ML17326B327

From kanterella
Jump to navigation Jump to search
Monthly Operating Rept for Dec 1987
ML17326B327
Person / Time
Site: Cook 
Issue date: 12/31/1987
From: Giles H, Puplis A, Will Smith
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
NRC
References
NUDOCS 8802050015
Download: ML17326B327 (11)


Text

REGULATOR NFORMATION DISTRIBUTION TEN (RIDS)

'ACCESSION NBR: 8802050015 DOC. DATE: 87/12/31 NOTARIZED:

NO DOCKET 0 FACIL: 50-315 Donald C.

Cook Nuclear Power Planti Unit ii Indiana 0

05000315 AUTH. NAME

'UTHOR AFFILIATION QILESI H.

Indiana Michigan Power Co.

(formerly Indiana 8c Michigan Ele PUPLISI A. S. 'ndiana Michigan Power Co.

(formerly Indiana 5 Michigan Ele SMITHI M. Q.

Indiana Michigan Power Co.

(formerly Indiana 8c Michigan Ele RECIP. NAME

'ECIPIENT AFFILIATION

SUBJECT:

Monthly operating rept for Dec 1987. N/880108 itr.

DISTRIBUTION CODE:

IEE4D COPIEB RECEIVED'LTR l

ENCL I

SIZE:

(D TITLE: Monthly Operating Report (per Tech Specs)

NOTES:

RECIPIENT ID CODE/NAME PD3-3 LA WIQQINQTON. D INTERNAL: AEOD/DOA ARM TECH ADV NRR/DOEA/EAB NRR/PMAS/ ILRB RQN3 EXTERNAL:

EQ8cQ QROH~ M NRC PDR COPIES LTTR ENCL 1

0 1

0 1

2 2

1 1

1 1

1 1

1 1

RECIPIENT ID CODE/NAME PD3-3 PD AEOD/DSP/TPAB NRR/DLPG/PEB NR /DRE RPB EG FILE, 01 LPDR NBIC COPIES LTTR ENCL 5

5 1

1 1

1 1

1 1

TOTAI NUMBER OF COPIES REQUIRED:

LTTR 21 ENCL 19

k 4

N

'I I'

I4 4'

N.R.C.

OPERATING DATA REPORT DOCKET NO.

50-315 DATE 1/6/88 COMPLETED BY H. Giles TELEPHONE 616-465-5901 OPERATING STATUS

l. Unit Name D.

C.

Cook Unit 1

2. Reporting Period DEC87

',notes

3. Licensed Thermal Power (MWt) 3250,.

4.

Name Plate Rating (Gross MWe) 1152

5. Design Electrical Rating (Net HWe) 1030 6.

Maximum Dependable Capacity (GROSS HWe) 1056 7.

Haximum Dependable Capacity (Net MWe) 1020

8. If Changes Occur in Capacity Ratings (Items no.

3 through 7) Since Last Report Give Reasons 9.

Power Level To Which Restricted. If Any (Net MWe) 10.

Reasons For Restrictions. If Any-This Mo.

Yr. to Date Cumnj.

11.

Hours in Reporting Period 744.0 8760 '

113952.0 12.

No. of Hrs. Reactor Was Critical 744.0 6000.6 81826.4

13. Reactor Reserve Shutdown Hours 0.0 0.0 463.0 14.

Hours Generator on Line 744.0 5922.8 80241.4

-15. Unit Reserve Shutdown Hours 0.0 0

~ 0 321.0 16.

Gross Therm.

Energy Gen.

(MWH) 2096851 16005334 232637843 17.

Gross Elect.

Energy Gen.

(MWH) 683500 5560570 76456440 18.

Net Elect.

Energy Gen.

(MWH) 656519 5371490 73568721 19.,Unit Service Factor 100.0 67.6 71.6 20'nit Availability Factor 100.0 67.6 71.6

21. Unit Capacity Factor (MDC Net) 86.5 60.1 64.4 22: Unit Capacity Factor (DER Net) 85 '

59.5 62.3

23. Unit Forced Outage Rate 0.0 5.8 8.3 24.

Shutdowns Scheduled over Next Six Months (Type, Date,and Duration):

Ice condenser survei11ance ou~ ~~gin zn&pril~MB~~~~

estimated duration of 10 dias,

25. If Shut. Down At End of Report Period, Estimated Date of Startup:
26. Units in Test, Status (Prior to Commercial Operation):

Forcast INITIALCRITICALITY INITIALELECTRICITY COMHERCIAL OPERATION Achieved

~O><<>5 871g31--

R

<>>OOO3>S PDR

AVERAGE DAILY POWER LEVEL (MWe-Net)

DOCKET NO.

50-315 UNIT ONE DATE 1/6/88 COMPLETED BY H. Giles TELEPHONE 616-465-5901 DAY 1

2 3

4 5

6 7

8 9

10 11 12 13 14 15 16 MONTH AVERAGE DAILY POWER LEVEL 922 920 922 921 923 921 923 923 924 923 922 921 923 922 921 922 DEC87 DAY 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 AVERAGE DAILY POWER LEVEL 922 922 922 921 921 921 921 900 545 524 531 887 924 921 922

UNITSIIUTI)(WNShNI) PO1NII RFI)U(.'11ONS g

~E<<

I)0(.'KET No.

(.'()Mpl.~l)It/

~

t.

mand N<<.

l4te g o A

voI

~ P/l I.ILcoscc I:vcIII Repin l tt

( ause 4 (utteellvc hcthol l<<

Ptevenl llcelltfcoec 265 871224 S

0

.H N/A-HF HTEXCH Power was reduced from 90% to 56K to allow cleaning of the main feedpump condensers.

Following cleaning, power was increased to 90$.

I': I:<<teed S: Sehedtded (91771 Reasons:

h.l llldploeol Italhllc(f:xpfalt)).

IJ.Mahilcttattcc <<i1'csl C-Refuclbtg I) Retodatmy Rest tletiuo li-Opetatiu I'tabtlog 4 Ucettsc I:xatohtall>>u I'-Adodolsttallve (I ()pctaliwtal ht<<t II:xplaiol II (lihct (Iixldab>ot.

4.0thet (Lxplahtl ltxldbll Ci ~ lost toetiuns f<<t ptepatatinu ofl)ata I:ntty Sheets f<<t I.kcnsee I!vent Rep<e Sio>>ee

DOCKET NO:

UNIT NAME'OMPLETED BY:

TELEPHONE:

DATE:

PAGE:

50-315 D. C.

Cook Unit 1 A. S. Puplis (616) 465-5901 January 8, 1988 lof1 HIGHLIGHTS:

MONTHLY OPERATING ACTIVITIES -

DECEMBER 1987 The reporting period began with the unit in Mode 1 at 90% of rated thermal power.

The unit remained at 90$ power until 1730 on 12-24-87, at which time a power reduction to 56K was initiated for cleaning of the East and West Feed Pump Turbine Condensers.

The unit reached 56% power at 0240 on 12-25-87.

A power increase to 90K was started at 2138 on 12-27-87 and terminated at 0509 on 12-28-87 when the unit reached 905 rated thermal power.

The reporting period ended with the unit at 90$ of rated thermal power.

Gross electrical generation was 683,500 MWH for the month.

SUMMARY

12-29-87 1053 12-31-87 0253 0305 Containment integrity at containment penetration No.

67 was broken for performance of a surveillance test procedure.

The limiting condition of operations for Technical Specification 3.6. 1.1 was entered.

At 1106 the same day containment integrity was re-established.

Technical Specification 3.0.3 was voluntarily entered to cycle a motor operated valve for normal surveillance testing.

Pressurizer relief valve block valve was declared inoperable because the valve closure time could not be determined.

The valve was closed, and the power supply isolated to satisfy the requirements of Technical Specification 3.4.1.1.

DOCKET NO.

UNIT NAME DATE COMPLETED BY TELEPHONE PAGE 50-315 D.

C.

Cook - Unit No.

1 Januar 8,

1988

. L. St.

man 616 465-5901 1 0 1

MAJOR SAFETY-.RELATED MAINTENANCE DECEMBER, 1987 1-DCR-310 (Steam Generator 3 Blowdown Containment Isolation Valve) had a body-bonnet leak.

The valve was disassembled, inspected, and reassembled with new intervals.

The valve tested satisfactorily.

\\

N

~r 1

u tl

Indiana Michigan Power Company Cook Nuclear Plant P.O. Box 458 Bridgrna, Ml 49106 616 465 5901 Director, Office Of Management, Informati on and Program Control U. S. Nuclear Regulatory Commission Washington, D. C.

20555 January 8, 1988 Gentlemen:

Pursuant to the requirements of Donald C.

Cook Nuclear Plant Unit 1 Technical Specification 6.9.1.10, the attached Monthly Operating Report for the Month of December, 1987 is submitted.

Sincerely, W.

G. Smith, Jr.

Plant Manager WGS/jd cc:

J.

E. Dolan M. P. Alexich R.

W. Jurgensen R. C. Callen C. A. Erikson D.

W. Paul D. R.

Hahn J. J.

Markowsky E. A. Morse PNSRC File INPO Records Center ANI Nuclear Engineering Department T. R. Stephens NRC Region III B. L. Jorgensen S. L. Hall D. A. Timberlake EPRI--Nuclear Safety Analysis Center

~qS~y,g

~ye<

l, 4 ~