ML17328A811

From kanterella
Jump to navigation Jump to search
Submits Steam Generator Tube Plugging Rept.Insp of Tubes Commenced on 901116 & Completed on 901201
ML17328A811
Person / Time
Site: Cook 
Issue date: 12/14/1990
From: Blind A
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To: Davis A
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 9012170163
Download: ML17328A811 (4)


Text

ACCELERATED D TRIBUTION DEMONST TION SYSTEM REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)

ACCESSION NBR:9012170163 DOC.DATE: 90/12/14 NOTARIZED: NO DOCKET.g FACIL:50-315 Donald C.

Cook Nuclear Power Plant, Unit 1, Indiana 05000315 AUTH.NAME AUTHOR AFFILIATION BLIND,A.A.

Indiana Michigan Power Co.

(formerly Indiana

& Michigan Ele RECIP.NAME RECIPIENT AFFILIATION DAVIS,A.B.

Document Control Branch (Document Control Desk)

SUBJECT:

Submits steam generator tube plugging rept.Insp of tubes commenced on 901116

& completed on 901201.

DISTRIBUTION CODE:

AOOID COPIES RECEIVED:LTR 3 ENCL 0

SIZE:

TITLE: OR Submittal:

General Distribution NOTES RECIPIENT ID CODE/NAME PD3-1 LA COLBURN,T.

INTERNAL: NRR/DET/ECMB 9H NRR/DOEA/OTSB11 NRR/DST/SELB 8D NRR/DST/SRXB 8E

~B REG FILE 01 EXTERNAL: NRC PDR COPIES LTTR ENCL 1

2 RECIPIENT ID CODE/NAME PD3-1 PD NRR/DET/ESGB NRR/DST 8E2 NRR/DST/SICB 7E NUDOCS-ABSTRACT OGC/HDS1 RES/DSIR/EIB NSIC COPIES LTTR ENCL NOTE TO ALL"RIDS" RECIPIENTS:

PLEASE HELP US TO REDUCE WASTE! CONTACT THE DOCUMENT CONTROL DESK, ROOiVI Pl-37 (EXT. 20079) TO ELIMINATEYOUR NAME FROM DISTRIBUTION LISTS FOR DOCUMENTS YOU DON'T NEED!

TOTAL NUMBER OF COPIES REQUIRED:

LTTR 18 ENCL

t l

ry

~

Indiana Michlga~

Power Company ~

Cook Nuclear Plant P.O. Box 458 Bridgman, Ml 49106 616 465 5901 Donald C.

Cook Nuclear Plant Unit 1 Docket No. 50-315 License No.

DPR-58 STEAM GENERATOR TUBE PLUGGING REPORT U.S. Nuclear Regulatory Commission Attn:

Document Control Desk Washington, D.C.

20555 Attn:

A. B. Davis December 14, 1990

Dear Mr. Davis:

Pursuant to the requirements of Donald C.

Cook Nuclear Power Plant"'Technical Specification 4.4.5.5(a), this letter is to inform you of the number of steam generator tubes plugged as a result of eddy current examination activities performed during the 1990 Unit 1 Refueling Outage.

Inspection of Unit 1 steam generators began on November 16,

1990, was completed on December 1,
1990, and included 100 percent of all previously nonplugged tubes.

The total number of tubes examined in each steam generator included 3,208 in SG-11, 3,240 in SG-12, 3,246 in SG-13, and 3,221 in SG-14

'onservative steam generator tube plugging criteria, similar to that utilized during the inspection of April-May 1989, were implemented as follows:

In the hot leg tubesheet crevice and tubesheet surface regions (up to approximately 6

inches) all clean indications or other signals representing possible tube wall degradation, regardless of voltage or phase

angle, were plugged.

At hot leg support plate intersections clear indications meeting a threshold voltage of 1.75 volts and having indicated through wall penetrations of a 40 percent were considered pluggable.

90i2170i63 goi2i43i FDR ADOCK OSOOO gy-Q

  • g H~~l Qgjgg~

//g

1 Steam Generator Tube Plugging Report December 14, 1990 Page 2 of 2 Applying the conservative evaluation criteria resulted in plugging a total of 170 tubes.

The number of tubes plugged per steam generator were 64 tubes in SG-11, 18 tubes in SG-12, 57 tubes in SG-13, and 31 tubes in SG-14.

Of the total number of tubes plugged 19 were plugged based on Technical Specification requirements (z 40 percent tube wall degradation) and included 5 tubes in SG-11, 8 tubes in SG-12, 5 tubes in SG-13, and 1 tube in SG-14.

Respectfully,

~

~

~

A. A. Blind Plant Manager

/cbm c:

D. H. Williams, Jr.

R.

C. Callen G. Charnoff T. E. Murley NRC Resident Inspector Bridgman NFEM Section Chief