ggS IlE0(

~ +

~

0 Cy

-'~c

~f o

O I

3

%~*y4 WASHINGTON, D. C. 20555 820i1904i4 Sii228 POR ADQCK 05000315 P

PDR i

UNITEDSTATES t

NUCLEAR REGULATORY COMMISSION INDIANA AND MICHIGAN ELECTRIC COMPANY DOCKET NO. 50-315 DONALD C.

COOK NUCLEAR PL'ANT UNIT NO.

1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.

51 License No. DPR-58 1.

The Nuclear Regulatory CoIIIIission (the Comnission) has found that:

A.

The applications for amendment by Indiana and Michigan Electric Company (the licensee) dated December 17, 1979 and May 28, 1980 (as supplemented January 27, 1981}, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the applications, the provisions of the Act, and the rules and regulations of the Commission;

~

C.

There is reasonable assurance (i} that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii} that such activities will be conducted in compliance with the Commission's regulations; D,

The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

J II I

1,

$'yl 2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment,

.and paragraph 2.C.(2) of Facility Operating License No. DPR-58 is hereby amended to read as follows:

(2)

Technical S ecifications The Technical Specifications contained in Appendices A and B, as revised through Amendment No.

51

,'are hereby incor porated in the license.

The licensee shall operate the facility in accordance with the Technical Speci fications-3.

This license amendment is effective as of the date of its issuance.

FOR THE NUCLEAR R GULATORY COMMISSION

Attachment:

Changes to the Technical Specifications Cb Ch ven

&var)a, ie Operating Reactors Br gl Division of Licensing Date of Issuance:

December 28, 1981

ATTACHMENT TO LICENSE AMENDMENT AMENDMENT NO.

51 TO FACILITY OPERATING LICENSE NO.

DPR-58 DOCKET NO. 50-315 Revise Appendix A as follows:

Insert Pa e

3/4 8-16

ELECTRICAL POWER, SYSTEMS 3/4.8.3 Alternative A.C.

Power Sources LIMITING CONDITION FOR OPERATION 3.8.3. 1 The steady state bus voltage for the manual alternate reserve source*

shall be

> 90K of the nominal bus voltage.

APPLICABILITY:

Whenever the manual alternate reserve source (69 kY) is connected to more than two buses.

ACTION:

Nith bus voltage less than 90K nominal, adjust load on the remaining buses to maintain steady state bus voltage

> 90K limit.

SURVEILLANCE RE UIREMENTS 4.8 ~ 3.1 No additional surveillance requirements other than those required by Specifications 4.8.1.1.1 and 4.8.1.2.

"Shared with 0.

C.

'Cook Unit 2.

0.

C.

Cook Unit 1 3/4 8-16 Amendment No.

51

pe RECT

'~C

'p>>

~

0

+a*++

UNITEDSTATES NUCLEAR REGULATORY COMMISSION WASHINGTON, D. C. 20555 INDIANA AND MICHIGAN ELECTRIC COMPANY DOCKET NO. 50-316 DONALD C.

COOK NUCLEAR PLANT UNIT NO.

2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 36 License 'No.

DPR-?4 l.

The Nuclear Regulatory Comission (the Comission) has found that:

A.

B.

C.

D.

The applications for amendment by Indiana and Michigan Electric Company (the licensee) dated December 17, 1979 and May 28, 1980 (as supplemented January 27, 1981), complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter I; The facility will operate in conformity with the applications, the provisions of the Act, and the rules and regulations of the Commission; There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C. (2} of Facility Operating License No. DPR-74 is hereby amended to read as follows:

(2)

Technical S ecifications The Technical Specifications contained in Appendices A and 8, as revised through Amendment No. 36, are hereby incorporated in the license.

The licensee shall operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of the date of its issuance.

OR THE NUC EAR REGULATORY COMMISSION teven Q Var a, C i 0

Division of Licensin perat>ng Reactors nch 41

Attachment:

Changes to the Technical Specifications Date of Issuance:

December 28, 1981

ATTACHMENT TO LICENSE AMENDMENT AMENDMENT NO.

36 TO FACILITY OPERATING LICENSE NO.

DPR-74 DOCKET NO. 50-316 Revise Appendix A as follows:

Remove Pacee Insert Pa e

3/4 8-15

0

ELECTRICAL POMER SYSTEMS 3/4.8.3 Alternative A.C.

Power Sources LIMITING CONDITION FOR OPERATION 3.8.3. 1 The steady state bus voltage for the manual alternate reserve source" shall be

> 90K of the nominal bus voltage.

APPLICABILITY: Mhenever the manual alternate reserve source (69 KV) is b

ACTION:

Mith bus voltage less than 90'X nominal, adjust load on the remaining 5uses to maintain steady state bus voltage

> 90K limit.

SURVEILLANCE RE UIREMENTS 4.8.3. 1 No additional surveillance requirements other than those required by Specifications 4.8. l.l. 1 and 4.8. 1.2.

Shared.with D.

C.

Cook Unit l.

D.

C.

COOK -.UNIT 2 3/4 8-15 Amendment No. 36