Amends 97 & 84 to Licenses DPR-58 & DPR-74,respectively, Changing Tech Specs Re Automatic Actuation of Control Room Charcoal Filter Fire Protection Sys to Manual Actuation
ML17324A976
Person / Time
Site: Cook  
Issue date: 06/30/1986
From: Youngblood B
Office of Nuclear Reactor Regulation
To:
Shared Package
ML17324A977 List:
References
NUDOCS 8607100090
Download: ML17324A976 (11)


Text

, ~

gpss RECT O~

0O C

Cy

+

~O

+>>*<<+

UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 INDIANA AND MICHIGAN ELECTRIC COMPANY DOCKET NO. 50-315 DONALD C.

COOK NUCLEAR PLANT UNIT NO. I AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.

97 License No. DPR-58 1.

The Nuclear Regulatory Comission (the Comission) has found that:

The application for amendment by Indiana and Michigan Electric Company (the licensee) dated March 14, 1986, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Comission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compl.iance with the Comission's regulations; D.

The issuance of this amendment will not be inimical to the comon defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and Paragraph 2.C.(2) of Facility Operating License No.

DPR-58 is hereby amended to read as follows:

Bb07100090 860630 PDR ADOCK 05000315 P

PDR

(2)

Technical S ecifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No.

97, are hereby incorporated in the license.

The licensee shall operate the facility in accordance with the Technical Specifications.

(3)

The change in Technical Specifications is to become effective within 60 days of issuance of the amendment.

In the period between issuance of the amendment and the effective date of the new Technical Specifi-

cations, the licensee shall adhere to the Technical Specifications for the systems, components, or operation existing at the time.

The period of time during changeover of systems, components or operation shall be minimized or compensated for by suitable temporary alternatives.

(4)

This license amendment is effective as of the date of its issuance.

FOR THE NUCLEAR REGULATORY COMMISSION I'ttachment:

Changes,to 'the Technical Specifications Date of Issuance:

June 30, 1986 B. J.

Youngblood, Director PWR Project Directorate ¹4 Division of PWR Licensing-A, NRR PWR¹4:DPWR-A DWig inton:mac 06/

/86 PW

'WR-A M

c 06/

/86 OELD 06/P,

/86 PWR¹4:DPWR-A BJYoungblood 06/ g'a/86

I I

A m

I t

gy,ll RECy C0O IA I

Op Yr+

gO

++*++

t UNITED STATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 INDIANA AND MICHIGAN ELECTRIC COMPANY DOCKET NO. 50-316 DONALD C.

COOK NUCLEAR PLANT UNIT NO.

2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.

84 License No.

DPR-74 1.

The Nuclear Regulatory Commission (the Commission) has found that:

A.

The application for amendment by Indiana and Michigan Electric Company (the licensee) dated March 14, 1986 complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.

There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and Paragraph 2.C.(2) of Facility Operating License No.

DPR-74 is hereby amended to read as follows:

(2)

Technical S ecifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No.

84

, are hereby incorporated in the license.

The licensee shall operate the facility in accordance with the Technical Specifications.

(3)

The change in Technical Specifications is to become effective within 60 days of issuance of the amendment.

In the period between issuance of the amendment and the effective date of the new Technical Specifi-

cations, the licensee shall adhere to the Technical Specifications for the systems, components, or operation existing at the time.

The period of time during changeover of systems, components or operations shall be minimized or compensated for by suitable temporary alternatives.

(4)

This license amendment is effective as of the date of its issuance FOR THE NUCLEAR REGULATORY COMMISSION

Attachment:

Changes to the Technical Specifications Date of Issuance:

JUne 30, 1986 B. J.

Youngblood, Director PWR Project Directorate ¹4 Division of PWR Licensing-A, NRR PWR¹4.DPWR-'

DWi ginton:rad 06

/86 PW 4'WR-A '

n 06/

/86 OEL~

06/ 5/86 PWR¹4:DPWR-A BJYoungblood 06/3o/86

II I

1 jI

ATTACHMENT TO LICENSE AMENDMENTS AMENDMENT NO.

97 fACILITY OP'ERATING LICENSE NO. DPR-58 AMENDMENT NO.

84 FACILITY OPERATING LICENSE NO.

DPR-74 DOCKET NOS.

50-315 AND 50-316 Revise Appendix A as follows:

Remove Pa es Unit 1 3/4. 7-46 B 3/4 7-8 Unit 2 3/4 7-41 B 3/4 7-7 Insert Pa es 3/4 7-46 B 3/4 7-8 3/4 7-41 B 3/4 7-7

~

~

J

~

~

TABLE 3'-5 SPRAY AND/OR SPRINKLER SYSTEMS A

OPEN HEAD DELUGE TYPE WATER SYSTEMS LOCATION ACTUATION 1-HV-AES-1, Charcoal Filters 1-HV-AES-2 Charcoal Filters 12-HV-AFX Charcoal,Filters*

1-HV-CPR-1 Charcoal Filters 1-HV-CIPX-1 Charcoal Filters 1-HV-ACRF-1 Charcoal Filters Manual a Electric-heat Manual

& Electric-heat Manual 6 Electric-heat Manual 6 Electric-heat Manual 8 Electric-heat Manual a Electric-heat B.

CLOSED HEAD SPRINKLER TYPE WATER SYSTEMS LOCATION Auxiliary Bldg. Cask Handling Area*

TYPE SYSTEM Preaction Sprinkler ACTUATION Dry Pilot Auxiliary Bldg. Drumming Area*

Auxiliary Bldg. Elev.

587<<

609<< (Corridors, charging, safety Inj. pump rooms, laundry area)

Reactor Coolant Pumps (4)

Preaction Sprinkler Preaction Sprinkler Preaction Sprinkler Dry Pilot Dry Pi)ot Manual

<<Shared system with D. C.

COOK UNIT 2.

D. C.

COOK - UNIT 1 3/4 7-46 Amendment No.

97

BASES 3/4.7.9 Cont.

The purpose of the charcoal filter fire suppression T/S is to account for detection and suppression of fires in the charcoal filters.

Manual operation of these systems is allowed because two-plaint heat detection with control room and local annunciation of trouble conditions is provided for the charcoal filters.

The OPERABILITY of the fire suppression system protecting the charcoal filters is only required when there is charcoal in the filters.

Actuation of spray water onto'he charcoal filters requires both the manual opening of the system isolation'valve and reaching the high temperature alarm setpoint for the automatic opening of the system deluge valve.

Because of the inaccessibility of the lower containment to personnel during operation due to ALARA radiation exposure

concerns, the use of one or more CCTVs in the lower containment, to monitor for fire and smoke, is an acceptable substitute to an hourly fire watch, if the fire suppression system becomes inoperable.

3/4.7.10 FIRE RATED ASSEMBLIES The OPERABILITY of the fire barriers and barrier penetrations ensures that fire damage will be limited.

These design features minimize the possibility of a single fire involving more than one fire area prior to detection and extinguishment.

The fire barriers, fire barrier penetrations for conduits, cable trays and piping, fire dampers, and fire doors are periodically.inspected to verify their OPERABILITY.

The ventilation seals are seals around ventilation duct work penetrating fire barriers.

D. C.

COOK - UNIT 1 B 3/4 7-8 Amendment No.

97

TABLE 3.7-5 SPRAY AND/OR SPRINKLER SYSTEMS A.

OPEN HEAD DELUGE TYPE WATER SYSTEMS LOCATION ACTUATION 2-HV-AES-1 Charcoal Filters 2-HV-AES-2 Charcoal Filters 12-HV-AFX Charcoal Zilters*

2-HV-CPR-1 Charcoal Filters 2-HV-CIPX-1 Charcoal Filters 2-HV-ACRF-1 Charcoal Filters Manual 6 Electric-heat Manual s Electric-heat Manual 6 Electric-heat Manual s Electric-heat Manual s Electric-heat Manual s Electric-heat B

CLOSED HEAD SPRINKLER TYPE WATER SYSTEMS LOCATION Auxiliary Bldg. Cask Handling Area*

TYPE SYSTEM Preaction Sprinkler ACTUATION Dry Pilot Auxiliary Bldg. Elev. 587* 6 609* (Corridors, charging, safety Znj. pump rooms, laundry area)

Preaction Sprinkler Auxiliary Bldg. Drumming Area*

Preaction Sprinkler Dry Pilot Dry Pilot Reactor Coolant Pumps (4)

Preaction Sprinkler Manual

  • Shared system with D. C.

COOK - UNIT 1.

D. C.

COOK - UNIT 2 3/4 7-41 Amendment No.

84

PLANT SYSTEMS BASES other tasks (e.g.,

an operator on tour) provided that such personnel fulfilled the above stated requirements.

As a. minimum, each area affected by an isolated low pressure CO system must be visited every twenty-five (25) to thirty-five (35) minutes by the Roving Fire Natch Patrol.

Such measures will provide the necessary level of fire protection while affording necessary provisions for personnel safety.

In the event that portions of the fire suppression systems are inoperable, alternate backup fire fighting equipment is required to be made available in the affected areas until the inoperable equipment is restored to service.

When the inoperable fire-fighting equipment is intended for use as a

backup means of fire suppression, a longer period of time is allowed to provide an alternate means of fire fighting than if the inoperable equipment is the primary means of Cire suppression.

The surveillance requirements provide assurance that the minimum OPERABILITY requirements of the fire suppression systems are met.

An allowance is made for ensuring a sufficient volume of Halon and CO in the storage tanks by verifying either the weight, level, or pressure ok the tanks.

Zn the event the fire suppression water system becomes inoperable, immediate corrective measures must be taken since this system provides the major fire suppression capability of the planti The requirement for a twenty-four hour report to the Commission provides for prompt evaluation of the acceptability of the corrective measures to provide adequate fire suppression capability for the continued protection of the nuclear plant.

The purpose of the charcoal filter fire suppression T/S is to account for detection and suppression of fires in the charcoal filters.

Manual operation of these systems is allowed because two-point heat detection with control room and local annunciation of trouble conditions is provided for the charcoal filters.

The OPERABILITY of the fire suppression system protecting the charcoal filters.is only required when there is charcoal in the filters.

Actuation of spray water onto the charcoal filters requires both the manual opening of the system isolation valve and reaching the high temperature alarm setpoint for the automatic opening of the system deluge valve.

Because of the inaccessibility of the lower containment to personnel during operation due to ALARA radiation exposure

concerns, the use of one or more CCTVS in the lower containment to monitor for fire and smoke, is an acceptable substitute to a continuous fire watch, if the fire suppression system becomes inoperable.

3/4.7.10 FIRE RATED ASSEMBLIES The OPERABILITY of the fire barriers and barrier penetrations ensures that fire damage will be limited.

These design features minimize the possibility of a single fire involving more than one fire area prior to detection and extinguishment.

The fire barriers, fire barzier penetrations for conduits, cable trays and piping, fixe dampezs, and fire doors are periodically inspected to verify their OpERABZLITY.

The ventilation seals are seals around ventilation duct work penetrating fire barriers.

D C.

COOK - UNIT 2 B 3/4 7-7 Amendment No.

84