Speech Entitled Fog Inerting Criteria for Hydrogen/Air Mixtures, Presented at 821003-07 Second Intl Workshop on Impact of Hydrogen on Water Reactor Safety in Albuquerque, Nm
ML17320A793
Person / Time
Site: Cook 
Issue date: 10/03/1982
From: Liparulo N, Tsai S
WESTINGHOUSE ELECTRIC COMPANY, DIV OF CBS CORP.
To:
Shared Package
ML17320A792 List:
References
2693Q:1, NUDOCS 8310140046
Download: ML17320A793 (24)


Text

FOG INERTING CRITERIA FOR HYOROGEN/AIR MIXTURES S. S. Tsai, and N. J. Liparulo Risk Assessment Technology Westinghouse Electric Corporation Presented at Second International Workshop on the Impact of f{ydrogen on Water Reactor Safety Albuquerque, New Mexico October 3-7, 1982

(

83i0140046 831010 l

PDR ADOCK 05000315 P

PDR 2693/:1

FOG INERTIHG CRITERIA FOR HYDROGEN/AIR MIXTURES S. S. Tsai, and N. J. Liparulo Risk Assessment Technology Mestinghouse Electric Corporation ABSTRACT A distributed ignition system has been proposed to ignite hydrogen at low concentration in the ice condenser containment during severe accidents.

The post-accident containment atmosphere could be misty due to fog generation from the break flow and condensation in the ice bed.

Thus it is important to establish a fog inerting criterion for effective performance o'f the ignition system.

This paper presents such a

criterion that specifies the necessary fogging conditions, i.e., fog concentration and drop size, for inerting a hydrogen/air mixture.

The criterion shows that the minimum fog inerting concentration varies with the square of the volume mean fog drop size.

The present fog inerting criterion is shown to be in general agreement with the Factory Mutual test data.

1.

INTRODUCTION A distributed ignition system has been proposed to ignite hydrogen at low concentration in the ice condenser containment during severe acci-dents.

The post-accident containment atmosphere may be misty because of fog generation by the break flow and condensation in the ice bed.

Thus it is of important to establish a fog inerting criterion for effective performance of the ignition system.

Zalosh and Bajpai(>)

have recently conducted hydrogen flamaability tests to determine the effect of water fogging on the hydrogen lower flammability limit.

In the tests, the minimum fog inerting concentra-tions for various volume mean drop sizes and tpdrogen concentrations were measured.

It was found that an 8 vol percent hydrogen mixture could be inerted at high fog concentration.

Fog formation may also have been responsible for failure of the two Lawrence Livermore tests(2) at high steam concentrations to'gnite tpdrogen during the test vessel cool-down period.

The capability of fog droplets in., inhibiting combustion or quenching flames is due to their heat absorbing capability - high heat of vapor-ization and small drop sizes (on the order of 10 p).

Due to the small drop sizes, fog droplets could vaporize rapidly (on the order of mili-seconds) within a propagating flame front (" I mm thick). If a sub-stantial amount of these droplets are present, the flame may be quenched.

The critical droplet diameter for quenching a hydrogen flame has been estimated by Sandia National Laboratories(>).

It was assumed that the measured "quenching distance" for a hydrogen flame propagating through a

2693/:I

tube or between plates could be used for fog droplets.

This model does not consider heat transfer and combustion occurring between the burned gas and the suspended droplets.

This paper presents a fog inerting criterion that specifies the necessary fogging conditions, i.e., fog concentration and drop size, for inerting a hydrogen/air mixture.

2.

FOG INERTING CRITERIA Recent hydrogen burn experiments(2) conducted at Lawrence Livermore Laboratory indicated that substantial fog formation could occur when saturated steam is discharged into an unheated vessel.

It appeared that this fog prevented a glow plug igniter from successfully igniting the hydrogen mixture in the vessel.

The ability of fog in inhibiting and quenching a hydrogen combustion can be explained as follows.

The fog droplets suspended in the hydrogen-air-steam mixture act as a heat sink that could absorb a large amount of combustion heat by vaporization, greatly reducing the pressure and temperature rises resulting from hydrogen combustion.

If droplets are sufficiently small such that they could vaporize inside the thin (1mm) flame front, the flame may be quenched or inhibited.

For a flame speed of 2 m/s, the drop residence time is of the order of 0.5 x 1Q-3 seconds.(3)

In such a short period of time, the droplets of initial radius less than about 4

p will vaporize entirely in the flam'e front.

The quenching of a propagating flame is also governed by the distance between droplets.

As the droplets become closely packed, the tota1 droplet surface area available for energy loss increases.

A critical spacing between droplets exists such that a large fraction of the heat released is absorbed, Thus preventing.flame propagation.

This critical spacing is known as the "quenching distance",

which is usually determined by propagating flames in tubes.

2.1 PREVIOUS MORK The effectiveness of fog droplets in inhibiting or quenching a flame depends on its quenching distance, which was determined by Berman et al. (3) as q = L4V/Sjcrit where V is the gas volume and S is the heat transfer surface area.

In the suspended fog droplets, this volume-to-surface ratio (i.e.,

V/S) is equal to d (1-n)/6q, where d is the mean droplet diameter and q is the volume fraction of the droplets.

Mhen four times this ratio approaches the quenching distance, a critical droplet diameter can be obtained as nd c=Y ~q (2) 2693':I

Using the quenching distance data for a given volume fraction of water and gas composition, the critical droplet diameter can be determined from Equation (2).

The drop sizes less than the critical drop size are capable of quenching a flame.

2.2 PRESENT THEORY The previous theories do not model the heat transfer and combustion processes occurring between the burned 'gas and the suspended droplets.

A new theory has been developed, which models the heat loss and combustion within a thin flame front.

1 +.K!p l

where ei Consider a hydrogen/air/steam/mist droplets mixture in which a flame is propagating.

The flame may be divided into three zones:

heating

zone, reaction zone, and post-reaction zone as shown in Figure 1.

The unburned gas at temperature Tu moves in the reaction zone with the laminar burning velocity Su.

If the unburned gas density is pu, then the constant mass flow rate m is equal to puSu.

The unburned gas is heated to ignition temperature Ti and burned in the reaction zone to reach the flame temperature Tf.

The fog droplets will act as a heat sink that reduces the flame temperature.

The problem has been formulated and solved by von Karmani4).

In his formulation, three energy equations, which incorporate the heat loss terms, were written for the three zones described above.

The solution to these equations yields the following relationship 2KG.

1 - exp (- ~ p

) (Y - Yf) x f

t (3)

Ll+

1+ (4K/

)

]

x 1-u C

(Ti -T)/q p

i u

Kei (S/C') e.

p 1

, the ratio of heat loss rate per unit volume to 'the heat release rate by'chemical reaction per unit volume heat of combustion C

mean specific heat mean heat conductivity reaction rate (mass of fuel consumed per

unit time per unit volume)

II 2693/:I

hydrogen mass fraction in the heating zone "f

=

hydrogen mass fraction in the reaction zone

>uSu A plot of Eq.

(3) is shown in Figure 2.

It is seen that for a given

<oi, there is a minimum value of (Yu - Yf1/ei.

Below this minimum value, there is no solution for the e;.

Therefore, this value is considered as the flamsability limit.

At the flamsability limit, the value of Kel can be determined from Figure 2 or from Eq.

3 as (K) ite. =f((Y f

ei

\\

s A plot of (K)crit ei as a function of (Yu - Yf)/ei is shown in Figure 3.

Equation 4 may be expressed as 2

u f

Y Y

q p

uSu (Yu-Yf) f e;

d 2

12 i (Ti Tu)

(4)

(5)

Detailed derivation procedure for Eq.

(5) is given in Appendix A.

Using the data on Su from Reference (5) we can calculate the right hand side of Eq. (5) for a given composition and initial gas temperature.

3-VERIFICATION OF THEORIES BY EXPERIMENTS Experiments have been conducted at factory Mutual to study the effects of water fog density, droplet diameter, and temperature on the lower flaranability limit of hydrogen-air-steam mixtures(2).

The results indicated that most of the fog nozzles tested at 20 C only changed the limit from 4.03 volume percent to 4.76 percent, corresponding to fog concentration in the range of 0.028-0.085 volume percent, and volume mean drop size ranging from 45-90 microns.

For the 50 C case, the lower flammability limit increases to 7.2 percent, corresponding to 0.01-0.04 volume percent of fog and 20-50 micron volume mean drop sizes.

The results demonstrated that the fog inerting effect is more pronounced at reduced drop sizes and increased temperature.

Figures 4 through 6 show the comparison between the test data and the theoretical predictions.

For this comp'arison, the present theory used the free stream temperature to calculate the thermodynamic properties used in Equation (5).

This yielded somewhat higher fog concentrations than those calculated by use of the mean of the flame and free stream temperatures.

In Figures 4 and 5, the data suggests a linear relation-ship between the volume concentration and volume mean drop size on the log-log plot. It also suggests that the minimum fog inerting concentra-tion varies approximately with the square of the volume mean drop size.

2693Q:I

The present theory is in good agreement with the Factory Mutual data at 4.76 percent H2; however, it overpredicts the minimum fog inerting concentration at 7.2 percent H2.

The cause of this discrepancy is still unknown.

The discrepancy may be caused by the uncertainty of the data.

The following discussion supports this view.

The fog droplets are very small and they vaporize very fast in a flame.

Therefore, the fog droplets behave as steam except for their larger heat absorption capability.

@hen the fog droplets vaporize, they absorb the heat of vaporization which is much larger than the steam sensible heat.

Typically, the heat of vaporization of water is about 1000 Btu/lb and the average specific heat of steam in the temperature range of interest is about 0.48 Btu/lb. It is well known that a hydrogen flame cannot propagate in steam higher than about 64 percent in a steam-air mixture.

At 7.9 percent H2, the adiabatic flame temperature is about 1240 F and therefore the increase of the steam sensible heat is about 540 Btu/lb.

Consequently,.for the same amount of fog droplets and steam, the fog droplets heat absorption capability is about 1.9 times higher.

This means that the fog concentration which is equivalent to 22.1 percent steam in a steam-air mixture is capable of inerting 7.9 percent H2.

This fog inerti ng volumetric concentration was calculated to be 1.61 x

10-4 ft~ H20/ft3 mix for 7.9 percent H2.

To inert 7.2'ercent H2, a minimum fog concentration of 1.56 x 10-4 ft3 H20/ft3 mix, equivalent to about 21.3 percent steam in a steam-air mixture is required.

These estimates show that the present predictions are reasonable and conservative.

The estimates are consistent with Factory Mutual data on 7.9 percent H2 but not on 7.2 percent H2-Itshould be noted that in the tests three fog concentration measuring techniques were used.

These three techniques gave substantially dif-ferent results.

The discrepancy is at least one order of magnitude difference.

The fog concentration data presented in Figures 4 through 6

were obtained from one of the techniques.

In vie'w of the uncertainty of the data, care must be exercised in using them for fog i nerting analysis purposes.

They should be used in conjunction with the present fog inerting criterion in the assessment of fog inerting potential in the ice condenser plants.

Some uncertainty also exists in the present fog inerting theory.

The maximum uncertairity associated with the under-prediction of the heat loss and temperature dependence of the thermo-physical properties is estimated to be +63 percent.

4.

SUMMARY

AkD CONCLUSIOkS A fog inerting criterion has been developed to predict the minimum fog concentration required to inert a given hydrogen concentration and volume mean fog drop size.

The present fog inerting criterion has been shown to be in general agreement with the Factory Mutual test data.

The criterion shows that the minimum fog inerting concentration varies with the square of the volume mean fog drop size.

2693':I

ACKNOWLEDGMENTS The authors wish to express their sincere gratitude to Drs.

V. Srinivas, B. Lewis, and B. Karlovitz for assistance, suggestions, and helpful discussions, to Messrs.

D. F. Paddleford, R. 8ryan, F.

G. Hudson, D. Renfro, and K. Shiu for valuable comments.

They also would like to thank TYA, Duke Power, and AEP for providing the financial support.

REFERENCES 1.

R.

G. Zalosh and S.

N. Bajpai, "Mater Fog Inerting of Hydrogen - Air Mixtures,i", EPRI Project Preliminary Rpt. 1932-1, September, 1981.

2.

B. Lowry, "Preliminary Results:

A Study of Hydrogen Igniters, "ENN80-45, Lawrence Livermore National Laboratory, November 17, 1980.

3.

M. Berman, et al., "Analysis of f{ydrogen Mitigation for Degraded Core Accidents in the Sequoyah Nuclear Power Plant," Sandia draft

report, December 1, 1980.

4.

T. von Karman, unpublished

notes, 1956.

5.

S. S. Tsai, and N. D. Liparulo, "Flame Temperature Criteria Tests,"

accepted for presentation at the Second Int. Workshop on the Impact of Hydrogen on Mater Reactor Safety, Albuquerque, New Mexico, October 3-7, 1982.

2693/:1

\\>

APPEHDI X A DERIYATIOH OF EQUATIOH (5)

This appendix gives detailed procedures to derive Eq. (5), starting from Eq.

(4)

<<)cr;t <;

= f <<~u - ~f)/oj )

(4) where the ratio of heat. loss rate per unit volume to the heat release rate by chemical reaction per unit volume, (K)crit, is defined as Kcrit = S/Cpw (A-I) and the ratio of sensible heat to heat of combustion, ei, is defined as e;

= Cp (Ti - Tu)/q (A-2)

To arrive at Eq. (5), it is necessary to assume that all the heat loss is attributed to convection heat transfer to fog droplets of only one drop size.

Under this assumption, the rate of heat loss per unit volume per degree, S,

may be e'xpressed as S

= nxd2h (A-3) where n

=

number of drops per unit volume d

volume mean drop size h

=

heat transfer coefficient It is further assumed that the relative velocity between the droplets and the mixture flow is so small that heat transfer coefficient, h, can be approximated by the conduction limit.

In fact, it can be shown that for small drop sizes, convection and radiation are unimportant heat transfer mechanisms at the drop surface.

Under this assumption, Eq.

(A-3) reduces to 12'

=~

d (A-4) where 7

=

mean heat conductivi ty n

volume fraction of mist droplets (- i d

)

n 3

6 2693Q: I

The of heat generation per unit volume, w, is related to the laminar buring veloc>ty, Su, and the thickness of the reaction zone, x, by S

(Y Yf) w =

The thickness of the reaction zone may be approximated by pSZ'A-6)

Combining Eqs. (A-l), (A-4), (A-5), and (A-6), we have 12'

,SZ (Yu - Yf)

Substituting Eqs.

(A-2) and (A-7) into Eq. (4),

we have Yu-Yf d

127 (T. - T)

(Y -Y) f(u

)

1 u

1 (5)

Q.E.D.

2693Q:1

,B

4

FIGURE j SCHEMATIC REPRESENTATION OF TEMPERATURE PROFILE THROUGH THE FLAME FRONT 0'd,a%5 gsO30 0

2.

<~v~rV+i FIGURE 2 THE PARAMETER A.

p AS A FUNCTION OF (Y-Y~)/e.

FOR DIFFERENT VALUES OF K9.

0.3 0.2 0.i 3

(Yu Yfj/0/

FIGURE 3 (K) 8.

AT THE FLAMMABILITYLIMIT AS A FUNCTION OF (Y

- Yf)/8.

cr)t i

u f i

2147 3 10.1 7

5 x

2 PlI-10-2 P4 I-5 z0I-LL 2

Iz O

0 103 CJ U0tL 5

0 SPRACO 2163 SP RACO 1405-0604 Q

SP RAGO 2020-1704 0

SPRACO 1806-1605 NON-FLAMMABLEZONE BERMAN ET AL.

THEORY PRESENT THEORY FLAMMABLEZONE 104 10 100 200 VOLUMEMEAN DIAMETER (MICRONS)

Figure 4. Comparison between Theories and Factory Mutuai Fog inerting Experiments on 4.76 Percent H2 2147.$

0 SPRACO 2163-7604 D SPRACO 2020-1704 Q SONICORE 035H X

0 C4 FlI-ROI-lEI-R LuORO 2

C9O V

NON-FLAMM ABLE'ONE PRESENT THEORY FLAMMABLE ZONE 7.2% H2 IN AIR AT-50 C 10 20 30 40 50 60 70 80 90 100 VOLUMEMEAN DIAMETER (MICRONS)

Figure 5. Comparison between the Present Theory and Factory Mutual Fog lnerting Experiments on 7.2 Percent H2

V

2147.1 NON-FLAMMABLEZONE x

5X10 3 0

x R

10-3 I-I-z Ro 5X10.4 0O U0 PRESENT THEORY FLAMMABLEZONE 6 FACTORY MUTUALDATA ON 7.9% H2 IN AIR 104 50 100 VOLUMEMEAN DIAMETER (MICRONS) 1000 Figure 6. Comparison between the Present Theory and Factory Mutual Fog tnerting Experiments on 7.9 Percent H2 13

, ~