LER 80-032/03L-0:on 800904,while Returning East RHR Pump to Svc After Maint,Pump Became Unstable & Declared Inoperable. Caused by Air in Sys During Fill & Vent.Procedure Changed & Problem Eliminated
ML17331A469
Person / Time
Site: Cook American Electric Power icon.png
Issue date: 10/03/1980
From: Murphy C
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML17331A469 (4)
LER 80-031/03L-0:on 800902,bistable for Containment Pressure hi-hi Protection Set II Tripped at 3.1005 Psig,Exceeding Limiting Conditions for Operation.Caused by Instrument Drift.Bistable Adjusted & Returned to Svc
ML17331A468
Person / Time
Site: Cook American Electric Power icon.png
Issue date: 10/03/1980
From: Delong S
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML17331A468 (1)
Forwards LERs 80-031/03L-0 & 80-032/03L-0
ML17331A466
Person / Time
Site: Cook American Electric Power icon.png
Issue date: 10/03/1980
From: Shaller D
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To: KEPPLER J G
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
Download: ML17331A466 (2)