Requests Exemption from 10CFR50,App A,Gdc 2 to Relieve Emergency Diesel Generator Combustion Air Intake Piping, Exhaust Piping & Supply Ventilation of Requirement to Withstand Effects of Tornado
ML17325B434
Person / Time
Site: Cook  
Issue date: 07/19/1991
From: Fitzpatrick E
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To: Murley T
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
AEP:NRC:1155A, NUDOCS 9107290134
Download: ML17325B434 (6)


Text

ACCELERATED DI UTION DEMONS TION SYSTEM REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)

DOCKET 05000315 05000316

SUBJECT:

Requests exemption from 10CFR50,App A,GDC 2 to relieve emergency diesel generator combustion air intake piping, exhaust piping

& supply ventilation of requirement to withstand effects of tornado.

DISTRIBUTION CODE:

A001D COPIES RECEIVED:LTR ENCL SIZE:

TITLE: OR Submittal:

General Distribution NOTES:

ACCESSION NBR: 9107290134 DOC. DATE: 91/07/19 NOTARIZED-NO FACIL:50-315 Donald C.

Cook Nuclear Power Plant, Unit 1, Indiana 50-316 Donald C.

Cook Nuclear Power Plant, Unit 2, Indiana AUTH.NAME AUTHOR AFFILIATION FITZPATRICK,E.

Indiana Michigan Power Co.

(formerly Indiana

& Michigan Ele RECIP.NAME RECIPIENT AFFILIATION MURLEY,T.E.

Document Control Branch (Document Control Desk)

RECIPIENT ID CODE/NAME PD3-1 LA

,/

COLBURN,T.

INTERNAL: NRR/DET/ECMB 7D NRR/DOEA/OTSB11 NRR/DST/SELB 7E NRR/DST/SRXB 8E OC LFMB G=

E 01 EXTERNAL:

RC PDR COPIES LTTR ENCL 1

1 2

2 1

1 1

1 1

1 1

1 1

0 1

1 1

1 RECIPIENT ID CODE/NAME PD3-1 PD NRR/DET/ESGB NRR/DST 8E2 NRR/DST/SICB8H7 NUDOCS-ABSTRACT OGC/HDS2 RES/DSIR/EIB NSIC COPIES LTTR ENCL 1

1 1

1 1

1 1

1 1

1 1

0 1

1 1

1 S

R D

NOTE TO ALL"RIDS" RECIPIENTS:

D D

PLEASE HELP US TO REDUCE WASTE! CONTACT THE DOCUMENT CONTROL DESK, ROOM P 1-37 (EXT. 20079) TO ELIMINATEYOUR NAMEFROM DISTRIBUTION LISTS FOR DOCUMENTS YOU DON'T NEED!

TOTAL NUMBER OF COPIES REQUIRED:

LTTR 18 ENCL 16

indiana Michigan Power Company P.O. Box 16631 Columbus, OH 43216 AEP:NRC:1155A Donald C.

Cook Nuclear Plant Units 1 and 2

Docket Nos.

50-315 and 50-316 License Nos.

DPR-58 and DPR 74 REQUEST FOR 10CFR50.12A EXEMPTION FOR EMERGENCY DIESEL GENERATIONS U.

S. Nuclear Regulatory Commission Attn:

Document Control Desk Washington, D.

C.

20555 Attn:

T.

E. Murley July 19, 1991

Dear Dr. Murley:

In accordance with the provisions of 10CFR50.12a, we hereby request exemption from the requirements of 10CFR50 Appendix A General Design Criterion 2.

Exem tion Re uest This exemption willrelieve, in part, the requirement for equipment important to safety to withstand the effects of natural phenomena.

In particular, the exemption will relieve the emergency diesel generator (EDG) combustion air intake piping, exhaust piping, and EDG supply ventilation of the requirement to be able to withstand the effects of a tornado.

This exemption is requested through August 17, 1991.

Details of the circumstances surrounding this request, compensatory actions to be

taken, evaluation of safety significance, justification for the duration of the request, significant hazards considerations, and environmental consequences review are provided in the attached letter AEP:NRC:1155, dated July 18, 1991.

This letter requested a

temporary waiver of compliance, which was granted verbally by your staff on July 18, 1991.

Upon determination that the plant was not in compliance, compensatory actions such as opening selected doors were implemented to provide tornado vacuum protection.

In additon, 9i07290134 9i07i9

PDRs, ADOCK 05000315 P

PDR

Dr. T.

E. Murley AEP:NRC:1155A methods for modifying the EDG appurtenances for wind loadings, that will bring the plant into compliance, have been identified, and willbe implemented, prior to expiration of this exemption request.

These completed and pending compensatory actions are described in the attached letter.

10CFR50.12(a)(2)(v) allows the NRC to grant an exemption request if the exemption would provide only temporary relief from the applicable regulation and the licensee has made good faith efforts to comply with the regulation.

Since the exemption request is to expire on August 17, and since compensatory actions have been and will be taken, we believe the requested exemption is within the scope of 10CFR50.12.

This document has been prepared following Corporate procedures that incorporate a reasonable set of controls to ensure its accuracy and completeness prior to signature by the undersigned.

Sincerely, Vice President eh cc:

D. H. Williams, Jr.

A. A. Blind - Bridgman J.

R. Padgett G. Charnoff NFEM Section Chief A. B. Davis - Region III NRC Resident Inspector

- Bridgman

ATTACHMENT TO AEP:NRC:1155A LETTER AEP:NRC:1155 DATED JULY 18, 1991