease

'of 102'F.

The'application of the hot leg nozzle gap in conjunction with the skewed power shape then resulted in a benefit of 237 F, for a net PCT reduction of 135'F.

The effect of the hot leg nozzle gap would not reduce the PCT significantly for the cosine power shape since the PCI'ccurs relatively early for that case.

Thus, the PCT of 2164'F for the cosine power shape would remain limitingfor the, 30% SGTP analysis, and there is no PCT penalty for skewed power shapes.

On this basis, it is concluded that the existing Unit 1 large break LOCA analysis for 30% SGTP with a cosine power shape is not affected by this issue.

In summary, the existing Unit 1 30% SGTP large break LOCA analysis with a cosine power shape is not affected by the change from PSSM to the ESHAPE methodology, and the analysis remains applicable as submitted.