ML17331A711

From kanterella
Jump to navigation Jump to search
Forwards Required Circuit Mods Per 810202 Request & 800620 Response to IE Bulletin 80-06, Engineered Safety Feature Reset Controls. Mods Will Be Implemented by 810831
ML17331A711
Person / Time
Site: Cook  
Issue date: 05/04/1981
From: Hunter R
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To: Harold Denton
Office of Nuclear Reactor Regulation
References
AEP:NRC:00387A, AEP:NRC:387A, IEB-80-06, IEB-80-6, NUDOCS 8105070283
Download: ML17331A711 (5)


Text

-REGULATOR'FORMATION'ISTRIBUTIONS~E i (RIOS~)

<<4

, ACCESSION NBRi81050T0283 OUC ~ OATEN'1/05/04 NOTARIZED'O DOCKET' FACIL:50 315 Donald C ~

Cook Nuclear Power. Pl anti Unit 1~ Indiana 8

05000315 50 316 Donald C.

Cook Nuclea~

Power Plant~ Unit 2~ Indiana 8

'003T'UTH

~ NAHE AUTHOR AFFILIATION HUNTERgR ~ ST Indiana 8 Michigan Electric Co ~

REC IP, MANE RECIPIENT AFFILIATION DENTON>HER, 'ffice of Nuclear Reactor Regulationi Director SUBJECT; Forw'ards required circuit mods per 810202 request 5 800620 response to IE, Bulletin 80 06'Engineered Safety Feature Reset Cont'rois,"

Boas will be implemented by 810831

'ISTRIBUTION COOEo A001S COPIES RECEIVED:LTR ENCL SIZE:

5 TITLE: Gener al Distribution for af ter Issuance of Oper ating. License NOTES:ICE:3 copies all mater ial ~

Send 3 copies of all material to ILES 05000315 05000316 RECIPIENT IO CODE/NAME ACTION.

VARGA g S, 04 INTERNAL D/DIRpHUiil FAC08 ILE 06 OELD 11 RAD ASMT BR COPIES LTTR ENCL 13 13 1

1 2

2 1

0 1

1 RECIPIENT ID CODE/NAHE DIR/DIV OF LIC NRC PDR 02 OR~SSESS BR 10 oi COPIFS LTTR ENCL 1

1 1

1 1

0 1

1 EXTERNALo ACRS NSIC 09 05 16 16 1

1 LPOR 03 MPY 0> >981 1'Q 5'OTAL NUMBER OF COPIES REQUIRED:

LTTR ~

ENCL

INDIANA II MICHIGAN ELECTRIC COMPANY P. O. BOX 18 BOWLING GREEN STATION NEW YORK, N. Y. 10004 C,

AEP:NRC:0038 Donald C.

Cook Nuclear Plant Unit Nos.

1 and 2

Docket Nos.

50-315 and 50-316 License Nos.

DPR-58 and DPR-74 IE Bulletin 80-06, Additional Information

,,<b.

gl Mr. Harold R. Denton, Director Office of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Washington, D.

C.

20555

Dear Mr. Denton:

This letter and its Attachment supplement our letter of June 20, 1'980 (AEP:NRC:00387) and provide the additional information requested by members of your staff and their consultants concerning our response to IE Bulletin 80-06 on the matter of ESF reset controls.

As a result of both the testing being conducted pursuant to the requirements of the subject Bulletin and additional engineering review, the test breaker control circuit for the Emergency Diesel Generator (EDG) needs to be modified to conform to the Bulletin require-ments.

In the current design, the test breaker changes position after the'Safety Injection signal has been reset.

This additional modification is being implemented on the same schedule as our previous commitments.

In our June 20, 1980 letter we committed to perform modifications in conformance with the Bulletin requirements, in the control circuits of the following equipment:

a)

Component Cooling Water Pump Emergency Ventilation Fans 12-HV-ACCP-1, -2, -3, b)

Engineered Safeguards Equipment Room Ventilation Dampers HV-AES1D, - AES2D, c)

Containment Air Recirculation Hydrogen Skimmer Fans HV-CEQ-1, -2.

+o(

/I

Mr. Harold R. Denton AEP:NRC:00387A A description of the required circuit modifications as 'requested on February 2, 1981 is provided in the Attachment to this letter.

Our June 20, 1980 letter also pointed out that no modifications to the control circuits of the main feedwater regulating valves were necessary since there is no unacceptable safety-related consequence to the valve changing its position when the feedwater isolation signal is reset.

On March 11, 1981, we were informed by members of your staff that the main feedwater regulating valve control circuits should conform to the bulletin's requirements, i.e. the valves should not change their emergency mode of operation upon reset of Feedwater Isolation.

The control circuits of the main feedwater regulating valves, in our present

design, receive a

Feedwater Isolation signal which causes an interruption of the power air to the valve operator by de-energizing either the Train A or Train B

solenoid valves.

This interruption causes the feedwater regulating valves to close.

We will modify our procedures involving resetting of Feedwater Isolation by adding steps to require the operator to place the feedwater regulating valve controllers in their manual closed position corresponding to zero feedwater flow before resetting the Feedwater Isolation signal.

Upon reset, the valve will now remain in the closed position, thereby con-forming to the bulletin's requirements.

This procedural change will be implemented in both Units 1 and 2 by August 31, 1981.

We believe that since the motor operated block valve in series with each feedwater regulating valve does not change its emergency mode of operation (i.e. closed) upon resetting Feedwater Isolation, this additional administrative control on the redundant function performed by the feedwater regulating valve is sufficient and adequately addresses the bulletin concerns without adding unnecessary complication to the control circuit.

Very truly yours, RSH/os R.

S. Hunter Vice President cc:

John E. Dolan - Columbus R.

C. Callen G. Charnoff R.

W. Jurgensen D. V. Shaller - Bridgman N. C. Moseley -

NRC (OIE)

Region III Resident Inspector at Cook Plant - Bridgman

ATTACHMENT TO AEP:NRC:0387A This attachment provides the description of the control circuit modifications necessary to prevent changing the emergency operating mode of ESF equipment upon the r esetting of the actuating signal at system level.

We committed to perform these modifications in our letter of June 20, 1980 (AEP:NRC:00387) which responded to IE Bulletin 80-06.

The Containment Air Recirculation Hydrogen Skimmer Fan Controls were acceptable as they were, except for the case in which the Containment Isolation, Phase B (CI-B) signal was reset before the 10 minute starting delay had elapsed.

In this case, the starting delay timer would reset and the fan would not start.

The circuit design was revised to provide a

seal-in circuit which kept'he starting delay timer energized after a CI-B signal had been initiated and subsequently reset.

The fan will start and continue to run unless the operator turns the fan contr'ol switch to the "off" position 'following the system level reset of CI-B.

A white indicating light has been provided to inform the operator that the seal-in circuit is operating.

The Engineered Safeguards Equipment Room Ventilation Fan charcoal filter bypass damper control circuit design was revised to include a seal-in circuit to keep the bypass damper control solenoid valves de-energized following an actuation and subsequent reset of CI-B signal.

A white in-dicating lamp is provided to inform the operator that the damper control circuit is sealed in.

A push button is provided which will allow the operator to interrupt the seal-in of this control circuit after a CI-B signal has been reset at the system level.

The operator may then position the damper as required.

The design of the control circuits to the Component Cooling Water Pump Emergency Ventilation Fans were revised to include a seal-in circuit around the -initiating contact.

The initiating contact operates on load conservation following loss of auxiliary power coincident with safety injection.

The initiating signal is maintained for 75 seconds which pro-vides more tha'n sufficient time for the bus to be re-energized from the emergency power source.

With the modified circuit, the fans will continue running after the reset of the load conservation signal.

With the EDG in the testing mode the test breaker is closed.

If a Safety Injection is initiated, the test breaker trips open as it should,

however, upon reset of. the SI signal at the system level, the test breaker closes.

The control circuit design of the EDG test breaker will be modified to prevent the breaker from reclosing to the test bank upon reset of the SI signal.

We are modifying the control of the breaker by adding a con-tact from the breaker's control switch in series with the breaker closing circuit.

This contact will be closed only when the control switch is in the'losed position.

This will prevent the breaker from reclosing once it has tripped open.

Operator action will be required for the breaker to be closed again.

In the event of a loss ofoffsite power requiring the EDG to en-ergize its corresponding safety buses an interlock is already provided in the control circuit design which prevents the test breaker from reclosing when the breakers connecting the EDG to its safety buses are closed.