Application for Amends to Licenses DPR-58 & DPR-74,changing Tech Spec 3/4.4.5, Steam Generators, to Clarify Requirements for Steam Generator Tube Integrity.Fee Paid
ML17324B134
Person / Time
Site: Cook  American Electric Power icon.png
Issue date: 11/13/1986
From: Alexich M
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To: Harold Denton
Office of Nuclear Reactor Regulation
Shared Package
ML17324B135 List:
References
AEP:NRC:0936D, AEP:NRC:936D, NUDOCS 8611180250
Download: ML17324B134 (9)


Text

REGULATORY

-ORl1ATION DISTRIBUTION SYS

( R I DS )

ACCESSION NBR-'611180250 DOC. DATE: 86/11/13 NOTARIZED:

NO DOCKET FACIL: 50-315 Donald C.

Cook Nuclear Power Planti Unit 1> Indiana 5

05000315 50-316 Donald C.

Cool Nuclear Power Planti Unit 2.

Ind iana 0

05000316 AUTH. NANE AUTHOR AFFILIATION ALEXICH,N. P.

Indiana 8r Nichigan Electric Co.

RECIP. NANE RECIPIENT AFFILIATION DENTONp H. R.

Office oF Nuclear Reactor Regulationi Director (post 851125

SUBJECT:

Application for amend to Licenses DPR-58 8c DPR-74> changing Tech Spec 3/4. 4. Si "Steam Generators" to clarifg requirements for steam generator tube integritg.

DISTRIBUTION CODE:

A058D COPIES RECEIVED: LTR ENCL SI ZE:

TITLE: OR/Licensing/Generic Submittal:

Steam Generator ube Integritg (Water NOTES:

RECIPIENT ID CODE/NANE PWR-A ADTS PWR-A EICSB PWR-A PD4 LA WIQQINQTON D PWR-A RSB INTERNAL IE DIR NRR PWR-A ADTS NRR/DSRO/EIB COP IES LTTR ENCL 1

2 2

1 1

1 1

1 1

1 RECIPIENT ID CODE/NANE PWR-A EB PWR-A FOB PWR-A PD4 PD PWR-A PSB NRR BWR *DTS

-B *DTS REG FIL 01 COPIES LTTR ENCL 1

1 1

1 1

1 1

1 1

1 EXTERNAL: LPDR NSIC 2

2 1

NRC PDR 1

1 TOTAL NUNBER OF COPIES REQUIRED:

LTTR 20 ENCL 20

t

~r I

~

t l,

I~

t N,

, N 4

INDIANA 8 MICHIGAN ELECTRIC COMPAN Y P.O. BOX 16631 COLUMBUS, OHIO 43216 November 13, 1986 AEP:NRC:0936D Donald C.

Cook Nuclear Plant Unit Nos.

1 and 2

Docket Nos.

50-315 and 50-316 License Nos.

DPR-58 and DPR-74 STEAM GENERATOR TUBE INTEGRITY TECHNICAL SPECIFICATIONS CHANGE REQUEST Mr. Harold R. Denton, Director Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Washington, D.C.

20555

Dear Mr. Denton:

This letter and its attachments constitute an application for amendment to the Technical Specifications (T/Ss) for the Donald C.

Cook Nuclear Plant Unit Nos.

1 and 2.

Specifically we are proposing a change to T/Ss 3/4.4.5, Steam Generators, to clarify that the requirements are for steam generator tube integrity.

The reasons for the proposed change and our analysis concerning significant hazards considerations are contained in Attachment 1 to this letter.

The proposed revised Technical Specification pages are contained in Attachment 2.

We believe that the proposed change will not result in (1) a significant change in the types of effluents or a significant increase in the amounts of any effluent that may be released offsite, or (2) a significant increase in individual or cumulative occupational radiation exposure.

These proposed changes have been reviewed by the Plant Nuclear Safety Review Committee (PNSRC) and will be reviewed by the Nuclear Safety and Design Review Committee (NSDRC) at their next regularly scheduled meeting.

In compliance with the requirements of 10 CFR 50.91(b)(1),

copies of this letter and its attachments have been transmitted to Mr. R.

C. Callen of the Michigan Public Service Commission and Mr. G.

Bruchmann of the Michigan Department of Public Health.

Pursuant to 10 CFR 170.12(c),

we have enclosed an application fee of

$150.00 for the proposed amendments.

if.3 eoR

~O agii18 ocg 0500 oaso e~~iosis P-iM@g~&.00

p)

Mr. Harold R. Denton AEP:NRC:0936D This document has been prepared following Corporate procedures which incorporate a reasonable set of controls to insure its accuracy and completeness pri.or to signature by the undersigned.

Very truly yours, f

M.

Q. Ale ich g,C ice esx en 0)g cm Attachments cc'.

John E. Dolan W.

G. Smith, Jr.

- Bridgman G. Bruchmann R.

C. Callen G. Charnoff NRC Resident Inspector

- Bridgman

ATTACHMENT 1 TO AEP:NRC:0936D REASONS AND 10 CFR 50.92 ANALYSIS FOR CHANGE TO THE DONALD C.

COOK NUCLEAR PLANT UNIT NOS.

1 AND 2 TECHNICAL SPECIFICATIONS

a II

Attachment to AEP:NRC:0936D Page 1

In recent discussions with NRC staff, a discrepancy was brought to our attention concerning T/S requirements for steam generators, specifically T/S 3/4.4.5.

The Bases section to this T/S clearly states that the purpose of the T/S and associated surveillance requirements is to maintain the structural integrity of the steam generator tubes.

The current T/S,

however, addresses only the operability of the steam generator.

We believe the scope of the steam generator operability includes steam generator tube integrity, but we agree with the NRC staff that this should be stated explicitly.

We propose the following changes 1.

Retitle the section beginning on page 3/4 4-7 "Steam Generator Tube Integrity."

The corresponding Bases section is also retitled.

2.

Change the Limiting Condition for Operation 3.4.5 to "The tube integrity of each steam generator shall be maintained."

Change the "Action" on page 3/4 4-7 to read:

"With the tube integrity of one or more steam generators not maintained, restore the tube integrity of the affected steam generator(s) prior to increasing T

above 200 F."

avg In T/Ss 4.4.5.0, 4.4.5.1 and 4.4.5.4.b, delete the word "OPERABLE" and insert the phrase "The tube integrity of."

5.

In Table 4.4-1, Notation 2, page 3/4 4-12, change the words "Each of the other two" to "the third and fourth" and add the word "respectively" for clarity.

As stated

above, we believe the scope of the current T/S includes steam generator tube integrity.

Steam generator operability, which is deleted from this T/S, is addressed in T/S 3/4.4.1 (Reactor Coolant Loops and Coolant Circulation).

These changes do not affect the requirements of T/S 3/4.4.1.

Therefore we believe these changes are administrative and merely clarify the'intent of T/S 3/4.4.5.

Per 10 CFR 50.92, a proposed amendment will not involve a significant hazards consideration if the proposed amendment does not:

(1) involve a significant increase in the probability or consequences of an accident previously evaluated, (2) create the possibility of a new or different kind of accident from any accident previously analyzed or evaluated, or (3) involve a significant reduction in a margin of safety.

Criterion. 1 The changes proposed in this letter will clarify the intent of the T/S but will not impact plant components or systems.

Therefore we believe these changes will not involve a significant increase in the probability or consequences of a previously evaluated accident.

Attachment to AEP:NRC:0936D Page 2

Criterion 2

These changes are purely administrative in nature.

The plant systems, components and operation will not be altered by these changes.

Therefore we believe this change will not create the possibility of a new or different kind of accident than has previously been analyzed or evaluated.

Criterion 3

Since these changes are administrative in nature, they will not impact the ability of plant systems and components to perform their safety function.

Therefore we believe these changes will not involve a significant reduction in a margin of safety.

The Commission has provided guidance concerning the determination of significant hazards by providing certain examples (48 FR 14780) of amendments considered not likely to involve a significant hazards consideration.

The first example is that of a purely administrative change to the T/Ss:

for example, a change to achieve consistency throughout the T/Ss, correction of an error, or a change in nomenclature.

We believe that the changes requested in this letter are of the type specified in the example.

Since these changes are administrative in nature, they do not reduce a margin of safety, do not increase the probability or consequences of a previously analyzed accident, and do'ot introduce the possibility of a new accident.

Therefore, we believe these changes do not involve a significant hazards consideration as defined by 10 CFR 50.92.

We request that the title of the Bases Section 3/4.4.5 be changed to correspond to the change in title of T/S 3/4.4.5.

In addition, we would like to add the following statement to T/S Bases 3/4.4.5:

"In MODES 1, 2,

3 and 4 the tube integrity of the steam generators shall be considered maintained if the primary-to-secondary leakage rate is within the limits of Specification 3.4.6.2."

This statement clarifies the intent of the change in nomenclature and better defines the term "tube integrity."