Monthly Operating Rept for Sept 1993 for DC Cook Nuclear Plant,Unit 1
ML17331B005
Person / Time
Site: Cook 
Issue date: 09/30/1993
From: Reynnells R, Russo M, Doreen Turner
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
Shared Package
ML17331B004 List:
References
NUDOCS 9310190274
Download: ML17331B005 (6)


Text

N.R.C.

OPERATING DATA REPORT DOCKET NO.

50-315 DATE 02/Oct/93 COMPLETED BY DG TURNER TELEPHONE 616-465-5901 OPERATING STATUS

1. Unit Name D.

C.

Cook Unit 1

2. Reporting Period SEPT 1993
3. Licensed Thermal Power (MWt) 3250 4.

Name Plate Rating (Gross MWe) 1152

5. Design Electrical Rating (Net MWe) 1020 6.

Maximum Dependable Capacity (GROSS MWe) 1056 7.

Maximum Dependable Capacity (Net MWe) 1000 notes

8. If Changes Occur in Capacity Ratings (Items no.

3 through

7) Since Last Report Give Reasons 9.

Power Level To Which Restricted. If Any (Net MWe) 10.

Reasons For Restrictions. If Any:

This Mo.

Yr. to Date Cumm.

11.

Hours in Reporting Period 720.0 6551.0 164351.0 12.

No. of Hrs. Reactor Was Critical 720.0 6551.0 123445.4

13. Reactor Reserve Shutdown Hours 0.0 0.0 463. 0
14. Hours Generator on Line 720.0 6551.0 121399.6
15. Unit Reserve Shutdown Hours 0.0 0.0 321. 0
16. Gross Therm.

Energy Gen.

(MWH) 2214841 20947490 356389813

17. Gross Elect.

Energy Gen.

(MWH) 707030 47455200 115709560

18. Net Elect.

Energy Gen.

(MWH) 680592 6526550 111288915

19. Unit Service Factor 100.0 100. 0 74.8
20. Unit Availability Factor 100.0 100.0 74.8
21. Unit Capacity Factor (MDC Net) 94.5 99.6 67.3
22. Unit Capacity Factor (DER Net) 92.7 97 '

65.7

23. Unit Forced Outage Rate 0.0 0.0 6.1 24.

Shutdowns Scheduled over Next Six Months (Type, Date,and Duration):

Refuelin outa e to be in Februar 5

1994 for an estimated duration of 90 da s.

25. If Shut Down At End of Report Period, Estimated Date of Startup:
26. Units in Test Status (Prior to Commercial Operation):

Forcast INITIALCRITICALITY INITIALELECTRICITY COMMERCIAL OPERATION Achieved 9310190274, 931006 PDR

,.ADOCK 05000315, R

'.-, PDR

\\

~

I I

AVERAGE DAILY POWER LEVEL (MWe-Net)

DOCKET NO.

50-315 UNIT ONE DATE 04/Oct/93 COMPLETED BY DG TURNER TELEPHONE 616-465-5901 DAY MONTH AVERAGE DAILY POWER LEVEL SEPT 1993 DAY AVERAGE DAIL POWER LEVEL 09/01/93 09/02/93 09/03/93 09/04/93 09/05/93 09/06/93 09/07/93 09/08/93 09/09/93 09/10/93 09/11/93 09/12/93 09/13/93 09/14/93 09/15/93 09/16/93 1001 996 1002 959 999 997 995 995 999 940 493 496 506 898 996

998, 09/17/93 09/18/93 09/19/93 09/20/93 09/21/93 09/22/93 09/23/93 09/24/93 09/25/93 09/26/93 09/27/93 09/28/93 09/29/93 09/30/93 999 998 1001 1005 1008 1009 1007 994 1003 1016 1015 1013 1011 1008 0

UNIT SHUTDOWNS AND POWER REDUCTIONS REPORT MONTH: "SEPTEMBER 1993 UNIT NAME:

DATE:

COMPLETED BY:

TELEPHONE:

Page 1 of 1 D. C.

COOK UNIT 1 October 8,'993

~

R. D. Reynnells (616) 465-5901 DURATION NO.

DATE TYPE HOURS METHOD OF SHUTTING LICENSEE DOWN EVENT REASON REACTOR REPORT NO~

SYSTEM CODE4 COMPONENT CAUSE AND CORRECTIVE ACTION CODE TO PREVENT RECURRENCE 306 930910 S

N/A N/A N/A N/A N/A The reactor power was reduced to 55%

RTP on 930910 to support the application of a Clamtrol Treatment for zebra mussel control.

1 Fe S

Forced Scheduled 2

Reason:

As Equipment Failure (Explain)

B:

Maintenance or Test C:

Refueling D:

Regulatory Restriction Es Operator Training and License Examination

. F:

Administrative G:

Operational Error (Explain)

H:

Other (Explain) 3 Methods 1:

Manual 2:

Manual Scram 3:

Automatic Scram 4:

Other (Explain) 4Exhibit G Instructions for preparation of data entry sheets for Licensee Event Report (LER) File (NUREG 1061) 5Exhibit I:

Same Source

DO T NO.:

UNIT NAME:

COMPLETED BY:

TELEPHONE:

DATE:

PAGE 50-315 D.C.

Cook Unit 1 R.

D. Reynnells (616) 465-5901 Oct. 8, 1993 Page 1 of 1 MONTHLY OPERATING ACTIVITIES SEPTEMBER 1993 HIGHLIGHTS The unit entered the reporting period in Mode 1 at 100 4 RTP.

On September 10, 1993 reactor power was reduced to 554 RTP to establish system conditions required to support "Clamtrol" treatment of circulating water and service water systems for zebra mussels.

Reactor power was restored to 1004 RTP on September 14, 1993.

The unit exited this reporting period in Mode 1 at 100 4 RTP.

There were no challenges to the pressurizer safety valves or power operated relief valves.

Gross Electrical generation for the month of August was 707030 MWH.

DETAILS 09-04-93 09-10-93 0133 Commenced reactor power decrease to 90< RTP for turbine valve testing.

0430 Reactor power is at 904 RTP.

1120 Commenced reactor power increase to 1004 RTP.

1325 Reactor power is at 100% RTP.

1906 Commenced reactor power decrease to 554 RTP to support Clamtrol Treatment for zebra mussel control.

09-11-93 0125 Reactor power is at 55% RTP.

09-13-93 2300 Commenced reactor power increase to 1004 RTP.

09-14-93 1350 Reactor power is at 100% RTP.

DOCKET NO:

UNIT NAME:

COMPLETED BY:

TELEPHONE:

DATE PAGE 50-315 D.C.

Cook Unit 1 M. E. Russo (616) 465-5901 October 6,

1993 1 of 1

MAJOR SAFETY-RELATED MAINTENANCE Se tember 1993 No major safety-related maintenance items are included for the month of September.