ML17326A691
| ML17326A691 | |
| Person / Time | |
|---|---|
| Site: | Duane Arnold (DPR-049) |
| Issue date: | 11/21/2017 |
| From: | Nestor Feliz-Adorno Engineering Branch 3 |
| To: | Dean Curtland NextEra Energy Duane Arnold |
| References | |
| IR 2018010 | |
| Download: ML17326A691 (6) | |
See also: IR 05000331/2017010
Text
UNITED STATES
NUCLEAR REGULATORY COMMISSION
REGION III
2443 WARRENVILLE RD. SUITE 210
LISLE, ILLINOIS 60532-4352
November 21, 2017
Mr. Dean Curtland
Director of Site Operations
NextEra Energy Duane Arnold, LLC
3277 DAEC Road
Palo, IA 52324-9785
SUBJECT: DUANE ARNOLD ENERGY CENTERREQUEST FOR INFORMATION
FOR AN NRC DESIGN BASES ASSURANCE INSPECTION (PROGRAM):
IMPLEMENTATION OF THE ENVIRONMENTAL QUALIFICATION PROGRAM;
INSPECTION REPORT 05000331/2018010
Dear Mr. Curtland:
On April 23, 2018, the U. S. Nuclear Regulatory Commission (NRC) will begin a triennial
baseline Design Bases Assurance Inspection (Program) at the Duane Arnold Energy
Center. This inspection will be performed in accordance with NRC Baseline Inspection
Procedure 71111.21N, Attachment 1.
The Design Bases Assurance Inspection will focus on the implementation of the electrical
equipment Environmental Qualification (EQ) Program to verify you are maintaining the qualified
status of equipment during the life of the plant. The EQ components to be reviewed during this
baseline inspection will be identified during the in-office preparation week that occurs prior to the
onsite inspection week.
The inspection will include a bagman trip to support selection of components and 2 weeks of
onsite inspection. The inspection team will consist of 3 NRC inspectors. The current inspection
schedule is as follows:
Bagman trip onsite week:
February 19, 2018
Team preparation week:
April 16-20, 2018
Onsite inspection weeks:
April 23-27, 2018, and May 7-11, 2018.
Experience with previous baseline design inspections of similar depth and length has shown
that this type of inspection is extremely resource intensive, both for the NRC inspectors and the
licensee staff. In order to minimize the inspection impact on the site and to ensure a productive
inspection for both parties, we have enclosed a request for information needed for the
inspection.
It is important that all of these documents are up-to-date and complete in order to minimize the
number of additional documents requested during the preparation and/or the onsite portions of
the inspection. Insofar as possible, this information should be provided electronically to the lead
inspector. The information request has been divided into four groups:
D. Curtland
-2-
The first group lists information necessary for our initial inspection scoping activities.
This information should be provided to the lead inspector no later than January 5, 2018.
Prior to the bagman trip on January 19, 2018, the lead inspector will communicate the
initial selected set of approximately 12 EQ components.
The second group of documents requested is those items needed to support the
bagman trip. This set of documents should be available to the lead inspector onsite
on February 19, 2018.
The third group of documents requested is those items needed to support our
in-office preparation activities for the selected set of 6-9 EQ components. This set of
documents should be provided to the lead inspector at the Regional Office no later than
April 5, 2018. During the in-office preparation activities, the team may identify additional
information needed to support the inspection.
The last group includes the additional information above as well as plant specific
reference material. This information should be available to the team onsite on
April 23, 2018. It is also requested that corrective action documents and/or questions
developed during the inspection be provided to the lead inspector as the documents
are generated.
The lead inspector for this inspection is Mr. Néstor J. Féliz Adorno. We understand that our
licensing contact for this inspection is Mr. B. Murrell of your organization. If there are any
questions about the inspection or the material requested in the enclosure, please contact the
lead inspector at (630) 829-9739 or via e-mail at Nestor.Feliz-Adorno@nrc.gov.
This letter does not contain new or amended information collection requirements subject
to the Paperwork Reduction Act of 1995 (44 U.S.C. 3501 et seq.). Existing information
collection requirements were approved by the Office of Management and Budget, Control
Number 3150-0011. The NRC may not conduct or sponsor, and a person is not required to
respond to, a request for information or an information collection requirement unless the
requesting document displays a currently valid Office of Management and Budget Control
Number.
This letter and its enclosure will be made available for public inspection and copying at
http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in
accordance with 10 CFR 2.390, Public Inspections, Exemptions, Requests for Withholding.
Sincerely,
/RA Michael Jones Acting for/
Néstor J. Féliz Adorno, Senior Reactor Inspector
Engineering Branch 3
Division of Reactor Safety
Docket No. 50-331
License No. DPR-49
Enclosure:
Document Request for Design Bases
Assurance Inspection EQ Program
cc: Distribution via LISTSERV
D. Curtland
-3-
Letter to Dean Curtland from Néstor J. Féliz Adorno dated November 21, 2017
SUBJECT: DUANE ARNOLD ENERGY CENTERREQUEST FOR INFORMATION
FOR AN NRC DESIGN BASES ASSURANCE INSPECTION (PROGRAM):
IMPLEMENTATION OF THE ENVIRONMENTAL QUALIFICATION PROGRAM;
INSPECTION REPORT 05000331/2018010
DISTRIBUTION:
RidsNrrDorlLpl3
RidsNrrPMDuaneArnold Resource
RidsNrrDirsIrib Resource
Cynthia Pederson
Kenneth OBrien
DRPIII
DRSIII
ADAMS Accession Number ML17326A691
OFFICE
RIII
RIII
RIII
RIII
NAME
MJones for NFeliz-
Adorno:cl
DATE
11/21/17
OFFICIAL RECORD COPY
DOCUMENT REQUEST FOR DESIGN BASES ASSURANCE INSPECTION EQ PROGRAM
Enclosure
Inspection Report: 05000331/2018010
Bagman Dates:
February 19, 2018
Inspection Dates:
April 23-27, 2018, and May 7-11, 2018
Inspection Procedure:
IP 71111.21N, Design Bases Assurance Inspection (Program),
Attachment 1, Environmental Qualification (EQ) under 10 CFR
50.49 Programs, Processes, and Procedures
Lead Inspector:
Néstor J. Féliz Adorno, Senior Reactor Inspector, DRS
630-829-9810
Nestor.Feliz-Adorno@nrc.gov
I.
Information Requested Prior to the Onsite Information Gathering/Bagman Week
The following information is requested by January 5, 2018, or sooner, to facilitate
inspection preparation. If you have any questions regarding this information, please call
the team leader as soon as possible. Please provide the information electronically in
pdf files, Excel, or other searchable formats, preferably on some portable electronic
media (e.g., CD-ROM, DVD, etc.). The portable electronic media should contain
descriptive names, and be indexed and hyperlinked to facilitate ease of use. Information
in lists should contain enough information to be easily understood by someone who
has knowledge of light water reactor technology.
1.
Risk-ranking of top 250 components required to meet environmental
qualifications (EQ) from your site specific probabilistic safety analysis
sorted by Fussell Vesely Importance.
2.
Probabilistic Safety Analysis listing of top ten risk significant systems.
3.
U.S. Nuclear Regulatory Commission Safety Evaluation Report(s) associated
with EQ.
4.
Electronic copies of Updated Final Safety Analysis Report, Technical
Specifications, and Technical Specifications Bases. Specifically identify which
Updated Final Safety Analysis Report sections address EQ (including seismic).
5.
Identify the various EQ standards (including year, edition, or revision) that the
station is committed to.
6.
Site (and corporate, if applicable) procedures associated with the Title 10 of the
Code of Federal Regulations, Part 50.49, EQ Program for electrical components.
Include procedures for procurement of qualified equipment, maintenance of
qualified equipment, modification to qualified equipment (including Equivalency
or Commercial Grade Dedication (CGD) Programs), and material storage and
shelf life controls.
DOCUMENT REQUEST FOR DESIGN BASES ASSURANCE INSPECTION EQ PROGRAM
2
7.
Copy of EQ Design Basis Document, if applicable.
8.
Copy of any open licensing commitments related to EQ, if applicable.
9.
Equipment Qualification Master List. Specific issues to be identified include:
safety classification (safety-related or nonsafety-related), Regulatory Guide 1.97
instrumentation, EQ qualification (e.g., DOR, NUREG 588, 50.49), original or
replaced after implementation of 50.49, and plant location.
10.
List of any installed equipment removed from the Equipment Qualification Master
List and basis for removal.
11.
List of EQ solenoid valves that are normally continuously energized.
12.
List or drawings of plant areas that are subjected to EQ, identifying design
(limiting) temperature, both normal and accident, high energy line break,
radiation levels, etc. that the associated equipment will have to be qualified to
meet EQ. If unit has obtained a power uprate (greater than 5 percent) provide
same information pre-update (earliest available if multiple uprates).
13.
List of CGD evaluations performed, for which the dedicated parts have been
issued for installation (parts issued for the last 10 years) on EQ applications in
the plant. Include CGD evaluation number, name of part, component ID or
description of the component the part was issued to repair, work order, and date
issued or installed.
14.
List of Corrective Action Documents related to the EQ program or EQ of specific
components for the last 5 years.
15.
Current management and engineering organizational chart.
II.
Information Requested (for the approximate 9-12 selected components) to be
Available by the Bagman Trip on February 19, 2018.
1.
EQ summary report for each component/subcomponent.
2.
Qualification Maintenance Requirement Sheet or equivalent.
3.
List of corrective action documents associated with each of the selected
components for the last 5 years.
4.
Photos of any component in containment or high radiation areas, if available.
III.
Information Requested (for the approximate 6-9 selected components) to be
Available by April 5, 2018.
This information should be separated for each selected component, especially if
provided electronically (e.g., folder with component name that includes EQ files,
Qualification Test Reports, calculations, corrective action documents, maintenance
history, etc.).
1.
EQ file, including associated Qualification Test Reports.
DOCUMENT REQUEST FOR DESIGN BASES ASSURANCE INSPECTION EQ PROGRAM
3
2.
Vendor manual (electronic copy or availability of hard copy during inspection).
3.
Preventive maintenance template.
4.
Last performed work order (WO) for each associated EQ preventive
maintenance.
5.
List of corrective maintenance WOs for the last 10 years. Include WO number,
date performed, and brief one line description.
6.
If repair work (e.g., a motor rewind) was performed under a purchase order,
provide copy of the purchase order.
7.
Thermal life calculation.
8.
Any self-assessments of the EQ program in the last 3 years.
IV.
Additional Information to be Provided on April 23, 2018, Onsite
1.
During the in-office preparation activities, the team may identify additional
information needed to support the inspection. The lead inspector will provide a
list of the additional information needed during the week of April 16, 2018.
V.
Information Requested to be Provided Throughout the Inspection
1.
Copies of any corrective action documents generated as a result of the teams
questions or queries during this inspection.
2.
Copies of the list of questions submitted by the team members and the
status/resolution of the information requested (provide daily by 2:30 p.m.
during the inspection to each team member).
If you have questions regarding the information requested, please contact the lead inspector.