LER 81-001/03L-0:on 810103,annunciator Indicated Loss of Control Voltage to West RHR Pump,Making Train of RHR Inoperable.Caused by Loose Fuse Clip on Main Control Fuses. Clip Adjusted & Breaker Cycled.Pump Placed on mini-flow
ML17331A602
Person / Time
Site: Cook 
Issue date: 01/23/1981
From: Murphy C
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML17331A602 (4)
Forwards LER 81-001/03L-0
ML17331A600
Person / Time
Site: Cook 
Issue date: 01/23/1981
From: Shaller D
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To: KEPPLER J G
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML17331A600 (2)